1、关于低压电容器柜设计制作与选型的规定为了保证对低压电容器的可靠保护,根据相关规范以及GB50227-2008并联电容器装置设计规范、GB/T22582-2008电力电容器低压功率因数补偿装置(代替JB7113-93)、GB/T15576-2008低压成套无功功率补偿装置,对常用低压电容器柜的设计、制作以及出厂整定作如下补充规定:一、对电容器柜总路刀熔开关熔芯及母排的配置见下表:表1.1电网Ue=400V50Hz不带电抗器序号电容器组额定容量Qcn(kVar)电容器额定电压Ucn(V)电容器组有效容量Qc=(Ue/Ucn)珠Qcn(kVar)额定电流Icn=Qcn/V3/Ucn(A)实际电流Ic

2、=(Ue/Ucn)*Icn熔芯规格In心1.5Ic(A)铜排规格TMY-1360400360.00519.63519.6380050*62450284.44461.89410.5763050*53480250.00433.03360.8563050*54300400300.00433.03433.0370050*55450237.04384.91342.1463040*56480208.33360.85300.7150040*57250400250.00360.85360.8563040*58450197.53320.76285.1250040*49480173.61300.71250.594

3、0040*410200400200.00288.68288.6850040*411450158.02256.61228.1040030*412480138.89240.57200.4740030*413160400160.00230.95230.9540030*314450126.42205.29182.4830030*315480111.11192.46160.3825030*316120400120.00173.21173.2130025*31745094.81153.96136.8625025*31848083.33144.34120.2820025*319100400100.00144

4、.34144.3425020*32045079.01128.30114.0520020*32148069.44120.28100.2420020*3228040080.00115.47115.4720020*32345063.21102.6491.2416020*32448055.5696.2380.1912520*3表1.2电网Ue=400V50Hz电抗率5.4%、5.7%、7%序号电容器额定容量Qcn(kVar)电容器额定电压Ucn(V)电容器组有效容量Qc=(Ue/Ucn)*(Uc/Ucn)*Qcn(kVar)额定电流Icn=Qcn/V3/Ucn(A)实际电流Ic=(Uc/Ucn)*Ic

5、n熔芯规格In心1.5Ic(A)铜排规格TMY-1360450301.51461.89435.2170050*52480265.00433.03382.5170050*53525221.52395.91319.7463050*54300450251.26384.91362.6763040*55480220.83360.85318.7563040*56525184.60329.92266.4550040*57250450209.38320.76302.2350040*48480184.03300.71265.6350040*49525153.83274.94222.0450040*4102004

6、50167.51256.61241.7840030*411480147.22240.57212.5040030*412525123.07219.95177.6440030*413160450134.00205.29193.4331530*314480117.78192.46170.0031530*31552598.45175.96142.1131530*316120450100.50153.96145.0725025*31748088.33144.34127.5025025*31852573.84131.97106.5820025*31910045083.75128.30120.8920020

7、*32048073.61120.28106.2520020*32152561.53109.9788.8220020*3228045067.00102.6496.7116020*32348058.8996.2385.0016020*32452549.2387.9871.0516020*3表1.3电网Ue=400V50Hz电抗率13.7%、14%序号电容器额定容量Qcn(kVar)电容器额定电压Ucn(V)电容器组有效容量Qc=(Ue/Ucn)*(Uc/Ucn)*Qcn(kVar)额定电流Icn=Qcn/V3/Ucn(A)实际电流Ic=(Uc/Ucn)*Icn熔芯规格In心1.5Ic(A)铜排规格

8、TMY-1360480290.75433.03419.6763050*52525243.04395.91350.8163050*53300480242.29360.85349.7363040*54525202.54329.92292.3450040*55250480201.91300.71291.4450040*46525168.78274.94243.6250040*47200480161.53240.57233.1540030*48525135.02219.95194.9040030*49160480129.22192.46186.5231530*310525108.02175.96155

9、.9231530*31112048096.92144.34139.8925025*31252581.01131.97116.9420025*31310048080.76120.28116.5820020*31452567.51109.9797.4520020*3158048064.6196.2393.2616020*31652554.0187.9877.9616020*3说明:1、此表未列出的容量,请按相近容量考虑选择。2、QcV80kVar或Qc360kVar时,按相关公式计算所得由设计人员标注在电气图纸上。二、关于电容柜分支回路三相电容器的保护元件及保护定值的配置见下表:表2.1电网Ue=

10、400V50Hz不带电抗器(三相电容器)序号电容器组额定容量Qcn(kVar)电容器额定电压Ucn(V)电容器组有效容量Qc=(Ue/Ucn)球Qcn(kVar)额定电流Icn=Qcn/V3/Ucn(A)实际电流Ic=(Ue/Ucn)*Icn熔芯规格In心1.5Ic(A)热继整定值(A)导线规格BVR(mm2)16040060.0086.6186.6116010050245047.4176.9868.431257935348041.6772.1760.14100692545040050.0072.1772.171258335545039.5164.1557.021006625648034.72

11、60.1450.12100582574540045.0064.9564.951007525845035.5657.7451.32805916948031.2554.1345.11805216103040030.0043.3043.308050161145023.7038.4934.216339101248020.8336.0930.07503510132540025.0036.0936.096341161445019.7532.0828.515033101548017.3630.0725.0640296162040020.0028.8728.875033101745015.8025.6622.

12、81402661848013.8924.0620.0532234191840018.0025.9825.98403062045014.2223.0920.53322442148012.5021.6518.0432214221640016.0023.0923.09402762345012.6420.5318.25322142448011.1119.2516.0425184251440014.0020.2120.21322342645011.0617.9615.9725184274809.7216.8414.0325164281240012.0017.3217.3232204294509.4815

13、.4013.6925164304808.3314.4312.0320144表2.2电网Ue=400V50Hz电抗率5.7%、7%(三相电容器)序号电容器组额定容量Qcn(kVar)电容器额定电压Ucn(V)电容器组有效容量Qc=(Ue/Ucn)*(Uc/Ucn)*Qcn(kVar)额定电流Icn=Qcn/V3/Ucn(A)实际电流Ic=(Ue/Ucn)*Icn熔芯规格In心1.7Ic(A)热继整定值(A)导线规格BVR(mm2)168.145057.0487.3782.331609550248050.1381.9172.361258335352541.9074.8960.48100703546

14、0.845050.9278.0173.501258535548044.7673.1364.601257435652537.4166.8654.00100622575045041.8864.1560.451007035848036.8160.1453.131006125952530.7754.9944.41805116104545037.6957.7454.4010063251148033.1354.1347.818055251252527.6949.4939.978046161340.845034.1752.3549.3210057251448030.0349.0843.35805016155

15、2525.1144.8736.24634216163445028.4843.6241.108047161748025.0340.9036.136342101852520.9237.3930.20503510193045025.1338.4936.276342162048022.0836.0931.886337102152518.4632.9926.65503110222545020.9432.0830.225035162348018.4030.0726.565031102452515.3827.4922.2040266252045016.7525.6624.185028102648014.72

16、24.0621.25402462752512.3121.9917.7632204281845015.0823.0921.76402562948013.2521.6519.13322243052511.0819.8015.9932184311645013.4020.5319.34402263248011.7819.2517.0032204335259.8517.6014.2125164341445011.7317.9616.92321943548010.3116.8414.8825174365258.6115.4012.4325144371245010.0515.4014.51251743848

17、08.8314.4312.7525154395257.3813.2010.6620124表2.3电网Ue=400V50Hz电抗率14%(三相电容器)序号电容器组额定容量Qcn(kVar)电容器额定电压Ucn(V)电容器组有效容量Qc=(Ue/Ucn)*(Uc/Ucn)*Qcn(kVar)额定电流Icn=Qcn/V3/Ucn(A)实际电流Ic=(Ue/Ucn)*Icn熔芯规格In心1.7Ic(A)热继整定值(A)导线规格BVR(mm2)167.848054.7681.5579.041609150252545.7774.5666.071257635362.448050.4075.0672.7412

18、58435452542.1368.6260.81125701655048040.3860.1458.291006725652533.7654.9948.7280561674548036.3454.1352.461006025852530.3849.4943.8580501693148025.0437.2936.146342101052520.9334.0930.21503510113048024.2336.0934.976340101252520.2532.9929.23503410132548020.1930.0729.145034101452516.8827.4924.3650286152

19、2.548018.1727.0626.23503061652515.1924.7421.9340256172048016.1524.0623.32402761852513.5021.9919.4940226191848014.5421.6520.98402462052512.1519.8017.5432204211648012.9219.2518.65322142252510.8017.6015.5932184231448011.3116.8416.3232194245259.4515.4013.642516425124809.6914.4313.9925164265258.1013.2011

20、.6920134说明:1、此表未列出的容量,请按相近容量考虑选择。2、QcV12kVar或Qc68kVar时,按相关公式计算所得由设计人员标注在电气图纸上。三、关于电容柜分支回路单相电容器的保护元件及保护定值的配置见下表:表3.1电网Ue=400V50Hz不带电抗器(单相电容器)序号电容器组额定容量Qcn(kVar)电容器额定电压Ucn(V)电容器组有效容量Qc=(Ue/Ucn)2*Qcn(kVar)额定电流Icn=Qcn/Ucn(A)实际电流Ic=(Ue/Ucn)*Icn熔芯规格In心1.5Ic(A)热继整定值(A)导线规格BVR(mm2)12023020.0086.9686.9616010

21、050226015.6576.9268.051257835327513.9972.7360.83100702541823018.0078.2678.261259035526014.0969.2361.241007025627512.5965.4554.74100632571623016.0069.5769.571258035826012.5261.5454.441006325927511.1958.1848.66805616101523015.0065.2265.2210075351126011.7457.6951.048059251227510.4954.5545.6280521613122

22、3012.0052.1752.17806025142609.3946.1540.83634716152758.3943.6436.50634210161023010.0043.4843.48805016172607.8338.4634.02633910182757.0036.3630.41503510197.52307.5032.6132.61503810202605.8728.8525.5240296212755.2527.2722.81402662252305.0021.7421.7440256232603.9119.2317.0132204242753.5018.1815.2132174

23、2532303.0013.0413.0425154262602.3511.5410.2125122.5272752.1010.919.1220102.52812301.004.354.351052.5292600.783.853.401042.5302750.703.643.041032.5表3.2电网Ue=400V50Hz电抗率5.7%、7%(单相电容器)序号电容器组额定容量Qcn(kVar)电容器额定电压Ucn(V)电容器组有效容量Qc=(Ue/Ucn)*(Uc/Ucn)*Qcn(kVar)额定电流Icn=Qcn/Ucn(A)实际电流Ic=(Ue/Ucn)*Icn熔芯规格In心1.7Ic(

24、A)热继整定值(A)导线规格BVR(mm2)12025017.9480.0078.021609050226016.5976.9272.131258335327514.8372.7364.48125743541825016.1572.0070.211258132526014.9369.2364.921257535627513.3565.4558.03100673571625014.3564.0062.411257235826013.2761.5457.701006635927511.8658.1851.581005925101525013.4660.0058.5110067351126012.4

25、457.6954.1010062251227511.1254.5548.361005625131225010.7748.0046.81805425142609.9546.1543.28805016152758.9043.6438.6980441616102508.9740.0039.01804516172608.2938.4636.07634116182757.4136.3632.24633716197.52506.7330.0029.26503410202606.2228.8527.05503110212755.5627.2724.185028102252504.4920.0019.5040226232604.1519.2318.0332216242753.7118.1816.12321942532502.6912.0011.7020134262602.4911.5410.8220124272752

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论