1、Review of Lecture 71. Partial Discharge in Power Capacitors2. Parameters and Standard3. Electrical Detection of PD in CapacitorContents: Parameters to estimate the PD of capacitor Apparent charge, qInception voltage, UiExtinction voltage, UeChange of q with voltage applying time1Power SourceCompensa

2、tion reactor is used in series or parallel with Cx so that to decrease the capacity of testing transformerReview of Lecture 7Currents through L and C while the two elements connected in parallelVoltages across L and C while the two elements connected in series2Review of Lecture 7Detection circuits S

3、traight detection circuitsBalanced detection circuit3Review of Lecture 7Some problems need to be noticedDetection impedances is required to withstand large current.Several detection impedances are needed to match the capacitor samplesConnection types of capacitor elements influence detection results

4、.4Lecture 8 PD Detection in Power Transformers电力变压器的局部放电及测量5Contents1. Significance of PD detection in Transformer电力变压器测量局放的重要性2. PD Propagation in Windings4. Detection Circuits for Transformers5. Calibration6. The Influence of Discharges in Bushing3. Test Procedure and Permissible Apparent Charge7.

5、 Electrical Location of PD in Transformers局部放电在绕组中的传播测试程序和允许放电水平变压器局部放电的测试回路校正套管放电的影响变压器局部放电的电气定位方法61. Significance of PD Detection in Transformerpower frequency withstand test impulse withstand test PD often affects the transformers properties in a long-term period. The withstand strength in a shor

6、t time does not change significantly. Withstand test is destructive, the voltage is so high that insulation is easy to be damaged.工频耐压试验冲击耐压试验局部放电通常影响变压器的长期运行性能,而对短时的耐压强度影响不大。耐压试验是有损试验,容易对绝缘造成破坏The voltage of PD test is much lower, and the testing duration is longer (0.51h).局部放电试验的试验电压相对较低,试验持续时间也较长

7、72. PD Propagation in WindingsEquivalent circuit of a transformer windingC-ground capacitance per unit lengthL-inductance per unit length, parasitic inductance K-series capacitance per unit length, longitudinal capacitance O-neutral point A-high voltage end单位长度对地电容单位长度的串联电容 单位长度的电感,即寄生电感 中性点高压端8Equi

8、valent circuit of a winding with a cavity discharge source2. PD Propagation in Windings92. PD Propagation in WindingsVoltage response along the winding沿绕组的电压响应103. Test Procedure and Permissible Apparent ChargeU1:pre-applied Voltage 预加电压U2:measuring voltage 测量电压Um :the maximum line voltageDuring obs

9、ervation, some impulses occasionally occurring with high magnitude can be neglected.在整个试验时间内连续观测,个别较高的脉冲可以忽略The noise level is required to be less than 50% magnitude of the highest detected impulse.外围噪声水平应低于规定的视在放电量的50%When test voltage is raised to U2 and decreased from U2, the inception and extinc

10、tion voltages are recorded.在电压升至U2及由U2降低的过程中,记录起始可能的放电电压和熄灭电压113. Test Procedure and Permissible Apparent ChargeDuring the first step under the test voltage U2, the maximum apparent charge is recorded.During the second step under the test voltage U2, discharge impulses need to be observed continuous

11、ly and the maximum apparent charge is recorded.U1:pre-applied Voltage 预加电压U2:measuring voltage 测量电压Um :the maximum line voltage在电压U2的第一阶段应读数并记录No record is required under test voltage U1.在U1阶段无需观测记录在电压U2第二阶段整个时间内,应连续地观测和记录局部放电水平12 If the following results are obtained, the PD experiment can be passe

12、d.3. Test Procedure and Permissible Apparent ChargeDuring the test procedure, the test voltage never suddenly decreases.During the last 30 minutes, the magnitudes of all observed impulses are smaller than the permissible apparent charge and do not increase towards the permissible apparent charge.如果满

13、足两个条件,则试验合格试验过程中,试验电压不产生突然下降在施加电压U2的第二阶段的30分钟内,所有测量的视在放电量连续维持在低于规定的限值,并且不表现出明显地、不断地倾向允许最大限制值增长的趋势134. Detection Circuits for TransformersTwo ways of the test:induced voltage test and applied voltage test.Principles of PD circuit selection 两种试验方法:感应加压方式,直接加压方式 试验回路选择采用尽量短的引线在试验中对主纵绝缘都能同时得到所应施加的电压To e

14、xecute the test with required voltage on both main insulation and longitudinal insulation.To use high voltage leads as short as possible.144.1 Detection circuits for single-phase transformers4. Detection Circuits for Transformers(a)(b)(c)(d)单相变压器的测试回路applied voltageinduced voltage154.2 Detection Cir

15、cuits for Three-Phase Transformers4. Detection Circuits for TransformersUA=0.25U, UB=0.75U, UC=UUBC=1.75U,UAC=1.25UUA=0.5U, UB=U, UC=0.5UUAB=1.5U,UBC=1.5U三相变压器的测试回路164. Detection Circuits for TransformersUA=0.5U, UB=0.5U, UC=UUAC=1.5U,UBC=1.5UUA=0.5U, UB=0.5U, UC=UUAC=1.5U,UBC=1.5U175. CalibrationCo

16、0.1CxCx: entrance capacitance 入口电容Co:50100pFCalibration impulse injected from the HV terminalCalibration impulse injected from the measuring terminal高压端校正入口校正Ck: capacitance of bushing 套管电容185. CalibrationExecute calibration at the place close to the detection terminal.Requirements of calibration:Put calibration unit as close as possible to the HV terminal in order to avoid influences of parasitic capacitances.Record the detected apparent charges and the relevant detection and calibration places.在测量部位和

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论