综采工作面供电系统整定计算一、按允许电压损失选择电缆截面积1、 1# KBSGZY-2000/6/1.14移动变电站变压器百分阻抗Ux%=5.4%,二次额定电压E2e=1.19KV、IE=344A、额定容量Sbe=2000KVA 、Pd=9600W:移动变电站电阻压降百分数URUR= Pd/10Sbe=9600/102000=0.48%移动变电站电阻压降百分数UdUd= =5.378%Ie2000/1.140.80.91250(A)Ub%= Ib /Ibe (Urcosb+UxSinb)=1250/1273 (0.480.85+5.3780.5268) =2.978Ub=Ub%E2e/100=2.9781190/100=35.43V电机正常运行时允许电压损失不超过额定电压的10%,即允许电压损失为:Uy=0.1Ue=0.11140=114V电缆支线上电压损失: (1) 、破碎机电缆选择-1140V组合开关破碎机Pe=375KW lz=215m查表 MCP-395橡套电缆的电抗X0=0.076/km,阻抗RO=0.195/km Uz= Pe lz (RO+XOtg)=3750.215(0.195+0.0760.6179)/1.14=17.1V允许电压损失:Uyg=Uy-Ub-Uz=114-35.43-17.1=61.47V需要最小截面:Ag=0.0235375250103/61.47114031.43mm2Ag=31.43mm2Ae=95mm2所以选择电缆截面积95mm2满足要求.(2) 、 转载机电缆选择-1140V组合开关转载机Pe=400KW lz=200m查表 MCP-395橡套电缆的电抗X0=0.076/km,阻抗RO=0.195/kmUz= Pe lz (RO+XOtg)=4000.2(0.195+0.0760.6179)/1.14=16.9V允许电压损失:Uyg=Uy-Ub-Uz=114-35.43-19=61.6V需要最小截面:Ag=0.0235400250103/61.6114033.22mm2Ag=33.22mm2Ae=95mm2所以选择电缆截面积95mm2满足要求.2、2#移动变电站KBSGZY4000/6/3.3阻抗电压Ux%5.5二次额定电压E2e=3.45KV、额定容量Sbe=4000KVA 、Pd=8300W:移动变电站电阻压降百分数URUR= Pd/10Sbe=8300/104000=0.26%移动变电站电阻压降百分数UdUd= =5.4%Ie3300/3.450.80.9804(A)Ub%= Ie /Ibe (Urcosb+UxSinb)=325/732 (0.260.85+5.40.5268) =1.35Ub=Ub%E2e/100=1.353450/100=46.57V电机正常运行时允许电压损失不超过额定电压的10%,即允许电压损失为:Uy=0.1Ue=0.13300=330V刮板机电缆选择-(1) 、 3300V组合开关刮板机尾电机高速Pe=700KW lz=500m查表 MCPT-370橡套电缆的电抗X0=0.06/km,阻抗RO=0.306/kmUz= Pe lz (RO+XOtg)=7000.5(0.306+0.060.6179)/3.3=36.38V (2) 、 3300V组合开关刮板机尾电机低速Pe=350KW lz=500m查表 MCPT-370橡套电缆的电抗X0=0.06/km,阻抗RO=0.306/kmUz= Pe lz (RO+XOtg)=3500.5(0.306+0.060.6179)/3.3 (3) 、3300V组合开关刮板机头电机高速Pe=700KW lz=250m查表 MCPT-370橡套电缆电抗X0=0.06/km,阻抗RO=0.306/kmUz= Pe lz (RO+XOtg)=7000.25(0.306+0.060.6179)/3.3=18.19V允许电压损失:Uyg=Uy-Ub-Uz=330-46.57-18.19=265.19V需要最小截面:Ag=0.0235700250103/265.1933005.04mm2Ag=5.04mm2Ae=70mm2(4) 、3300V组合开关刮板机头电机低速Pe=350KW lz=250m查表 MCPT-370橡套电缆的电阻,电抗X0=0.06/km,阻抗RO=0.306/kmUz= Pe lz (RO+XOtg)=3500.25(0.306+0.060.6179)/3.3=9.09V允许电压损失:Uyg=Uy-Ub-Uz=330-46.57-9.09=274.34V需要最小截面:Ag=0.0235350250103/274.3433002.27mm2Ag=2.27mm2Ae=70mm2所以选择电缆截面积70mm2满足要求.(4) 、采煤机电缆选择-3300V组合开关采煤机Pe=1122KW lz=500m查表 MCPT-395橡套电缆的电抗X0=0.076/km,阻抗RO=0.195/kmUz= Pe lz (RO+XOtg)=11220.5(0.195+0.0760.6179)/3.3=41.9V允许电压损失:Uyg=Uy-Ub-Uz=330-41.08-41.9=247.2V需要最小截面:Ag=0.02351122500103/247.2330016.1mm2Ag=16.1mm2Ae=95mm2所以选择电缆截面积95mm2满足要求.二、供电系统最远点两相短路电流计算1、660V供电系统最远点两相短路电流计算(1)、查表MYP-335橡套电缆的电阻R1,电抗r0=0.08/km阻抗=0.52/km,(变电站列车)电缆长度L -0.8km, R1=r0L=1.180.520.8=0.472X1=X0L=0.080.8=0.06(2)、查表MYP-335橡套电缆的电阻-R1,电抗-r0=0.08/km阻抗=0.52/km,(列车工作面148#支架)电缆长度L- 0.4kmR2=r0L=1.180.520.4=0.236X2=X0L=0.080.4=0.03(3)、查表KBSGZY-500/6/0.69矿用变压器百分阻抗Ux%=3.77,二次额定电压E2e=0.69KV、额定容量Sbe=500KVA、空载损耗Pd=3100W:电抗 Xb=Ux%=3.77=0.052 阻抗 Rb= =0.0059(4)、两相短路电流=R1+R2Rb =0.472+0.236+0.0059=0.7139 =X1+X2+ Xb=0.06+0.03+0.052=0.142ZD=I=472.6 A 三相短路电流I=I=545.7A660V馈电开关整定:负荷总功率为66KWIe66103/1.7326600.70.8103A IzdIe COS=0.7 =0.8故:低压过电流整定 Izd100A灵敏校验,取两相短路电流校验:KlmI(2)/Izd472/1004.721.5 合格2、1140V供电最远点两相短路电流(负荷转载机、破碎机、乳化泵、喷雾泵)(1)(1140V组合开关破碎机)215m查表 MYP-395橡套电缆的电阻-R1,电抗-r0=0.076/km,阻抗=0.195/km,(变电站列车)电缆长度L -0.215km, R1=r0L1=1.180.1950.215=0.0184 X1= X0L1=0.0760.215=0.0163 (2)查表1#KBSGZY-2000/6/1.14移动变电站变压器百分阻抗Ux%=5.4%,二次额定电压-E2e=1.19KV、额定容量Sbe=2000KVA 、Pd=9600W:电抗 Xb=Ux%=5.4=0.0325 阻抗 Rb= =0.007(3)两相短路电流=R1Rb =0.0184+0.007=0.0254 =X1 + Xb=0.016+0.0325=0.0485I=11049A 三相短路电流I=I=12758A(3)、采煤机2#变压器阻抗:查表:KBSGZY4000/6/3.3阻抗电压Ux%5,空载损耗Pd=2750W二次额定电压-E2e=3.45KV、额定容量Sbe=1600KVA:电抗 Xb=Ux%=5=0.1078阻抗 Rb= =0.0127从最远点至变压器之间的低压电缆阻抗:MCPT395+125 R00.195/KM,X00.076/KM,(3300V组合开关采煤机)实际长度为500米,Rd1.180.1950.50.115 Xd0.0760.50.038短路点的每项总电阻和总电抗分别为:Rd+ Rb+Rg0.115+0.0127+0.080.207Xd+ Xb +Xy0.038+0.1078+0.2380.3838采煤机2#变压器短路电流计算:最小的两相短路电流Is(2)3965A三相短路电流I=I=4578A4、移动变电站过电流整定计算:1、 KBSGZY-2000KVA移变(负荷转载机400KW、破碎机375KW、乳化泵3315KW、喷雾泵2160KW):负荷总功率为2000KW COS=0.8 =0.9高压侧:Ie2000/60.80.9267(A) 取Izd260(A) 低压侧:Ie2000/1.7321.190.80.91351A 取Izd1200(A) 灵敏校验:KlmI(2)/Izd10.61.5 合格2、 KBSGZY-4000KVA移变负荷-煤机、刮板机:负荷总功率为3300KW高压侧:Ie3300/60.80.9441(A) 取Izd440(A)低压侧:Ie3300/3.30.80.9804(A)取Izd800(A) 灵敏校验:KlmI(2)/Izd=5.721.5 合格5、变压器容量的选择(1)采煤机、刮板输送机KBSGZY-4000KVA变压器容量计算:SB=对于综采面:COSPj=0.72 KX=0.4+0.6 P为最大电机功率数所以:KX=0.4+0.6=0.53 SB=2416KVA 4000KVA所以选用容量为KBSGZY-40
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 纤维调施胶干燥工岗位操作规程考核试卷及答案
- 油料计量员职业考核试卷及答案
- 新质生产力新产业新业态新模式
- 硝基苯装置操作工主管竞选考核试卷及答案
- 环丁砜装置操作工晋升考核试卷及答案
- 2025年新能源汽车电池质量认证体系研究报告
- 历年高中竞赛试题及答案
- 光学普通磨工技术考核试卷及答案
- 抗疫知识竞赛试题及答案
- 洞察2025年B2B市场采购决策者需求与沟通策略研究
- 2025年广西中考道德与法治试题答案详解讲评课件
- 2024全国司法考试真题
- 罗伊模式在肿瘤个案护理中的应用
- T细胞指标:脓毒症侵袭性念珠菌感染诊断与预后评估的新视角
- 2025新会计法培训
- 2025年全国新高考I卷真题1卷语文+数学+英语试卷(含答案)
- 中国山西省危险废物处理市场调查报告
- 成人床旁心电监护护理规程
- 2025年高考全国一卷语文试题真题文档版(含答案)
- 公司财务u盾管理制度
- 拍摄肖像授权协议书
评论
0/150
提交评论