自主可控新一代变电站二次系统技术规范
装置类系列规范2继电保护装置
(试行)
国家电网公司
2021年2月
目次
1范围···························································································································2
2规范性引用文件············································································································2
3总则···························································································································2
4技术要求·····················································································································2
4.1功能要求····················································································································2
4.2软件版本定义··············································································································3
4.3接口要求····················································································································4
附录A(规范性附录)装置接口及虚端子······································································5
A.1220kV及以上电压等级线路保护装置接口信息···································································5
A.210kV~110(66)kV线路保护装置接口信息······································································7
A.3220kV及以上电压等级元件保护装置接口信息··································································12
A.410kV~110(66)kV元件保护装置接口信息····································································18
1
继电保护装置技术规范
1范围
为规范自主可控的新一代变电站二次系统中保护装置的功能和技术要求,为保护设备的设计、研
发提供指导和参考,特制定本规范。
本规范适用于750kV及以下自主可控的新一代变电站,1000kV自主可控的新一代变电站可参照执
行。
2规范性引用文件
下列文件中的条款通过本标准的引用而成为本标准的条款。凡是注日期的引用文件,其随后所有的修
改单或修订版均不适用于本标准,然而,鼓励根据本标准达成协议的各方研究是否可使用这些文件的最新
版本。凡是不注日期的引用文件,其最新版本适用于本标准。
Q/GDW1161线路保护及辅助装置标准化设计规范
Q/GDW1175变压器、高压并联电抗器和母线保护及辅助装置标准化设计规范
Q/GDW1076610kV~110(66)kV线路保护及辅助装置标准化设计规范
Q/GDW1076710kV~110(66)kV元件保护及辅助装置标准化设计规范
Q/GDW11010继电保护信息规范
自主可控新一代变电站二次系统技术规范通用类系列规范1总体技术导则
自主可控新一代变电站二次系统技术规范通用类系列规范3变电站网络通信
自主可控新一代变电站二次系统技术规范通用类系列规范4DL/T860通信报文
自主可控新一代变电站二次系统技术规范通用类系列规范6二次设备安全防护
自主可控新一代变电站二次系统技术规范装置类系列规范1采集执行单元
自主可控新一代变电站二次系统技术规范通用类系列规范8变电站设备信息模型
3总则
3.1装置应采用自主可控装置,功能性能应满足现行国标、行标和国网企标的技术要求。
3.2装置与站控层设备通信应支持DL/T860通信报文规范。
4技术要求
4.1功能要求
4.1.1110(66)kV电压等级线路保护装置、母联(分段)保护、电容器、电抗器、站用变保护装置宜
集成测控功能。
4.1.2110(66)kV及以上电压等级继电保护装置应支持采用点对点通信方式与本间隔采集执行单元通
信,应支持采用网络方式传输保护间的启动失灵、闭锁重合闸等命令。
4.1.310(35)kV保护测控集成装置采用常规采样、常规跳闸方式,同时应支持网络传输GOOSE跳
合闸等命令,10(35)kV分段多合一保护装置同时支持独立的SV和GOOSE共口输出。
4.1.435kV常规变电站备自投装置应采用常规采样、常规跳闸方式。
2
4.1.5变压器保护、接地变保护、故障解列、备自投装置应支持采用点对点通信方式及通过网络传输
GOOSE跳闸等命令,如主变保护跳分段及闭锁备自投等。
4.1.6保护装置应支持就地和远方投退软压板、复归装置、修改定值、切换定值区等操作功能。
4.1.7装置组网口应保持独立,组网口应具备组播输出报文输出流量控制功能,应避免不同组网口同时
输出网络风暴报文。
4.1.8对装置组网口进行非订阅报文网络压力检验,装置不应出现死机、重启等异常现象,风暴消失后
装置功能应能恢复正常。
4.1.9装置应符合《自主可控新一代变电站二次系统技术规范通用类系列规范6二次设备安全防护》
二次设备安全防护要求。
4.1.10装置自检异常时宜支持具备异常板卡定位功能,板卡定位信息宜按“插槽号+插件功能+异常种
类”命名,例如“1N16管理CPU插件异常”,其中“1N16”表示插槽号,“管理CPU”表示插件功能。
4.1.11装置ICD模型文件中,五防联闭锁等测控相关的跨间隔联闭锁信息访问点定义为S1;其它跳闸
及跨间隔信息的访问点定义为G1。
4.1.12装置应能通过DL/T860通信报文规范上送CCD文件的CRC校验码,应能通过文件服务上送CCD
文件、CID文件,支持通过文件服务下装CCD和CID文件,CID文件模型中的信息命名须符合《自主
可控新一代变电站二次系统技术规范通用类系列规范8变电站设备信息模型》要求。
4.1.13继电保护装置定值数据集dsSetting中定值和控制字的名称和顺序应满足Q/GDW1161、
Q/GDW1175、Q/GDW10766、Q/GDW10767及Q/GDW11010等保护及信息标准化设计规范要求。
4.1.14母线保护和变压器保护等订阅信号相关的各间隔保护、采集执行单元等装置,应规范GOOSE
及SV发送数据集,统一数据集中所有通道信息的属性、引用路径、顺序及数量等,并不受功能选配影
响,支持母线保护和变压器保护等实现按远期配置CCD文件。依托Q/GDW1396以及相关保护设计规
范,保护GOOSE控制块相关配置应按表1要求固化,保护装置虚端子参见附录A。
表1保护GOOSE配置要求
GOCBRef(控制块引用路径)GOID(控制块名)DataSet(数据集)
IEDname+PIGO/LLN0$GO$gocb0IEDname+PIGO/LLN0.gocb0IEDname+PIGO/LLN0$dsGOOSE
4.2软件版本定义
3
注:装置分类○4中GZK表示国网自主可控新一代,其中-DA-GZK,表示自主可控的新一代国网智能
化装置,SV采样、GOOSE跳闸。其中-GZK,表示10(35)kV自主可控的新一代国网常规采样常规
跳闸装置。其中-MA-GZK表示10(35)kV自主可控的新一代国网多合一装置,常规采样常规跳闸,
并支持GOOSE开入开出和SV输出。
4.3接口要求
4.3.1对时接口:应支持接受对时系统发出的IRIG-B对时码;条件成熟时也可采用GB/T25931标准进
行网络对时,对时精度应满足要求。
4.3.2组网通信接口:应支持至少2组DL/T860通信报文和GOOSE共网通信接口,宜采用百兆光纤以
太网口,其中GOOSE报文主要用于实现保护跨间隔信息交互及故障录波。备自投、故障解列装置、
66kV电容器保护、66kV电抗器保护、66kV站用变保护和35kV及以下电压等级保护装置可采用电接
口。
4.3.3直采通信接口:SV采样GOOSE跳闸装置直采通信接口应支持与采集执行单元点对点的GOOSE
和SV共网通信,接口数量应满足需求,最低要求详见附录A。
4.3.4其它接口:调试接口、打印机接口。
4.3.5线路保护采用复用光纤时,保护应支持2M光纤直连通信设备。
4
附录A
(规范性附录)
装置接口及虚端子
A.1220kV及以上电压等级线路保护装置接口信息
A.1.13/2断路器接线线路保护装置接口数量基本要求见表A.1.1。
表A.1.13/2断路器接线线路保护接口数量基本要求
装置名称组网通信接口过程层接口备注
线路保护23
A.1.2双母线接线线路保护装置接口数量基本要求见表A.1.2。
表A.1.2双母线接线线路保护接口数量基本要求
装置名称组网通信接口过程层接口备注
线路保护21
A.1.33/2断路器接线线路保护装置GOOSE输出虚端子见表A.1.3。
表A.1.33/2断路器接线线路保护虚端子表
序号信号名称软压板引用路径备注
1跳边断路器A相PIGO/B1PTRC1.Tr.phsA
2跳边断路器B相跳边断路器PIGO/B1PTRC1.Tr.phsB
3跳边断路器C相PIGO/B1PTRC1.Tr.phsC
4启动边断路器A相失灵PIGO/B1PTRC1.StrBF.phsA
5启动边断路器B相失灵启动边断路器失灵PIGO/B1PTRC1.StrBF.phsB同一LN
6启动边断路器C相失灵PIGO/B1PTRC1.StrBF.phsC
7边断路器永跳边断路器永跳PIGO/B1PTRC1.BlkRecST.stVal
闭锁边断路器重合
8闭锁边断路器重合闸PIGO/B1PTRC1.BlkRecST.stVal
闸
9跳中断路器A相PIGO/B2PTRC1.Tr.phsA
10跳中断路器B相跳中断路器PIGO/B2PTRC1.Tr.phsB
11跳中断路器C相PIGO/B2PTRC1.Tr.phsC
12启动中断路器A相失灵PIGO/B2PTRC1.StrBF.phsA
13启动中断路器B相失灵启动中断路器失灵PIGO/B2PTRC1.StrBF.phsB同一LN
14启动中断路器C相失灵PIGO/B2PTRC1.StrBF.phsC
15中断路器永跳中断路器永跳PIGO/B2PTRC1.BlkRecST.stVal
闭锁中断路器重合
16闭锁中断路器重合闸PIGO/B2PTRC1.BlkRecST.stVal
闸
17远传1开出无PIGO/PSCH1.ProRx.stVal
18远传2开出无PIGO/PSCH2.ProRx.stVal
19过电压远跳发信无PIGO/GGIO1.Ind1.stVal
20保护动作无PIGO/GGIO1.Ind2.stVal
21通道一告警无PIGO/GGIO1.Ind3.stVal
5
序号信号名称软压板引用路径备注
22通道二告警无PIGO/GGIO1.Ind4.stVal
23通道故障无PIGO/GGIO1.Ind5.stVal
24过负荷告警无PIGO/GGIO1.Ind6.stVal
注1:7)项和8)项、15)项和16)项在同一厂家保护装置中只存在其一。
注2:GOOSE输出虚端子对应功能未选配时,固定输出0。
A.1.4双母线接线线路保护装置GOOSE输出虚端子见表A.1.4。
表A.1.4双母线接线线路保护虚端子表
序号信号名称典型软压板引用路径备注
1跳断路器A相PIGO/PTRC1.Tr.phsA
2跳断路器B相跳闸PIGO/PTRC1.Tr.phsB
3跳断路器C相PIGO/PTRC1.Tr.phsC
4启动A相失灵PIGO/PTRC1.StrBF.phsA
同一LN
5启动B相失灵启动失灵PIGO/PTRC1.StrBF.phsB
6启动C相失灵PIGO/PTRC1.StrBF.phsC
7永跳永跳PIGO/PTRC1.BlkRecST.stVal
8闭锁重合闸闭锁重合闸PIGO/PTRC1.BlkRecST.stVal
9重合闸重合闸PIGO/RREC1.Op.general
10三相不一致跳闸三相不一致PIGO/PPDP1.Op.general
11远传1开出无PIGO/PSCH1.ProRx.stVal
12远传2开出无PIGO/PSCH2.ProRx.stVal
13过电压远跳发信无PIGO/GGIO1.Ind1.stVal
14保护动作无PIGO/GGIO1.Ind2.stVal
15通道一告警无PIGO/GGIO1.Ind3.stVal
16通道二告警无PIGO/GGIO1.Ind4.stVal
17通道故障无PIGO/GGIO1.Ind5.stVal
18过负荷告警无PIGO/GGIO1.Ind6.stVal
注1:7)项和8)项在同一厂家保护装置中只存在其一。
注2:GOOSE输出虚端子对应功能未选配时,固定输出0。
A.1.5断路器保护装置过程层接口数量基本要求见表A.1.5。
表A.1.5断路器保护装置过程层接口数量基本要求
装置名称组网通信接口过程层接口备注
断路器保护装置24
A.1.6断路器保护装置GOOSE输出虚端子见表A.1.6。
表A.1.6断路器保护装置GOOSE输出虚端子表
序号信号名称典型软压板引用路径备注
1跳断路器A相PIGO/PTRC1.Tr.phsA
2跳断路器B相跳闸PIGO/PTRC1.Tr.phsB同一LN
3跳断路器C相PIGO/PTRC1.Tr.phsC
6
序号信号名称典型软压板引用路径备注
4永跳永跳PIGO/PTRC1.BlkRecST.stVal
5闭锁重合闸闭锁重合闸PIGO/PTRC1.BlkRecST.stVal
6重合闸重合闸PIGO/RREC1.Op.general
7失灵跳闸1失灵跳闸1PIGO/B1PTRC1.Tr.general
8失灵跳闸2失灵跳闸2PIGO/B2PTRC1.Tr.general
9失灵跳闸3失灵跳闸3PIGO/B3PTRC1.Tr.general
10失灵跳闸4失灵跳闸4PIGO/B4PTRC1.Tr.general
11失灵跳闸5失灵跳闸5PIGO/B5PTRC1.Tr.general
12失灵跳闸6失灵跳闸6PIGO/B6PTRC1.Tr.general
13保护动作无PIGO/GGIO1.Ind1.stVal
注1:4)项和5)项在同一厂家保护装置中只存在其一。
注2:GOOSE发送数据集名称:dsGOOSE,GOOSE控制块名称:gocb0。
A.210kV~110(66)kV线路保护装置接口信息
A.2.1110(66)kV线路保护测控智能化装置接口数量基本要求见表A.2.1。
A.2.1110(66)kV线路保护测控智能化装置接口数量基本要求
设备名称组网通信接口过程层接口备注
线路保护测控
集成装置21—
A.2.2110(66)kV线路保护测控智能化装置GOOSE输出虚端子见表A.2.2。
A.2.2110(66)kV线路保护测控智能化装置GOOSE输出虚端子表
(保护部分)
序号信号名称软压板引用路径备注
1保护跳闸保护跳闸PIGO/PTRC1.Tr.general
2启动失灵启动失灵PIGO/PTRC1.StrBF.general
同一LN
3闭锁重合闸闭锁重合闸PIGO/PTRC1.BlkRecST.stVal
4永跳永跳PIGO/PTRC1.BlkRecST.stVal
5重合闸重合闸PIGO/RREC1.Op.general保护用
6远传1开出远传1开出PIGO/PSCH1.ProRx.stVal保护用
7远传2开出远传2开出PIGO/PSCH2.ProRx.stVal保护用
8保护动作—PIGO/GGIO1.Ind1.stVal保护用
9重合闸动作—PIGO/GGIO1.Ind2.stVal保护用
10过负荷告警—PIGO/GGIO1.Ind3.stVal保护用
11通道一告警—PIGO/GGIO1.Ind4.stVal保护用,注2
保护用,仅用于
12通道二告警—PIGO/GGIO1.Ind5.stVal
T型接线
注1:“远传1开出、远传2开出”、“通道告警”仅适用于纵联电流差动保护装置。
注2:对于T接线路名称为“通道一告警”,而对于非T接线路名称为“通道告警。
注3:3)项和4)项在同一厂家保护装置中只存在其一。
注4:保护相关的GOOSE过程层访问点LD,inst名为“PIGO”
7
(测控部分)
序号信号名称软压板引用路径备注
1断路器遥控合——测控用
2断路器遥控分——测控用
3遥控1合——测控用
4遥控1分——测控用
5遥控1操作允许——测控用
6…——测控用
7遥控8合——测控用
8遥控8分——测控用
9遥控8操作允许——测控用
10遥控复归1——测控用
11遥控复归2——测控用
12备用开出1——测控用,可选
13…——测控用,可选
14备用开出n——测控用,可选
A.2.3备自投智能化装置接口数量基本要求见表A.2.3。
A.2.3备自投智能化装置接口数量基本要求
设备名称组网通信接口过程层接口备注
过程层端口数量中包含一
进线及分段备自投装置25个组网口,该端口也可用
于点对点
主变及分段备自投装置25—
扩大内桥备自投装置24—
A.2.4进线、主变及分段(桥)备自投智能化装置GOOSE输出虚端子见表A.2.4。
A.2.4进线、主变及分段(桥)备自投智能化装置GOOSE输出虚端子表
序号信号名称软压板引用路径备注
主变备自投跳
PIGO/H1TrPTRC1.Tr.gener
1跳电源1高断路器跳电源1高断路器1#主变高压侧断
al路器
PIGO/L1TrPTRC1.Tr.gener
2跳电源1断路器跳电源1断路器—
al
主变备自投跳
PIGO/H2TrPTRC1.Tr.gener
3跳电源2高断路器跳电源2高断路器2#主变高压侧断
al路器
PIGO/L2TrPTRC1.Tr.gener
4跳电源2断路器跳电源2断路器—
al
PIGO/Bus1TrPTRC1.Tr.gen
5跳分段断路器跳分段断路器—
eral
主变备自投合
PIGO/H1ClPTRC1.Tr.gener
6合电源1高断路器合电源1高断路器1#主变高压侧断
al路器
PIGO/L1ClPTRC1.Tr.gener
7合电源1断路器合电源1断路器—
al
8合电源2高断路器合电源2高断路器PIGO/H2ClPTRC1.Tr.gener主变备自投合
8
序号信号名称软压板引用路径备注
al2#主变高压侧断
路器
PIGO/L2ClPTRC1.Tr.gener—
9合电源2断路器合电源2断路器
al
PIGO/Bus1ClPTRC1.Tr.ge—
10合分段断路器合分段断路器
neral
11跳闸出口1跳闸出口1PIGO/PTRC1.Tr.general—
12跳闸出口2跳闸出口2PIGO/PTRC2.Tr.general—
13跳闸出口3跳闸出口3PIGO/PTRC3.Tr.general—
14跳闸出口4跳闸出口4PIGO/PTRC4.Tr.general—
15跳闸出口5跳闸出口5PIGO/PTRC5.Tr.general—
16跳闸出口6跳闸出口6PIGO/PTRC6.Tr.general—
17跳闸出口7跳闸出口7PIGO/PTRC7.Tr.general—
18跳闸出口8跳闸出口8PIGO/PTRC8.Tr.general—
19跳闸出口9跳闸出口9PIGO/PTRC9.Tr.general—
20跳闸出口10跳闸出口10PIGO/PTRC10.Tr.general—
21跳闸出口11跳闸出口11PIGO/PTRC11.Tr.general—
22跳闸出口12跳闸出口12PIGO/PTRC12.Tr.general—
23跳闸出口13跳闸出口13PIGO/PTRC13.Tr.general—
24跳闸出口14跳闸出口14PIGO/PTRC14.Tr.general—
25跳闸出口15跳闸出口15PIGO/PTRC15.Tr.general—
26跳闸出口16跳闸出口16PIGO/PTRC16.Tr.general—
27备自投动作—PIGO/GGIO1.Ind1.stVal—
A.2.5扩大内桥接线备自投智能化装置GOOSE输出虚端子见表A.2.5。
A.2.5扩大内桥接线备自投智能化装置GOOSE输出虚端子表
序号信号名称软压板引用路径备注
1跳电源1断路器跳电源1断路器PIGO/L1TrPTRC1.Tr.general—
2跳电源2断路器跳电源2断路器PIGO/L2TrPTRC1.Tr.general—
3合电源1断路器合电源1断路器PIGO/L1ClPTRC1.Tr.general—
4合电源2断路器合电源2断路器PIGO/L2ClPTRC1.Tr.general—
5合内桥1断路器合内桥1断路器PIGO/Int1ClPTRC1.Tr.general—
6合内桥2断路器合内桥2断路器PIGO/Int2ClPTRC1.Tr.general—
7跳内桥1断路器跳内桥1断路器PIGO/Int1TrPTRC1.Tr.general—
8跳内桥2断路器跳内桥2断路器PIGO/Int2TrPTRC1.Tr.general—
9跳闸出口1跳闸出口1PIGO/PTRC1.Tr.general—
10跳闸出口2跳闸出口2PIGO/PTRC2.Tr.general—
11跳闸出口3跳闸出口3PIGO/PTRC3.Tr.general—
12跳闸出口4跳闸出口4PIGO/PTRC4.Tr.general—
13跳闸出口5跳闸出口5PIGO/PTRC5.Tr.general—
14跳闸出口6跳闸出口6PIGO/PTRC6.Tr.general—
15跳闸出口7跳闸出口7PIGO/PTRC7.Tr.general—
9
序号信号名称软压板引用路径备注
16跳闸出口8跳闸出口8PIGO/PTRC8.Tr.general—
17跳闸出口9跳闸出口9PIGO/PTRC9.Tr.general—
18跳闸出口10跳闸出口10PIGO/PTRC10.Tr.general—
19跳闸出口11跳闸出口11PIGO/PTRC11.Tr.general—
20跳闸出口12跳闸出口12PIGO/PTRC12.Tr.general—
21跳闸出口13跳闸出口13PIGO/PTRC13.Tr.general—
22跳闸出口14跳闸出口14PIGO/PTRC14.Tr.general—
23跳闸出口15跳闸出口15PIGO/PTRC15.Tr.general—
24跳闸出口16跳闸出口16PIGO/PTRC16.Tr.general—
25备自投动作—PIGO/GGIO1.Ind1.stVal—
A.2.6故障解列装置接口数量基本要求见表A.2.6。
A.2.6故障解列智能化装置过程层接口数量基本要求
设备名称组网通信接口过程层接口备注
点对点接口用于跳
故障解列装置110kV
25线路
A.2.7故障解列装置GOOSE输出虚端子见表A.2.7。
A.2.7故障解列装置GOOSE输出虚端子表
序号信号名称软压板引用路径备注
1跳闸出口1跳闸出口1PIGO/PTRC1.Tr.general—
2跳闸出口2跳闸出口2PIGO/PTRC2.Tr.general—
3跳闸出口3跳闸出口3PIGO/PTRC3.Tr.general—
4跳闸出口4跳闸出口4PIGO/PTRC4.Tr.general—
5跳闸出口5
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- HY/T 0497-2025雷达自动验潮仪
- 企业管理-PNC(规划-导航-控制)管理制度
- 龙岩市五县重点达标名校2026年初三中考总复习单元同步滚动测试卷物理试题含解析
- 陕西商南县2025-2026学年初三1月阶段测试数学试题试卷含解析
- 2026年云南省施甸县初三第一次质量预测数学试题含解析
- 四川省成都市高新南区重点名校2026届初三数学试题二模试卷含解析
- 2026年四川省简阳市简城区初三下学期第一次联考物理试题试卷含解析
- 安徽界首地区市级名校2025-2026学年初三下学期8月开学数学试题含解析
- 广西南宁市青秀区第二中学2026届初三4月调研测试(二模)物理试题含解析
- 高中语文《登岳阳楼》课件+统编版高一语文必修下册
- 5.1人民代表大会制度 课件(23张幻灯片)+内嵌视频 道德与法治统编版八年级下册
- 高考18个文言虚词用法详解
- 超高性能混凝土进展及工程应用
- 旋毛虫法语课件
- 五原县供热工程专项规划(2014-2030年) 说明书
- 上海市2023年基准地价更新成果
- 拔牙术拔牙并发症
- 选派援疆医疗卫生人才协议书
- XB/T 405-2016铈铁合金
- GB/T 9966.16-2021天然石材试验方法第16部分:线性热膨胀系数的测定
- GB/T 3733.2-1983卡套式端直通接头体
评论
0/150
提交评论