下载本文档
版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
1、精品 料推荐selection and rating of transformersa). introductionthe number of non-linear loads which draw non-sinusoidal currents even if fed with sinusoidal voltage - connected to the power supply system is large and is continuing to grow rapidly. these currents can be defined in terms of a fundamental c
2、omponent and harmonic components of higher order.in power transformers the main consequence of harmonic currents is an increase in losses, mainly in windings, because of the deformation of the leakage fields. higher losses mean that more heat is generated in the transformer so that the operating tem
3、perature increases, leading to deterioration of the insulation and a potential reduction in lifetime.as a result, it is necessary to reduce the maximum power load on the transformer, a practice referred to as de-rating, or to take extra care in the design of the transformer to reduce these losses.to
4、 estimate the de- rating of the transformer, the load -factor may sbek used. this factor is calculated according to the harmonic spectrum of the load current and is an indication of the additional eddy current load losses. it reflects the excess losses experienced in a traditional wire wound transfo
5、rmer.modern transformers use alternative winding designs such as foil windings or mixed wire/foil windings.b). transformer lossestransformer losses consists of no-load (or core loss) and load losses. this can be expressed by the equation below.where:pc = core or no-load loss,pll = load losspt = tota
6、l loss.core or no-load loss is due to the voltage excitation of the core. although the magnetizing current does include harmonics, these are extremely small compared with the load current and their effect on the losses is minimal. load losses are made up of i2 r loss, eddy current loss and stray los
7、s, or in equation form:where:i2r = loss due to load current and dc resistance of the windingspec = winding eddy current losspsl = stray losses in clamps, tanks, etc.the i2r loss is due to the current flowing in the resistance of the windings. it is also called ohmic loss or dc ohmic loss. the ohmic
8、loss is proportional to the square of the magnitude of the load current, including the harmonic components, but is independent of the frequency. it is determined by measuring the dc resistance and calculating the resulting loss using the winding currents at full load.there are no test methods availa
9、ble to determine individual winding eddy current loss or to separate transformer stray loss from eddy current loss. instead, the total stray and eddy current loss is determined by determining the total load loss and subtracting the calculated ohmic losses, i.e.,the eddy current loss is assumed to va
10、ry with the square of the rms current and the square of the frequency (harmonic order h), i.e.,where:1精品 料推荐h = harmonic order, 1,2,3, etc.hmax = the greatest harmonic order to be consideredi h = current at harmonic orderh, amperes h,i r = rated current, amperes ,pec,r = eddy current loss at rated c
11、urrent and frequency.the eddy current loss depends on the square of the conductor dimension perpendicular to the leakage flux field. at the ends of the winding the flux field bends and the larger dimension of the rectangular conductor is perpendicular to a vector component of the leakage flux field.
12、 equalizing the height of die primary and secondary windings, which can be achieved with any winding design, reduces the concentrated eddy loss at the winding ends. using foil windings or multiple strands per winding reduces both eddy current loss.stray loss occurs due to the stray flux which introd
13、uces losses in the core, clamps, tank and other iron parts. stray loss may raise the temperatures of the structural parts of the transformer. for dry-type transformers increased temperatures in these regions do not contribute to an increase in the winding hot spot temperature. stray losses are diffi
14、cult to calculate and it is common to assume that the losses will vary as the square of the current times the frequency (harmonic order), as shown by:c). transformers and k-factorthere are different approaches to accounting for additional losses in selecting a transformer. here we would suggest the
15、way applied by transformer manufacturers in conjunction with underwriters laboratories in the united states, it is to calculate the factor increase in eddy current loss and specify a transformer designed to cope; this is known as the -kfactor .where:h = harmonic numberi h = the fraction of total rms
16、 load current at harmonic numberhmany power quality meters read the k-factor of the load current directly. once the k-factor of the load isknown, it is a simple matter to specify a transformer with a higher k-rating from the standard range of 4, 9, 13, 20, 30, 40, 50.note that a pure linear load one
17、 that draws a sinusoidal current would have a k-factor of unity. a higher k-factor indicates that the eddy current loss in the transformer will be k times the value at the fundamental frequency. -krated transformers are therefore designed to have very low eddy current loss at fundamental frequency.d
18、). transformer design considerationmany transformer manufacturers have developed designs rated for non-sinusoidal load currents while optimizing their production costs. the design process involves an analysis of the eddy current loss distribution in the windings and calculation of the hot spot tempe
19、rature rise. analysis of the eddy loss distribution may be performed using finite element or other type computer programs. thermal studies should be conducted using embedded thermocouples installed in test windings of prototype transformers to measure hot spot temperature to refine mathematical mode
20、ls to calculate the hot spot temperature.2精品 料推荐the subject of harmonics has received much publicity in recent times leading to the belief that the industry is only just beginning to understand the effect of harmonics and to calculate the increased eddy current losses. in fact, the study of the effe
21、cts is quite old, with eddy current losses in conductors in a magnetic field dating from 1906. many early investigations were highly mathematical and the flux plots given in these early papers were every bit as detailed, and probably as accurate, as those produced by modern computer programs.althoug
22、h hot spot temperature is an important performance parameter to be met by the manufacturer, there are currently no defined test methods, nor is there a requirement that this parameter be measured on production or prototype transformers. this is important since temperature is fundamental in determini
23、ng the life of the equipment.the hot spot temperature in dry-type transformers is sometimes a contentious issue. hot spots, the positions of the highest temperature, occur naturally due to the non-uniform heat generation and the fact that the rate of heat transfer to the environment is not uniform;e). k-13 or k-20 transformer?transformers shall be capable of operating within the specified temperatur
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 湖南省湘西州重点中学2025-2026学年高中毕业班第二次诊断性检侧(物理试题文)试题含解析
- 陕西省安康市汉滨2025-2026学年初三物理试题中考模拟试题含解析
- 黑龙江省哈尔滨市双城区2026年初三年级期末调研考试(数学试题)试卷含解析
- 海南省琼中学县2025-2026学年初三第一次适应性测试数学试题含解析
- 广东省梅州市大埔县市级名校2025-2026学年初三一模数学试题(海淀一模)试卷含解析
- 患者入院护理伦理决策
- 国税教育培训制度
- 导游教育培训制度
- 四大事务所绩效考核制度
- 医疗机构审计制度
- 车间安全生产检查记录表
- 2025年机关事业单位工勤技能岗位等级考核试题机关工勤等级考试附答案
- 2025年湖北省烟草专卖局(公司)招聘206人笔试参考题库附带答案详解
- 2025年安徽省综合类事业单位招聘考试公共基础知识真题试卷及参考答案
- 生活垃圾收集人员培训管理方案
- 薪资核定及管理办法
- 劳动课自制沙拉课件
- 药膳养生鸡汤培训课件
- 监狱辅警面试题目及答案
- 十五五特殊教育发展提升行动计划
- 医院运营数据统计分析
评论
0/150
提交评论