版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
1、CommercialUtility PowerUPSUPS BatteriesAir conditioning, Lighting,Mechanical, Building Loads,etc.Network Computer LoadsTransfer SwitchgearGenerator ParallelingControl SwitchgearEmergencyGenerators Selective coordination was first required by the NEC in 1993 for elevator circuits. Amendments to the C
2、ode in 2005 and 2008 strengthened the requirements and expanded them to include emergency and legally required standby systems, as well as critical operations power systems. Selective coordination, as defined in the 2008 NEC, is the “localization of an overcurrent condition to restrict outages to th
3、e circuit or equipment affected, accomplished by the choice of overcurrent protective devices and their ratings or settings.” It is a complicated process of coordinating the ratings and settings of overcurrent protective devices, such as circuit breakers, fuses, and ground fault protection relays, t
4、o limit overcurrent interruption (and the resultant power outages) to the affected circuit or equipment (the smallest possible section of a circuit). In other words, the only overcurrent protective device that should open is the device immediately “upstream” from the circuit/equipment experiencing a
5、n overcurrent condition.Selective Coordination Requirements NEC(2008) 701.18 Coordination: requires “Legally required standby system(s) overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices.”GUtility4000AAPCB1600AAPCB1600AAPCB800AICCB400AMCCBAn over
6、current event (overload, short circuit, or ground fault) here should trip the 400A MCCBATSMCCBs (Molded Case Circuit Breaker) typically instantaneous or Current Limiting Devices.ICCBs (Insulated Case Circuit Breaker) are 30 cycle withstand or up to 4 Cycle Instantaneous.APCBs (Air Power Circuit Brea
7、ker) are typically 30 cycle withstand devices.GUtility4000AAPCB1600AAPCB1600AAPCB800AICCB400AMCCBFault on load side of ATS could see up to 30 cycles of fault current -depending on the Air Power Circuit Breaker settings that is feeding it- and could travel through the ATS and the ATS contacts.ATSIf t
8、he 400A MCCB does not trip/clearATSIn the absence of other means to satisfy selective coordination, the ATS must withstand a fault or even close on potential fault to be properly coordinated. Fuses 2005 NEC 1999 NEC 2002 NEC Local Adoption2005 NEC 8 StatesWVWIMTNDSDWAORNVIDUTAZNMTXCOWYNBM IKYTNMNIAM
9、OARLAMSILINOHALGAKSOKNHMENYPAVADENJMARIFLNCSCVTCALocal Adoption (10)MD2008 NEC 32 StatesM INote: Some local adoption states have earlier than 2005 adoptions in some jurisdictions Basically 2002 NEC but some islands back to 1993 NECCTAKRevised April 19, 2010State Adopted Unincorporated AreasState Ado
10、ptedS. Carolina Code Council adopted 2009 IRC with 2008 NEC 3/22/10 with implementation 1-1-11Expected July 10Expected January 2011 Expected July 2010“ Around 1989 UL introduced an optional 3 cycle test for any over- current protection device.Prior to this, manufactures could test with any over-curr
11、ent device.If a manufacturer didnt test to 3 cycles, they would be required provide a label that lists all breakers that the switch was “coordinated with”.This requirement did not take into consideration air power circuit breakers APCBs. Some of these breakers were 4-5 cycle devices (GE AKR and West
12、inghouse DS) January 9th, 2002 UL introduced an optional short time current rating test.A withstand and a close and withstand test is required to get a UL short time rating.36A.1 A switch marked with a short-time current rating in accordance with 41.20.1 shall be tested under the conditions describe
13、d in 36A.2 -36A.12 and shall withstand the short-time current for the period specified. At the conclusion of the test:28.1 Transfer switch equipment shall perform in an acceptable manner, as intended by the manufacturer, when subjected to an overload test consisting of the number of operations speci
14、fied in Table 28.1, controlling a test current as described in Table 28.2.Table 28.1 Overload TestSwitch rating, amperesNumber of cycles of operationRate of Operation* 0-300301- 400401- 600601- 800801- 16001601- 25002501 and above50505050502531 per minute1 per 2 minutes1 per 3 minutes1 per 4 minutes
15、1 per 5 minutes1 per 5 minutes1 per 5 minutes Device used forDevice rated in amperesPower test currentFactorMotor loads or total system a-c 6 times rated current 0.40- 0.50 Table 28.2 Method of determining test current for overload tests on transfer switches28.4 A cycle is defined as making and brea
16、king the required test current on both the normal and alternate contacts. During the test, the alternate source shall be displaced 120 electrical degrees from the normal source for a 3 phase supply or 180 electrical degrees for a single phase supply.28.6 The minimum on time in each contact position
17、is to be 1/6 second (ten electrical cycles based on a 60Hz source), unless automatic tripping of the over-current device occurs.30.1 A transfer switch shall perform as intended when subjected to an endurance test controlling a test current as described in Table 30.1 and at a rate and number of cycle
18、s described in Tables 30.2 and 30.3.Table 30.1Method of determining test current for endurance tests The test cycle is to be 1 second “on” and 59 seconds “off”. A controller may be operated at a rate of more than 1 cycle per minute if synthetic loads are used or if a sufficient number of banks of la
19、mps controlled by a each bank will cool for at least 59 seconds between successive applications of current.Table 30.2Endurance test cycles for emergency system switches including legally required stand-by systems. 29.1 Transfer switches when tested under the conditions described in 29.2 29.12 shall
20、not attain a temperature at any point high enough to constitute a risk of fire or to damage any materials employed in the device, and shall not show temperature rises at specific points greater than those indicated in Table 29.129.2 For the temperature test the transfer switch is to be operated unde
21、r intended use conditions and is to carry its test current continuously at the test potential specified in Table The test current shall be 100 percent of the rated current. No overlapping fault current of individual devices.This is coordinated properly.In a perfect world this is great.In t
22、his case, since it takes 8 cycles for the upstream breaker to clear the fault, a 3 cycle rated transfer switch is inadequate.ATS Feeder Breaker8 cycles to clearA 30 cycle UL rated Transfer Switch truly gives you complete coordination with any over-current protective device.Utility isLostLoad is fedb
23、y emergencypowerUtility isRestoredUnloadedenginecool down periodEngineshuts down system returnedto normaloperationNELOverlapping NeutralVsNELBreaksBeforeNELMakesNELNELELNNELLNE12NELLNEATS-1Life Safety &SupportBranchesATS-2CriticalBranchesATS-3EquipmentBranchesGEGEGEEmergencyDistributionSwitchgea
24、rGeneratorControl &SynchronizingSwitchgearUtilityDistributionSwitchgearLoadControlCircuitryUtilitySourceGELoss ofEngine #1ATS - 3 ShedsNon-Critical LoadsLNENORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTOBypass/Isolation Switch One-Line Diagram(Normal operating mode)NORMALLOADEMERGENCYNORMISOLA
25、TEATSBPNBPEBPNBPEAUTONORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTONORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTONORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTONORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTOLOAD BYPASSED TO NORMALNORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTOLOAD BYPASS
26、ED TO NORMALNORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTOLOAD BYPASSED TO NORMALNORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTOLOAD BYPASSED TO NORMALNORMALLOADEMERGENCYNORMISOLATEATSBPNBPEBPNBPEAUTOLOAD BYPASSED TO NORMALIf the transfer switch portion is bypassed & isolated to normal and the
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 急诊培训与考核制度
- 第三方人员考核制度
- oa监督与考核制度
- 人事委托后考核制度
- 销售管理岗考核制度
- 统计站人员考核制度
- 护理员培训考核制度
- 任务数目标考核制度
- 机加工企业考核制度
- 员工号晋级考核制度
- idc数据中心运营制度
- 八年级地理下册《东北地区人口与城市的时空格局》教学设计与实施
- 高考化学2026年模拟试卷必刷题汇编-元素及其化合物(解答大题)
- 5.1《四大地理区域的划分》课件-2025-2026学年湘教版地理八年级下册
- 2025年10月自考00138中国近现代经济史试题及答案
- GB/T 25383-2025风能发电系统风力发电机组风轮叶片
- 办事合同协议书
- 江苏省2024年中职职教高考文化统考数学试卷及答案
- 石油化工基础知识课件
- 忠诚宣言:出轨丈夫的保证书
- 三维可视化建模软件gocad的应用
评论
0/150
提交评论