DATASHEET

6800B系列交流电源/分析仪

375至1750VA

ProvidesacompleteACandDCpowerandmeasurementsolution

ProtectvaluableDUTswithextensiveprotectionfeatures

Easytousegraphicaluserinterface(GUI)

Page

PAGE

2

TheCompleteACPowerTestSolution

KeysightTechnologies,Inc.,ACpowersource/analyzersprovideacompleteACtestsolution.AsACsources,theycombinethecapabilitiesofapoweramplifierandanarbitrarywaveformgenerator.Thisallowsyoutosimulatenormalwaveformsandmanytypesofdistortedpowerwaveforms.Thebuiltinpoweranalyzercombinesthecapabilitiesofamultimeter,oscilloscope,harmonicanalyzerandpoweranalyzer.TheseinstrumentsmayalsobeusedtoproduceDCpower,eitheraloneorasaDCoffsettoanACwaveform.

SinceyourproductwillhavetooperateintherealworldofunpredictableACpower,youneedtodesignandverifyitscorrectoperationunderawiderangeofACpowerinputs.Brownouts,dropouts,sags,andotherirregularitiesarenotunusualinmanycommunitiestoday.KeysightACpowersource/analyzershavethefeaturesneededtoeasilyaccomplishthistestgoaleitherinanR&Denvironmentoronthemanufacturingtestfloor.Ifyouplantosellyourproductsinaworldwidemarket,youwillalsoneedtotestthematthelinevoltagesandfrequenciesforwhichtheywilleventuallyoperate.Thereisalsoadditionaltestingneededtomeetregulatoryrequirementsforsaleintosomecountries.

KeysightACpowersource/analyzersofferacompletesolutionforACpowertesting,helpingyoutosimplifythisimportanttask.Theseinstrumentscombinethefeaturesofapoweramplifierandarbitrarywaveformgeneratortogiveyoutheabilitytodoalloftheteststhatyouneed.Therearemanystandardpreprogrammedwaveforms,oryoucanusethetransientgenerationsystemtosimulatesophisticatedandrepeatableAClinedisturbances.DCpowercanalsobegenerated,eitherasaDCoffsetorasapureDCsignal.

PowerfulBuilt-inMeasurementCapabilities

KeysightACpowersource/analyzershaveextensive16-bitprecisionmeasurementcapabilitieswhichwouldnormallyrequireanumberofcomplexmeasurementinstruments,includingaDMM(digitalmultimeter),oscillo-scope,poweranalyzer,andharmonicanalyzer.Theprecisionmeasurementsinclude:

rms,DC,AC+DCvoltageandcurrent

Peakvoltageandcurrent

Real,apparent,andreactivepower

Harmonicanalysisofvoltageandcurrentwaveformsprovidingamplitudeandphaseuptothe50thharmonic

THD(totalharmonicdistortion)

Triggeredacquisitionofdigitizedvoltageandcurrent

UsingthemeasurementcapabilitiesofaKeysightACpowersource/analyzersimplifiesyourtestsetupsandhelpsyouobtainaccuratedataquickly.

DualpoweranalyzerOption020

Thepowerfulbuilt-inpowermeter/analyzerinKeysightACpowersource/analyzersprovideseverythingthatyouneedtomakeACmeasurementsattheACinputtoyourDUT.Formanytestscenarios,thisistheextentoftheACanalysisrequired.

Sometestscenarios,however,requireACmeasurementstobemadeatboththeACinputandtheACoutputoftheDUT.Option020providesanadditionalpoweranalyzer,completewithaprecisioncurrentshunt,whichcanbeconnectedanywhereyouneedit.ThissecondanalyzercanevenbeusedfortestswheretheACpowersource/analyzerisnotprovidingpower,thusexpandingtheusefulnessofthisinstrumenttomanymoretestconfigurations.Theadditionalanalyzerisequivalentinspecificationsandcapabilitiestothestandardanalyzer.

Usingthedualpoweranalyzeroptioninsteadofanadditionalpoweranalyzerinstrumentexternallyismorethanjustconvenient.Measurementsonallfourmeasurementchannels(ACsourceoutputvoltageandcurrent,anddualpoweranalyzervoltageandcurrentinputs)areinherentlysynchronizedwiththeACpowersource/analyzersoutputwaveform.Thisprecisionwouldbedifficulttoachieveusingseparatemeasurementinstruments.

Examplesdualpoweranalyzerapplications

Completetestingofuninterruptiblepowersources(UPS)

EfficiencytestingofDCpowersupplies

EfficiencytestingofACpowersources

Efficiencytestingoftransformers

Safetytestingoftransformers

LinedisturbanceandbrownouttestingofDCpowersupplies

LinedisturbanceandbrownouttestingofACpowersources

Sleepmodecurrentmonitoring

Independentpoweranalyzer

Sleepmodecurrentmonitoring

Page

PAGE

4

Manyelectronicproductshavepower-savingorsleepmodes.Inthismode,thedevicedrawsonlyenoughpowertobeabletorecognizea“wake-up”signal,andthenexecuteasmooth“wake-up”.Thepowerdrawninthismodeisacriticalparameter,andtheabilitytoaccuratelymonitoritisimportant.Theaccessoryprecisioncurrentshuntthatissuppliedwithoption020ismountedinsuchawaytomakeiteasyforyoutoreplaceitwithaprecisionresistorofyourchoice.Bydoingthis,youcanconfigurethesystemtoaccuratelymonitorextremelylowcurrents.Thisprovidesaneasywayforyoutoprofilethecurrentdrawinallmodesofyourproduct’soperation.SinceKeysight6811B-6813BACpowersource/analyzersproduceDCpoweraswellasACpower,portablebatteryoperatedproductscanalsobetestedwiththisconfiguration.

UPS(uninterruptiblepowersource)testing

ThedualpoweranalyzeroptionprovidesmanyimportantbenefitsforUPStesting.SincethekeytocorrectUPSoperationishavingtheoutputreactproperlytochangesontheinput,beingabletomonitortheoutputrelativetotheinputsimplifiestesting.Forexample,commandsareavailabletoenablecalculationofUPStransfertime,andthephasedifferencebetweentheUPSinputandoutputvoltage.KeysightACpowersource/analyzersalsohaveprogrammableoutputimpedance,enablingtheUPSdesignertoverifyproductstabilityoverawiderangeofAClineimpedance.

Graphicaluserinterface(GUI)

Whenyouneedtorunavarietyoftests,studytheresultscarefully,andthenrunmoretestswithslightlyvariedconditions,writingcomputerprogramsusingtheextensiveSCPIcommandsetmayseemburdensome.ThisiswhenyoushoulddownloadthelatestcopyoftheKeysightACpowersource/analyzergraphicaluserinterfacefrom

TheACpowersource/analyzerGUImakesitquickandeasytosettheoutputofyourACpowersource/analyzer,beitfromastoredwaveformorwithawaveformthatyoucreateusingyourmouse.TheGUIalsoallowsyoutoseetheoutputoftheACpowersource/analyzeringraphicalform,savetheresults,ordumpthemdirectlyintoaMicrosoftExcelfile.

MicrosoftExcellink

ThedirectExcellinkfeaturewasrecentlyaddedtomeetthecurrentneedsofR&Dengineers.Itmakesiteasytokeeptheresultsofmanytests,andmakesthemeasilyretrievable.Withit,thetestrecordsresultingfromchangingconditionscanbekeptinoneplaceandeasilycompared.

Accesstorawdataoftenhelpsinfullyunderstandingtestresults.Forexample,smalllocalpeaksmaynotbeevidentinprocesseddata.V,Iandphaseresultsfromharmonic

measurementsareparticularlysusceptibletonotshowingthecompletestoryinagraphicalrepresentation.

MicrosoftExceloffersawidevarietyofdatamanipulationandgraphicalcapabilitiesthatcanhelpanengineergainthefullestunderstandingfromthetestdata.

Testsuiteforavionicsequipment

Page

PAGE

5

KeysightACpowersource/analyzersarewellsuitedfortestingequipmentintendedforuseintheavionicsindustrywhichoperateatnominally400Hz.OneofthespecialrequirementsthatmanymanufacturersinthisindustrymustconcernthemselveswithistestingtomeetRTCADO-160standards.

ThesestandardsinvolvebothACandDCimmunitytests.TheACpowersource/analyzerGUIincludesasectiondevotedtothesetests.Byusingthistool,youcanquicklystepthroughtherequiredset-upswithconfidence.

Extensiveprotectiontopreventloaddamage

Inadditiontoovercurrent,overvoltage,overpowerandovertemperatureprotection,the6800seriesoffersoutputdisconnectrelaysandremoteinhibitcapability(quicklydisablingtheoutputoftheACpowersource/analyzersviaaTTLsignal)toprotectthedeviceundertest.

ApplicationInformation

The6800seriescanhelpyoutestandimproveyourproducts.Youcaneasilyperform:

Statictesting–generatingandmeasuringvoltage,frequency,andlinecurrentformeetingworldwidespecifications.

Dynamictesting–generatingAClinetransientsforlimittestinganddesignverification.

Specialtytesting–measuringcurrentharmoniccontentandcreatingcustomACpowerwaveforms(suchasacombinedAC+DCsignaltosimulateatelephonering).

Precomplianceregulatorytesting—measuringcurrentharmonics,voltagefluctuationsandflickeremissionsandgeneratingvoltageandfrequencydisturbancesandinterharmonicstodetermineproductimmunity.

DevelopmentengineersandtestprofessionalsinawidevarietyofindustriesuseACpowersource/analyzers.Hereareafewexamples:

Avionics–Instrumentation,ATEteststations

Computerproducts–Computers,monitors,peripherals

Consumerproducts–Homeappliances,audioandvideoequipment,heating/coolingcontrols

Electricalproducts–Relays,transformers,powercomponents,firealarms

Lightingproducts–Electronicballasts,compactfluorescentbulbs,timers

Motors–ACmotors,electroniccontrollers

Powerproducts–AC/DCadapters,AC/DCpowersupplies,PBXpowersupplies,uninterruptiblepowersupplies

Telecomproducts–RFamplifiers,CATVdevices,MUX’s,routers,switches

KeysightACpowersource/analyzerwithdualpoweranalyzeroption(sideview)

Dualpoweranalyzerinput(forVandI)

Keysightsuppliedcable

(forVandI)

Keysightsuppliedshunt

ACin

AC

Equipmentundertest

ACline

Output

Shunt

Load

Line Load

sourceoutput

cables

(customersupplied)

Figure1.TestconfigurationofefficiencymeasurementusinganKeysightACsourcewiththe020dualpoweranalyzeroption.

ACPowerSource/AnalyzerGraphicalUserInterface

Page

PAGE

6

Figure2.Inrushcurrentmeasurement.

Figure4.Voltageslewcontrol(brownout).

Figure3.Ringervoltage(DC+AC)generation.

Figure5.OnecycleACmainsdropout.

Figure6.Userdefinedwaveform:noisewithspikes. Figure7.TestingofUPSinputandoutputusingdualpoweranalyzer-

Option020.

Specifications

Forasinewavewitharesistiveloadat0°to40°C,withinanoutputfrequencyrangeof45Hzto1000Hz,andinACcoupledmodeaftera30minutewarm-upunlessotherwisenoted.

Page

PAGE

7

Specifications

(At0°to40°Cunlessotherwisespecified)

6811B

6812B

6813B

Numberofphases

1

1

1

Outputratings(Maximum)

–Power

375VA

750VA

1750VA

–rmsvoltage

300V

300V

300V

–rmscurrent

3.25A

6.5A

13A

–Repetitiveandnon-repetitivepeakcurrent

40A

40A

80A

–Crestfactor

12

6

6

–Loadpowerfactorcapability

0to1

0to1

0to1

–DCpower

285W

575W

1350W

–DCvoltage

±425VA

±425V

±425V

–DCcurrent

2.5A

5.0A

10.0A

Outputfrequencyrange1

DC;45Hzto1kHz

DC;45Hzto1kHz

DC;45Hzto1kHz

Constantvoltagerippleandnoise(20kHzto10MHz)

–60dB(relativetofullscale)

–60dB(relativetofullscale)

–60dB(relativetofullscale)

Lineregulation(%offullscale)

0.1%

0.1%

0.1%

Loadregulation(%offullscale)

0.5%

0.5%

0.5%

Maximumtotalharmonicdistortion

0.25%at50/60Hz

0.25%at50/60Hz

0.25%at50/60Hz

1%worstcase

1%worstcase

1%worstcase

45to1kHz

45to1kHz

45to1kHz

Programmingaccuracy

(At25°±5°C)

6811B

6812B

6813B

RMSvoltage(%ofoutput+offset)

0.15%+0.3V

(45to100Hz)

0.15%+0.3V

(45to100Hz)

0.15%+0.3V

(45to100Hz)

0.5%+0.3V

(>100to500Hz)

0.5%+0.3V

(>100to500Hz)

0.5%+0.3V

(>100to500Hz)

1%+0.3V

(>500to1000Hz)

1%+0.3V

(>500to1000Hz)

1%+0.3V

(>500to1000Hz)

DCvoltage

0.1%+0.5V

0.1%+0.5V

0.5%+0.3V

Frequency

0.01%+10μHz

0.01%+10μHz

0.01%+10μHz

1.ProductmaybeoperatedbetweenDCand45Hzsubjecttocertainderatings.Measurementsmaybeextendedto4.5Hzatfullaccuracyonlybyselectingadigitizationrateof250μsperpoint.Frequencycontentofthemeasuredsignalmustbelimitedto4kHzorlesstoavoidaliasingeffects.

Specifications(Continued)

Forasinewavewitharesistiveloadat0°to40°C,withinanoutputfrequencyrangeof45Hzto1000Hz,andinACcoupledmodeaftera30minutewarm-upunlessotherwisenoted.

Page

PAGE

8

Measurementaccuracy

(At25°±55°C)

6811B

6812B

6813B

Rms.voltage(45to100Hz)

0.03%+100mV1

0.03%+100mV1

0.03%+100mV1

DCvoltage

0.05%+150mV1

0.05%+150mV1

0.05%+150mV1

RMScurrent(45to100Hz)2

–Highrange

0.05%+10mA

0.05%+10mA

0.05%+10mA

–Lowrange

0.05%+1.5mA

0.05%+1.5mA

0.05%+1.5mA

Power(VA)(45to100Hz)2

–Highrange

0.1%+1.5VA+12mVA/V

0.1%+1.5VA+12mVA/V

0.1%+1.5VA+12mVA/V

–Lowrange

0.1%+1.5VA+1.2mVA/V

0.1%+1.5VA+1.2mVA/V

0.1%+1.5VA+1.2mVA/V

Power(watts)(45to100Hz)2

–Highrange

0.1%+0.3W+12mW/V

0.1%+0.3W+12mW/V

0.1%+0.3W+12mW/V

–Lowrange

0.1%+0.3W+1.2mW/V

0.1%+0.3W+1.2mW/V

0.1%+0.3W+1.2mW/V

Frequency

0.01%+0.01Hz

0.01%+0.01Hz

0.01%+0.01Hz

Powerfactor

0.01

0.01

0.01

Currentmagnitude(lowrange)

–Fundamental

0.03%+1.5mA

0.03%+1.5mA

0.03%+1.5mA

–Harmonics2to49

0.03%+1mA+0.2%/kHz

0.03%+1mA+0.2%/kHz

0.03%+1mA+0.2%/kHz

Currentmagnitude(highrange)

–Fundamental

0.05%+5mA

0.05%+5mA

0.05%+5mA

–Harmonics2to49

0.05%+3mA+0.2%/kHz

0.05%+3mA+0.2%/kHz

0.05%+3mA+0.2%/kHz

Supplementalcharacteristics

(Non-warrantedcharacteristicsdeterminedbydesignandusefulinapplyingtheproduct)

6811B

6812B

6813B

Averageprogrammingaccuracy

(%ofoutput+offset)rmscurrent

1.2%+50mA

1.2%+50mA

1.2%+50mA

Averageprogrammingresolution

–rmsvoltage

125mV

125mV

125mV

–DCvoltage

250mV

250mV

250mV

–Overvoltageprogramming(OVP)

2Vpeak

2Vpeak

2Vpeak

–rmscurrent

2mA

4mA

4mA

–Peakcurrent

1.25mA

25mA

25mA

–Outputfrequency

10μHz

10μHz

10μHz

–Phase

N/A

N/A

N/A

ProductmaybeoperatedbetweenDCand45Hzsubjecttocertainderatings.Measurementsmaybeextendedto4.5Hzatfullaccuracyonlybyselectingadigitizationrateof250μsecondsperpoint.Frequencycontentofthemeasuredsignalmustbelimitedto4kHzorlesstoavoidaliasingeffects.

Sel

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

最新文档

评论

0/150

提交评论