1、欢迎下载内容仅供参考防静电环氧地坪施工Anti-static Epoxy Self-leveling system抗静电环氧自流平地面The proposal :3mm Anti-static Epoxy Self-leveling systemSikafloor 239EDFAntistatic epoxy self-leveling system抗静电环氧自流平系统Approx.Sikafloor 239EDFAntistatic epoxy self-leveling system抗静电环氧自流平系统Approx.3mmcoatingthickness涂装厚度约 3 mmSikafloo

2、r239EDFisaseamless,self-smoothing,flooringsystembasedonadvanced solvent-freeepoxysystemandselectedgradedfillers.Thecuredfloorexhibitsexcellent electrostatically dissipative behavior. The smooth, impervious surface can be easily maintained in a hygieniccondition.Sikafloor 239EDF 是一种无接缝、自流平环氧系统,它以一种先进

3、的无溶剂环氧树脂为基料,并采用专门级配的填充料。该地面具有优异的防静电性能,其表面形成光滑的无渗透的地面,易于保持卫生状态。Performance 性能:Electrostatically dissipative (Resistance to ground 106RG109 Ohm)防静电性能(106RG109欧姆)High level of aesthetics and easy to clean 高度美观,易清洗Comfort and care 舒适,安全Smooth and seamless 光滑,无缝Structure Profile 系统结构图:防静电面层 Anti-static T

4、op-coatConductiveLayerLevelayerPrimerConcreteSystem Description 系统介绍:StepStepProduct & ConsumptionApplication Method步骤产品和用量施工方法Surface Preparation:Cleaning, grinding and shot blasting基层处理清理,研磨和喷砂处理Primer:Sikafloor161+石英砂 0.3-0.4kg/m2Trowel,roller底漆刮板,滚筒Epoxy Levelingmortar环氧找平层Sikafloor161+适量石英砂0.9k

5、g/ 0.9kg/m2Trowel刮板Conductive CopperTapeAdhibit导电铜带粘贴Conductive LayerSikafloor220W 0.1kg/m2Roller导电层滚筒Top-coatSikafloor 239EDF 1.8kg/m2Trowel刮板面层+SikaDur 505 0.6kg/m2Material Description 材料说明:Sikafloor 161 is a 2 component epoxy resin based, solvent free primer.Sikafloor 161 是一种双组分环氧树脂基无溶剂型底油Sikaflo

6、or220Wisatwopartwaterdispersed,epoxyresinwithhighconductivity是一种双组分水性环氧树脂,具有较高的导电性能。Sikafloor 239EDF is a two part, self-smoothing, coloured epoxy resin coating.Decorative and protective dissipative self-smoothing system for concrete or cement screeds with normal up to medium heavy wear.Sikafloor 23

7、9EDF 装饰和保护的涂层Sikadur 505Qisadriedfinequartzaggregate,0.1-0.3mmforfillingself-levelingfloors and as filler in Sikafloor 156/263/264 as leveling mortar or scrape layer.Sikadur 505Q是一种干燥细颗粒骨料,0.10.3 mm ,用于填充自流平地面及用作Sikafloor161/263/264自流平砂浆或刮磨层的腻子层。ThinnerDSorThinnerCisasolventforcleaningpurpose. Thinn

8、erDSor ThinnerC 是用于清洁的溶剂Application Method 施工工艺Inspection Substrate Quality 基面质量检查Theconcretesubstratemustbesoundandofsufficientcompressivestrength(minimumN/mm2)withaminimumpulloffstrengthof1.5N/mm2.混凝土基面必须密实和有足够的抗压强度(最小25 N/mm2),1.5 N/mm2。Substrateneedstobedry,moisturecontent4%.Testmethod:Sika-Tram

9、exmeteror CMmeasurement.Awaterproofinglayermustbeinstalledundertheconcreteor vapor going up will result in epoxy layer bubbling and delamination. 2 mm Sikafloor 81 EpoCem system need to be applied as a moisturebarrier.基层须干燥,含水率4%,测试方法:Sika-Tramex仪或CM测量法。混凝土基层下须设置 防水层,否则存在水汽上升导致环氧层起泡、脱落风险。建议施工2mmSika

10、lfoor81系统作为防潮层。Thesubstratemustbecleanandfreeofallcontaminantssuchasdirt,oil,grease,coatings and surface treatments,etc.基面必须清洁、无任何污染物,如:灰尘、油、油脂、涂层和表面处理等。Measure Application Conditions 施工条件测量SubstrateTemperature:+10min./+30基面温度:最低+10/最高+30Ambient Temperature +10 min. / +30 max.环境温度:最低+10/最高+30 Relati

11、veAirHumidity:80%R.H.80%相对湿度Dew Point: The substrate and uncured floor must be at least 3above dew point toreduce the risk of condensation or blooming on the floor finish.露点:基面和未固化的地面温度必须至少高于露点3,以防水汽凝结形成斑点。Substrate Preparation 基面处理re-clean the floor surface, degrease agent will be used where necess

12、ary.清洁地表,必要时使用清洁剂;Carryoutsurfacepreparationbyusingshotblastingmachine(dustfreeselfenclosedshotblastingunit)andhandtoolstoremovesurfacelaitanceandtoprovidesoundand texturedsurface.使用自动无尘喷砂设备和手动工具进行表面预处理,去除混凝土表面翻沫及松散结构,并提供涂装所需的必要的粗糙度;Removeallremainingdustanddebrisbydrybrushingandvacuumcleaning.丸及灰尘,

13、并真空吸尘;Repair all floor defects such as honey combs, scratches, working joints and so on by usingSikaDur and Sikaflex range of materials.使用SikaDur 与Sikaflex等系列产品对地面缺陷如蜂窝麻面、划痕、施工缝等进行修补;Mixing of material 材料混合:In general, all products must be mechanically mixed using an electrical power stirrer with300

14、400rpm,priortomixingstirpartAmechanically.WhenallofpartBhasbeen addedtopartA,continuouslymixfor2minutesuntilauniformmixhasbeenachieved. DependingontheproductadinthefillerorCcomponentandmixforanother2minutes until a uniform mix has beenachieved.A300 400 转速/把所有B组分加入A2 分钟直到混合均匀。根据产品加入填料或C组分, 继续搅拌两分钟直到混

15、合均匀。Toensurethoroughmixing,pourmaterialsintoanothercontainerandmixagaintoachieve a consistent mix. Over mixing must be avoided to minimize air entrapment.保证通过混合、倾倒材料进入另一容器后,再次搅拌达到一致混合。需要避免过度搅拌产生气泡Application of Sikafloor 161, consumption approx. 0.4 kg/m for primer;Application of Sikafloor 161, cons

16、umption approx. 0.4 kg/m for primer;consumption approx. 0.9 kg/m Sikafloor 161 mixed with 0.45kg/m2 quartz sand.Sikafloor 161 0.4 kg/m,2.7kg/m2Application of Conductive Copper Tape 导电铜带施工欢迎下载内容仅供参考ApplicationofApplicationofConductivelayer 导电层施工Apply with a layer of Sikafloor220W,consumptionapprox.kg

17、/m.Sikafloor 220W0.1 kg/m,Application of anti-staticTop layerApplication of anti-staticTop layer 防静电面层施工Aftercuringoftheconductivelayer,application of a layer Sikafloor with a trowel; consumption approx. 1.8kg/m Sikafloor 239EDF mixedwith0.6kg/m2 quartzsand.导电层固化后, 用刮板施工 Sikafloor7 / 8欢迎下载内容仅供参考Also apply with a spike rolling for deairing and levelling.用齿状刮刀施工并立即用带钉的滚筒排气找平。After application, clean the application tools with Thinner DS.施工结束后用

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论