住宅建筑给水管水力计算算例及讨论_第1页
住宅建筑给水管水力计算算例及讨论_第2页
住宅建筑给水管水力计算算例及讨论_第3页
住宅建筑给水管水力计算算例及讨论_第4页
住宅建筑给水管水力计算算例及讨论_第5页
已阅读5页,还剩9页未读 继续免费阅读

下载本文档

版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领

文档简介

住宅建筑给水管水力计算算例及讨论摘要: 通过对当前新建的典型普通多层住宅生活给水系统详细的水力计算,得出在设定的流速范围内管道和水表的口径及水头损失。从而得出为满足使用要求需要的室外干管水压,最后对涉及的有关问题进行了讨论。Hydraulic Calculation of Water Supply Line for Residential BuildingHuang Yunfei et alAbstract: Minute hydraulic calculation was conducted for newly constructed multi-story residential buildings. The size and headlosses of the water supplying pipeline and meters under pre-decided flowrate were obtained and then the necessary pressure of outdoor water mains could be determined. Also some related problems were discussed.0概述 规范GBJ15-88(简称规范)第2.6.3条规定:给水管的管径应根据设计秒流量、室外管网能保证的水压和最不利处的配水点所需的水压计算确定。本文通过设定的典型住宅生活给水管的水力计算,谋求在一定的流速范围内,可供压力与管道、水表配置的协调,达到使用要求与工程经济的最佳组合。1典型住宅的设定 选用常州市在住宅小区规划设计中常用的5层7层多层住宅。为寻找规律性,计算外延至9层。 采用常州市当前新设计住宅常用的设备配置标准,如表1。表1住宅给水设备的配置和当量采用设备名称配置数量规范给水当量住宅厨房洗涤盆1(0.7)1.0洗脸盆1(0.8)1.0浴盆(附淋浴器)1(0.1)1.5大便器浮球阀式冲洗水箱10.5家用洗衣机11.2合计(4.2)5.2注:不计一户双卫。按规范,前3项括号中的值,用于有热水供应(第3类住宅)且冷水和热水分别到达用水器具时计算冷水系统用。笔者考虑,目前南方地区有集中式热水供应的小区较罕见,但家用燃气式或电热式热水器在新的成套住宅中实际上已被越来越多地采用,住宅设计应正视这个事实。这些“准热水供应系统”较多采用单管供应热水,其给水当量值采用不带括号的数字。 这里选用目前较多使用的1梯(单元)2户,给水双立管,1总表和每户设分水表(户表)的3梯(单元)楼。室外(庭院)管布至山墙间道路(通常在该路上有城市或小区给水干管),其长度按较典型的楼房设计取值。本算例设定的给水系统图见图1。图1住宅给水系统图以目前仍广泛采用的镀锌钢管为水力计算依据,并以UPVC管作对比说明。2设计公式与参数 按规范,住宅设计秒流量q=. 0.2+K . Ng。这里和K值的采用,如按第2类型住宅(无热水供应),则=1.02,K=0.004 5;如按第3类型住宅(有热水供应),则=1.10,K=0.005。考虑到、K值均与用水规律有关,上述的准热水供应系统和社会集中热水供应系统在档次上还有区别,故仍采用第2类住宅标准,即=1.02,K=0.004 5。 住宅需要水压H1=控制点与室外给水管道的几何水头H2+供水至控制点的水头损失H3+控制点所需的自由水头H4。 (1)控制点及其安装高度的确定。按规范,家庭用水器具以淋浴器的控制阀(图1中A)需要的自由水头最大,为2.5m4.0m,高于其它用水器具的1.5m2.0m,理应作为控制点。按标准图,与浴盆配套使用的软管式淋浴器的A点安装高度为地板以上0.510m0.565m,本算例采用0.55m。 (2)H3为图A系统总水头损失,含BC、CD、DE、EF、FG、GH等6个管段的水头损失。各管段按常规配置了弯头、三通等配件,考虑到水力计算的简化及阻力较大的管衬还时有使用等因素,假设各管段均设有1只大小头。 (3)H4在这里指淋浴器需要的自由水头,可用两种方法具体确定。一是参照规范,范围为2.5m4.0m,考虑到顶层(最不利层)不宜使用大阻力淋浴器,可采用H4=3.0m;二是按屋顶水箱安装高度反算,按江苏通用图集苏G9206,住宅水箱安装高度为水箱内底高于屋面0.72m,换算至淋浴器控制阀处的净水头为2.9+0.72-0.55=3.07m。两种方法基本一致,故本算例采用H4=3.0m。 按上述设定条件和系统图,本水力计算范围,起点为住宅楼给水支管(即庭院管)的起点H,终点为末单元顶层住户的淋浴器控制阀A,其需要自由水头3.0m。当控制点A转换成安装高度为1m的户表后侧B点时,需要的自由水头H4=3+0.55-1=2.55m(这里不计室内管道的水头损失)。当住宅室内外地坪高差0.45m(3个踏步级),不计室外管道埋深,住宅层高为2.9m,则5、6、7、8、9层的H2分别为13.05m、15.95m、18.85m、21.75m和24.65m。3水力计算3.1管道设计流速V的采用 按规范,生活给水管V2m/s,并规定当有防噪声要求且管径DN25,可采用0.8m/s1.0m/s。给水排水设计手册(2)还规定,生活给水管道流速一般采用支管0.8m/s1.2m/s,干管1.2m/s2.0m/s。本算例水力计算按3个流速系列(方案)分别计算,设定的流速系列见表2。表2流速方案设定流速方案DN25DN3211.201.4021.401.6531.651.903.2管道水头损失 沿程损失查给水排水设计手册(1)的钢管和铸铁管水力计算表。局部损失采用局阻系数法计算。表3为9层住宅楼的水力计算,其BC段含58层相应段的计算。表4为58层的CH段水力计算。表3九层住宅楼水力计算管段编号当量q/L/s方案DN/mmV/m/s1 000il/m沿程压损/m值局部压损/m备注B-C15.20.4912250.941132.90.331.840.08闸门0.5,弯头1.0,大小头0.24,三通0.10。3201.554111.190.23210.40.701320.7449.52.90.140.340.009大小头0.24三通0.1023251.322140.620.03315.60.8813320.92752.90.220.340.015同2420.81.0213321.101002.90.290.340.02同2526.01.1613321.221262.90.360.340.03同2631.21.2813321.351422.90.410.340.03同2736.41.391401.1188.42.90.260.340.02同223321.481840.530.04841.61.511401.191012.90.290.340.02同223321.582110.610.04C-D46.81.6112401.271144.00.462.740.23闸门0.50,弯头1.0,大小头0.24,分流式三通1.03321.692400.960.40D-E93.62.3913501.1364.54.00.263.500.23闸门0.5,弯头(3只)3.0E-F93.62.3913501.1364.516.01.040.340.02同2F-G187.23.6312701.033916.00.620.340.02同23501.711482.370.05G-H280.84.6813701.336416.01.022.900.26闸门0.4,弯头(2只)2.0三通0.5表458层住宅楼CH段水力计算管段编号当量q/L/s方案DN/mmV/m/s1000il/m沿程压损/m值局部压损/mC-D段5层261.1613321.221264.00.502.740.216层31.21.2813321.371590.640.237层36.41.391/2340/321.10/1.4787/1820.35/0.730.17/0.328层41.61.511/2340/321.19/1.58101/2110.40/0.840.20/0.35D-E段5层521.7012/340/321.32/1.79129/2714.00.52/1.083.50.31/0.576层62.41.891/2350/400.98/1.5141.8/1610.18/0.640.17/0.647层72.82.071/2350/400.98/1.6450/1860.20/0.740.17/0.488层83.22.2312/350/401.06/1.8056/2340.22/0.940.20/0.58E-F段5层521.7012/340/321.35/1.79129/27116.02.06/4.330.340.03/0.066层62.41.891/2350/400.98/1.5141.8/1610.67/2.580.017/0.047层72.82.071/2350/400.98/1.6450/1860.80/2.980.02/0.058层83.22.2312/350/401.06/1.8056/2340.90/3.740.02/0.06F-G段5层1042.5513501.207316.01.170/340.026层124.82.8413501.35901.440.037层145.63.121/2370/500.88/1.4629.1/1070.46/1.710.01/0.048层166.43.381/2370/500.96/1.6034.5/1280.55/2.050.02/0.04G-H段5层1563.251/2370/500.82/1.5332/11816.00.51/1.892.900.10/0.356层187.23.6312/370/501.02/1.6938.4/1440.61/2.300.15/0.427层218.43.9912/370/501.13/1.8846.8/1770.75/2.830.19/0.528层249.64.3413701.23540.860.413.3水表水头损失 水头损失,Q为以m3/h计的设计流量,K为水表的特性系数,口径为DN15mm、20mm、25mm、32mm、40mm、50mm、80mm的LXS旋翼式水表的K值的计算结果分别为0.9、2.5、4.9、10、40、90、490。按规范,LXS型水表的最大水头损失不得超过2.45m。水表水力计算见表5。表5水表水力计算住宅层数所在管段q/L/sQ/m3/hQ2表径/mmK值V/m/s水表压损/m户表BC段之0.491.763.11(25204.92.50.941.550.63)1.245 D-E 1.70 6.12 37.45 (5040(329040100.801.321.790.42)0.943.75)6D-E1.896.8046.2940(3240101.511.871.164.63)7D-E2.077.4555.50(504090400.981.640.62)1.398D-E2.238.0064.00(504090401.061.800.71)1.609D-E2.398.6073.9650(4090401.131.910.821.85)确定水表口径时综合考虑下列因素:一是户表一般安装在室内,必须考虑其噪声问题;二是表径的大小直接关系到向供水部门缴纳增容费的多少;三是水表的更换比较容易。为此本算例按适度从紧、稍留余地的原则,具体采用:户表流速1.6m/s,压损1.5m;总表流速1.8m/s,压损1.7m。表5中不带括号者为本算例所采用,不再作方案比选。 汇总以上计算结果,住宅给水管道水头损失及对供水压力需求值见表6。表6水头损失及压力需求汇总住宅层数流速方案几何水头H2水头损失H3控制点自由水头H4住宅需要水头H1管道水表(户表+总表)合计沿程局部5113.055.740.7942.188.7142.5524.31427.101.06510.34525.945311.291.50514.97530.5756115.954.880.7512.408.0312.5526.53127.731.26510.89529.395310.281.68514.36532.8657118.854.310.7442.637.6842.5529.08429.141.28513.05534.455312.081.76516.47537.8758121.754.941.0542.848.8342.5533.13427.631.26511.73536.035312.051.83516.72541.0259124.655.700.9842.068.7442.5535.94426.771.0459.87537.07539.881.39513.33540.5354讨论 (1)对于生活给水系统,规范中有“当有防噪声要求,且管径25时,可采用0.8m/s1.0m/s”的规定。笔者理解,因受管道公称直径级别的限制,该流速规定并非一定要在该范围内取值(这实际上往往是不可能的),而是能取该值更好。本算例确定的流速方案,以不大于某值来划分。以本算例9层住宅楼为例,3个方案的实际采用流速的平均值为:DN25时,分别为0.94m/s、1.13m/s和1.44m/s;DN32时分别为1.08m/s、1.26m/s和1.41m/s。 (2)在设定的流速条件下,住宅楼(含通常情况下的庭院管道)的层数与需求水压的关系见表6。受管径公称级别的限制有个别的突起突降现象,但总的反映较为规律。与手册二提出的按层数估算需求水压值比较,后者相当于本算例流速方案1与方案2之间。而估算法没有明确室外需求水压出现在哪一部位,需求水压值内是否包含了庭院管道及几只水表的压损,所以只能用于粗略的大概估算。 由本算例可知9层住宅楼的底层用户(即C点)水压,即使第3方案也没有超过35m,无需减压。 关于3个流速方案的具体采用,笔者以为在一般情况下宜采用需求水压较低的方案1,这也为用水设备进一步改善留有余地。当设计的住宅位于水压有确切保障的区域(小区),也可采

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150