自主可控新一代变电站二次系统技术规范

装置类系列规范2继电保护装置

(试行)

国家电网公司

2021年2月

目次

1范围···························································································································2

2规范性引用文件············································································································2

3总则···························································································································2

4技术要求·····················································································································2

4.1功能要求····················································································································2

4.2软件版本定义··············································································································3

4.3接口要求····················································································································4

附录A(规范性附录)装置接口及虚端子······································································5

A.1220kV及以上电压等级线路保护装置接口信息···································································5

A.210kV~110(66)kV线路保护装置接口信息······································································7

A.3220kV及以上电压等级元件保护装置接口信息··································································12

A.410kV~110(66)kV元件保护装置接口信息····································································18

1

继电保护装置技术规范

1范围

为规范自主可控的新一代变电站二次系统中保护装置的功能和技术要求,为保护设备的设计、研

发提供指导和参考,特制定本规范。

本规范适用于750kV及以下自主可控的新一代变电站,1000kV自主可控的新一代变电站可参照执

行。

2规范性引用文件

下列文件中的条款通过本标准的引用而成为本标准的条款。凡是注日期的引用文件,其随后所有的修

改单或修订版均不适用于本标准,然而,鼓励根据本标准达成协议的各方研究是否可使用这些文件的最新

版本。凡是不注日期的引用文件,其最新版本适用于本标准。

Q/GDW1161线路保护及辅助装置标准化设计规范

Q/GDW1175变压器、高压并联电抗器和母线保护及辅助装置标准化设计规范

Q/GDW1076610kV~110(66)kV线路保护及辅助装置标准化设计规范

Q/GDW1076710kV~110(66)kV元件保护及辅助装置标准化设计规范

Q/GDW11010继电保护信息规范

自主可控新一代变电站二次系统技术规范通用类系列规范1总体技术导则

自主可控新一代变电站二次系统技术规范通用类系列规范3变电站网络通信

自主可控新一代变电站二次系统技术规范通用类系列规范4DL/T860通信报文

自主可控新一代变电站二次系统技术规范通用类系列规范6二次设备安全防护

自主可控新一代变电站二次系统技术规范装置类系列规范1采集执行单元

自主可控新一代变电站二次系统技术规范通用类系列规范8变电站设备信息模型

3总则

3.1装置应采用自主可控装置,功能性能应满足现行国标、行标和国网企标的技术要求。

3.2装置与站控层设备通信应支持DL/T860通信报文规范。

4技术要求

4.1功能要求

4.1.1110(66)kV电压等级线路保护装置、母联(分段)保护、电容器、电抗器、站用变保护装置宜

集成测控功能。

4.1.2110(66)kV及以上电压等级继电保护装置应支持采用点对点通信方式与本间隔采集执行单元通

信,应支持采用网络方式传输保护间的启动失灵、闭锁重合闸等命令。

4.1.310(35)kV保护测控集成装置采用常规采样、常规跳闸方式,同时应支持网络传输GOOSE跳

合闸等命令,10(35)kV分段多合一保护装置同时支持独立的SV和GOOSE共口输出。

4.1.435kV常规变电站备自投装置应采用常规采样、常规跳闸方式。

2

4.1.5变压器保护、接地变保护、故障解列、备自投装置应支持采用点对点通信方式及通过网络传输

GOOSE跳闸等命令,如主变保护跳分段及闭锁备自投等。

4.1.6保护装置应支持就地和远方投退软压板、复归装置、修改定值、切换定值区等操作功能。

4.1.7装置组网口应保持独立,组网口应具备组播输出报文输出流量控制功能,应避免不同组网口同时

输出网络风暴报文。

4.1.8对装置组网口进行非订阅报文网络压力检验,装置不应出现死机、重启等异常现象,风暴消失后

装置功能应能恢复正常。

4.1.9装置应符合《自主可控新一代变电站二次系统技术规范通用类系列规范6二次设备安全防护》

二次设备安全防护要求。

4.1.10装置自检异常时宜支持具备异常板卡定位功能,板卡定位信息宜按“插槽号+插件功能+异常种

类”命名,例如“1N16管理CPU插件异常”,其中“1N16”表示插槽号,“管理CPU”表示插件功能。

4.1.11装置ICD模型文件中,五防联闭锁等测控相关的跨间隔联闭锁信息访问点定义为S1;其它跳闸

及跨间隔信息的访问点定义为G1。

4.1.12装置应能通过DL/T860通信报文规范上送CCD文件的CRC校验码,应能通过文件服务上送CCD

文件、CID文件,支持通过文件服务下装CCD和CID文件,CID文件模型中的信息命名须符合《自主

可控新一代变电站二次系统技术规范通用类系列规范8变电站设备信息模型》要求。

4.1.13继电保护装置定值数据集dsSetting中定值和控制字的名称和顺序应满足Q/GDW1161、

Q/GDW1175、Q/GDW10766、Q/GDW10767及Q/GDW11010等保护及信息标准化设计规范要求。

4.1.14母线保护和变压器保护等订阅信号相关的各间隔保护、采集执行单元等装置,应规范GOOSE

及SV发送数据集,统一数据集中所有通道信息的属性、引用路径、顺序及数量等,并不受功能选配影

响,支持母线保护和变压器保护等实现按远期配置CCD文件。依托Q/GDW1396以及相关保护设计规

范,保护GOOSE控制块相关配置应按表1要求固化,保护装置虚端子参见附录A。

表1保护GOOSE配置要求

GOCBRef(控制块引用路径)GOID(控制块名)DataSet(数据集)

IEDname+PIGO/LLN0$GO$gocb0IEDname+PIGO/LLN0.gocb0IEDname+PIGO/LLN0$dsGOOSE

4.2软件版本定义

3

注:装置分类○4中GZK表示国网自主可控新一代,其中-DA-GZK,表示自主可控的新一代国网智能

化装置,SV采样、GOOSE跳闸。其中-GZK,表示10(35)kV自主可控的新一代国网常规采样常规

跳闸装置。其中-MA-GZK表示10(35)kV自主可控的新一代国网多合一装置,常规采样常规跳闸,

并支持GOOSE开入开出和SV输出。

4.3接口要求

4.3.1对时接口:应支持接受对时系统发出的IRIG-B对时码;条件成熟时也可采用GB/T25931标准进

行网络对时,对时精度应满足要求。

4.3.2组网通信接口:应支持至少2组DL/T860通信报文和GOOSE共网通信接口,宜采用百兆光纤以

太网口,其中GOOSE报文主要用于实现保护跨间隔信息交互及故障录波。备自投、故障解列装置、

66kV电容器保护、66kV电抗器保护、66kV站用变保护和35kV及以下电压等级保护装置可采用电接

口。

4.3.3直采通信接口:SV采样GOOSE跳闸装置直采通信接口应支持与采集执行单元点对点的GOOSE

和SV共网通信,接口数量应满足需求,最低要求详见附录A。

4.3.4其它接口:调试接口、打印机接口。

4.3.5线路保护采用复用光纤时,保护应支持2M光纤直连通信设备。

4

附录A

(规范性附录)

装置接口及虚端子

A.1220kV及以上电压等级线路保护装置接口信息

A.1.13/2断路器接线线路保护装置接口数量基本要求见表A.1.1。

表A.1.13/2断路器接线线路保护接口数量基本要求

装置名称组网通信接口过程层接口备注

线路保护23

A.1.2双母线接线线路保护装置接口数量基本要求见表A.1.2。

表A.1.2双母线接线线路保护接口数量基本要求

装置名称组网通信接口过程层接口备注

线路保护21

A.1.33/2断路器接线线路保护装置GOOSE输出虚端子见表A.1.3。

表A.1.33/2断路器接线线路保护虚端子表

序号信号名称软压板引用路径备注

1跳边断路器A相PIGO/B1PTRC1.Tr.phsA

2跳边断路器B相跳边断路器PIGO/B1PTRC1.Tr.phsB

3跳边断路器C相PIGO/B1PTRC1.Tr.phsC

4启动边断路器A相失灵PIGO/B1PTRC1.StrBF.phsA

5启动边断路器B相失灵启动边断路器失灵PIGO/B1PTRC1.StrBF.phsB同一LN

6启动边断路器C相失灵PIGO/B1PTRC1.StrBF.phsC

7边断路器永跳边断路器永跳PIGO/B1PTRC1.BlkRecST.stVal

闭锁边断路器重合

8闭锁边断路器重合闸PIGO/B1PTRC1.BlkRecST.stVal

9跳中断路器A相PIGO/B2PTRC1.Tr.phsA

10跳中断路器B相跳中断路器PIGO/B2PTRC1.Tr.phsB

11跳中断路器C相PIGO/B2PTRC1.Tr.phsC

12启动中断路器A相失灵PIGO/B2PTRC1.StrBF.phsA

13启动中断路器B相失灵启动中断路器失灵PIGO/B2PTRC1.StrBF.phsB同一LN

14启动中断路器C相失灵PIGO/B2PTRC1.StrBF.phsC

15中断路器永跳中断路器永跳PIGO/B2PTRC1.BlkRecST.stVal

闭锁中断路器重合

16闭锁中断路器重合闸PIGO/B2PTRC1.BlkRecST.stVal

17远传1开出无PIGO/PSCH1.ProRx.stVal

18远传2开出无PIGO/PSCH2.ProRx.stVal

19过电压远跳发信无PIGO/GGIO1.Ind1.stVal

20保护动作无PIGO/GGIO1.Ind2.stVal

21通道一告警无PIGO/GGIO1.Ind3.stVal

5

序号信号名称软压板引用路径备注

22通道二告警无PIGO/GGIO1.Ind4.stVal

23通道故障无PIGO/GGIO1.Ind5.stVal

24过负荷告警无PIGO/GGIO1.Ind6.stVal

注1:7)项和8)项、15)项和16)项在同一厂家保护装置中只存在其一。

注2:GOOSE输出虚端子对应功能未选配时,固定输出0。

A.1.4双母线接线线路保护装置GOOSE输出虚端子见表A.1.4。

表A.1.4双母线接线线路保护虚端子表

序号信号名称典型软压板引用路径备注

1跳断路器A相PIGO/PTRC1.Tr.phsA

2跳断路器B相跳闸PIGO/PTRC1.Tr.phsB

3跳断路器C相PIGO/PTRC1.Tr.phsC

4启动A相失灵PIGO/PTRC1.StrBF.phsA

同一LN

5启动B相失灵启动失灵PIGO/PTRC1.StrBF.phsB

6启动C相失灵PIGO/PTRC1.StrBF.phsC

7永跳永跳PIGO/PTRC1.BlkRecST.stVal

8闭锁重合闸闭锁重合闸PIGO/PTRC1.BlkRecST.stVal

9重合闸重合闸PIGO/RREC1.Op.general

10三相不一致跳闸三相不一致PIGO/PPDP1.Op.general

11远传1开出无PIGO/PSCH1.ProRx.stVal

12远传2开出无PIGO/PSCH2.ProRx.stVal

13过电压远跳发信无PIGO/GGIO1.Ind1.stVal

14保护动作无PIGO/GGIO1.Ind2.stVal

15通道一告警无PIGO/GGIO1.Ind3.stVal

16通道二告警无PIGO/GGIO1.Ind4.stVal

17通道故障无PIGO/GGIO1.Ind5.stVal

18过负荷告警无PIGO/GGIO1.Ind6.stVal

注1:7)项和8)项在同一厂家保护装置中只存在其一。

注2:GOOSE输出虚端子对应功能未选配时,固定输出0。

A.1.5断路器保护装置过程层接口数量基本要求见表A.1.5。

表A.1.5断路器保护装置过程层接口数量基本要求

装置名称组网通信接口过程层接口备注

断路器保护装置24

A.1.6断路器保护装置GOOSE输出虚端子见表A.1.6。

表A.1.6断路器保护装置GOOSE输出虚端子表

序号信号名称典型软压板引用路径备注

1跳断路器A相PIGO/PTRC1.Tr.phsA

2跳断路器B相跳闸PIGO/PTRC1.Tr.phsB同一LN

3跳断路器C相PIGO/PTRC1.Tr.phsC

6

序号信号名称典型软压板引用路径备注

4永跳永跳PIGO/PTRC1.BlkRecST.stVal

5闭锁重合闸闭锁重合闸PIGO/PTRC1.BlkRecST.stVal

6重合闸重合闸PIGO/RREC1.Op.general

7失灵跳闸1失灵跳闸1PIGO/B1PTRC1.Tr.general

8失灵跳闸2失灵跳闸2PIGO/B2PTRC1.Tr.general

9失灵跳闸3失灵跳闸3PIGO/B3PTRC1.Tr.general

10失灵跳闸4失灵跳闸4PIGO/B4PTRC1.Tr.general

11失灵跳闸5失灵跳闸5PIGO/B5PTRC1.Tr.general

12失灵跳闸6失灵跳闸6PIGO/B6PTRC1.Tr.general

13保护动作无PIGO/GGIO1.Ind1.stVal

注1:4)项和5)项在同一厂家保护装置中只存在其一。

注2:GOOSE发送数据集名称:dsGOOSE,GOOSE控制块名称:gocb0。

A.210kV~110(66)kV线路保护装置接口信息

A.2.1110(66)kV线路保护测控智能化装置接口数量基本要求见表A.2.1。

A.2.1110(66)kV线路保护测控智能化装置接口数量基本要求

设备名称组网通信接口过程层接口备注

线路保护测控

集成装置21—

A.2.2110(66)kV线路保护测控智能化装置GOOSE输出虚端子见表A.2.2。

A.2.2110(66)kV线路保护测控智能化装置GOOSE输出虚端子表

(保护部分)

序号信号名称软压板引用路径备注

1保护跳闸保护跳闸PIGO/PTRC1.Tr.general

2启动失灵启动失灵PIGO/PTRC1.StrBF.general

同一LN

3闭锁重合闸闭锁重合闸PIGO/PTRC1.BlkRecST.stVal

4永跳永跳PIGO/PTRC1.BlkRecST.stVal

5重合闸重合闸PIGO/RREC1.Op.general保护用

6远传1开出远传1开出PIGO/PSCH1.ProRx.stVal保护用

7远传2开出远传2开出PIGO/PSCH2.ProRx.stVal保护用

8保护动作—PIGO/GGIO1.Ind1.stVal保护用

9重合闸动作—PIGO/GGIO1.Ind2.stVal保护用

10过负荷告警—PIGO/GGIO1.Ind3.stVal保护用

11通道一告警—PIGO/GGIO1.Ind4.stVal保护用,注2

保护用,仅用于

12通道二告警—PIGO/GGIO1.Ind5.stVal

T型接线

注1:“远传1开出、远传2开出”、“通道告警”仅适用于纵联电流差动保护装置。

注2:对于T接线路名称为“通道一告警”,而对于非T接线路名称为“通道告警。

注3:3)项和4)项在同一厂家保护装置中只存在其一。

注4:保护相关的GOOSE过程层访问点LD,inst名为“PIGO”

7

(测控部分)

序号信号名称软压板引用路径备注

1断路器遥控合——测控用

2断路器遥控分——测控用

3遥控1合——测控用

4遥控1分——测控用

5遥控1操作允许——测控用

6…——测控用

7遥控8合——测控用

8遥控8分——测控用

9遥控8操作允许——测控用

10遥控复归1——测控用

11遥控复归2——测控用

12备用开出1——测控用,可选

13…——测控用,可选

14备用开出n——测控用,可选

A.2.3备自投智能化装置接口数量基本要求见表A.2.3。

A.2.3备自投智能化装置接口数量基本要求

设备名称组网通信接口过程层接口备注

过程层端口数量中包含一

进线及分段备自投装置25个组网口,该端口也可用

于点对点

主变及分段备自投装置25—

扩大内桥备自投装置24—

A.2.4进线、主变及分段(桥)备自投智能化装置GOOSE输出虚端子见表A.2.4。

A.2.4进线、主变及分段(桥)备自投智能化装置GOOSE输出虚端子表

序号信号名称软压板引用路径备注

主变备自投跳

PIGO/H1TrPTRC1.Tr.gener

1跳电源1高断路器跳电源1高断路器1#主变高压侧断

al路器

PIGO/L1TrPTRC1.Tr.gener

2跳电源1断路器跳电源1断路器—

al

主变备自投跳

PIGO/H2TrPTRC1.Tr.gener

3跳电源2高断路器跳电源2高断路器2#主变高压侧断

al路器

PIGO/L2TrPTRC1.Tr.gener

4跳电源2断路器跳电源2断路器—

al

PIGO/Bus1TrPTRC1.Tr.gen

5跳分段断路器跳分段断路器—

eral

主变备自投合

PIGO/H1ClPTRC1.Tr.gener

6合电源1高断路器合电源1高断路器1#主变高压侧断

al路器

PIGO/L1ClPTRC1.Tr.gener

7合电源1断路器合电源1断路器—

al

8合电源2高断路器合电源2高断路器PIGO/H2ClPTRC1.Tr.gener主变备自投合

8

序号信号名称软压板引用路径备注

al2#主变高压侧断

路器

PIGO/L2ClPTRC1.Tr.gener—

9合电源2断路器合电源2断路器

al

PIGO/Bus1ClPTRC1.Tr.ge—

10合分段断路器合分段断路器

neral

11跳闸出口1跳闸出口1PIGO/PTRC1.Tr.general—

12跳闸出口2跳闸出口2PIGO/PTRC2.Tr.general—

13跳闸出口3跳闸出口3PIGO/PTRC3.Tr.general—

14跳闸出口4跳闸出口4PIGO/PTRC4.Tr.general—

15跳闸出口5跳闸出口5PIGO/PTRC5.Tr.general—

16跳闸出口6跳闸出口6PIGO/PTRC6.Tr.general—

17跳闸出口7跳闸出口7PIGO/PTRC7.Tr.general—

18跳闸出口8跳闸出口8PIGO/PTRC8.Tr.general—

19跳闸出口9跳闸出口9PIGO/PTRC9.Tr.general—

20跳闸出口10跳闸出口10PIGO/PTRC10.Tr.general—

21跳闸出口11跳闸出口11PIGO/PTRC11.Tr.general—

22跳闸出口12跳闸出口12PIGO/PTRC12.Tr.general—

23跳闸出口13跳闸出口13PIGO/PTRC13.Tr.general—

24跳闸出口14跳闸出口14PIGO/PTRC14.Tr.general—

25跳闸出口15跳闸出口15PIGO/PTRC15.Tr.general—

26跳闸出口16跳闸出口16PIGO/PTRC16.Tr.general—

27备自投动作—PIGO/GGIO1.Ind1.stVal—

A.2.5扩大内桥接线备自投智能化装置GOOSE输出虚端子见表A.2.5。

A.2.5扩大内桥接线备自投智能化装置GOOSE输出虚端子表

序号信号名称软压板引用路径备注

1跳电源1断路器跳电源1断路器PIGO/L1TrPTRC1.Tr.general—

2跳电源2断路器跳电源2断路器PIGO/L2TrPTRC1.Tr.general—

3合电源1断路器合电源1断路器PIGO/L1ClPTRC1.Tr.general—

4合电源2断路器合电源2断路器PIGO/L2ClPTRC1.Tr.general—

5合内桥1断路器合内桥1断路器PIGO/Int1ClPTRC1.Tr.general—

6合内桥2断路器合内桥2断路器PIGO/Int2ClPTRC1.Tr.general—

7跳内桥1断路器跳内桥1断路器PIGO/Int1TrPTRC1.Tr.general—

8跳内桥2断路器跳内桥2断路器PIGO/Int2TrPTRC1.Tr.general—

9跳闸出口1跳闸出口1PIGO/PTRC1.Tr.general—

10跳闸出口2跳闸出口2PIGO/PTRC2.Tr.general—

11跳闸出口3跳闸出口3PIGO/PTRC3.Tr.general—

12跳闸出口4跳闸出口4PIGO/PTRC4.Tr.general—

13跳闸出口5跳闸出口5PIGO/PTRC5.Tr.general—

14跳闸出口6跳闸出口6PIGO/PTRC6.Tr.general—

15跳闸出口7跳闸出口7PIGO/PTRC7.Tr.general—

9

序号信号名称软压板引用路径备注

16跳闸出口8跳闸出口8PIGO/PTRC8.Tr.general—

17跳闸出口9跳闸出口9PIGO/PTRC9.Tr.general—

18跳闸出口10跳闸出口10PIGO/PTRC10.Tr.general—

19跳闸出口11跳闸出口11PIGO/PTRC11.Tr.general—

20跳闸出口12跳闸出口12PIGO/PTRC12.Tr.general—

21跳闸出口13跳闸出口13PIGO/PTRC13.Tr.general—

22跳闸出口14跳闸出口14PIGO/PTRC14.Tr.general—

23跳闸出口15跳闸出口15PIGO/PTRC15.Tr.general—

24跳闸出口16跳闸出口16PIGO/PTRC16.Tr.general—

25备自投动作—PIGO/GGIO1.Ind1.stVal—

A.2.6故障解列装置接口数量基本要求见表A.2.6。

A.2.6故障解列智能化装置过程层接口数量基本要求

设备名称组网通信接口过程层接口备注

点对点接口用于跳

故障解列装置110kV

25线路

A.2.7故障解列装置GOOSE输出虚端子见表A.2.7。

A.2.7故障解列装置GOOSE输出虚端子表

序号信号名称软压板引用路径备注

1跳闸出口1跳闸出口1PIGO/PTRC1.Tr.general—

2跳闸出口2跳闸出口2PIGO/PTRC2.Tr.general—

3跳闸出口3跳闸出口3PIGO/PTRC3.Tr.general—

4跳闸出口4跳闸出口4PIGO/PTRC4.Tr.general—

5跳闸出口5

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论