1、作者:Pan Hon glia ng仅供个人学习摘要为满足经济发展的需要,根据有关单位的决定修建1座110KV延长变电所.本工程初步设计内容包含变电所电气设计,新建的延长变电所从110KV侧清涧变电所受电,其负荷分为35KV和10KV两个电压等级. 通过技术和经济比较,现采用下列方案:1. 内设两台三绕组变压器,电压等级为121/37.8/11.2. 110KV进线采用内桥接线形式.3. 本工程初步设计内容包括变电所电气设计.4. 35KV和10KV配电装置同样采用单母线分段接线.5. 所用电分别从10KV两端母线获得.关键词:变电所主变压器潮流计算短路计算设备选型AbstractFor sa

2、tisfy ing the dema nd that economy developme nt, the authorities concerned decide to con struct a Yan Cha ng tran sformer substati on.This engineering first step design contents includes the transformer substation of electricDesign. The new-et up salt a YanChangtransformersubstati on obta in power f

3、orm Qi ng Jia n substati on (110KV) . There are two kinds of local loads in the substation,. One is 35KV,the other is 10KV.Pass the tech nique to compare with the economy, adopt the follow ing scheme now:1. There are two three-winding transformers in the substation. Voltage grade adopt 121KV 38.5KV

4、and 11KV.2. For 110KV main electricalconn ecti ons shall adopt in side bridgeconn ecti on.3. The 110KVenters the line 2 return, The adoption builds trolley wire.4. For 35KV and 10KV main electricalconnectionsemploy singlesecti on alized bus.5. Auxiliary power system get power form the 10KV sectional

5、ized bus.Key phrase:Change to give or get an electric shockMain tran sformer Curre nt calculati onShort circuit calculati onThe equipme nts choose the type目录第一章原始资料分析4.第二章110KV延长变电所接入系统设计 .6.第三章110KV延长变电所地方供电系统设计 7第四章110KV延长变电所主变选择 16第五章所用变选择24第六章主接线设计24第七章 短路电流计算错误!未定义书签。第八章变电所电气设备选择 35第九章继电保护配置58参

6、考文献60.110KV延长变电所设计说明书根据西安科技大学电气工程及其自动化专业(函授)毕业设计任务书的 要求,设计110KV延长变电所.110KV延长变电所,采用双回110KV线路接入系统.35KV、10KV配电线 路均采用双回线供电.110KV采用内桥接线,安装两台SFPSZ9-75000/110三相三线圈变压器.35KV、10KV母线采用单母线分段接线.第一章原始资料分析一、原始资料1、待建110KV延长变电站从相距30km的110KV清涧变电站受电.2、待建110KV延长变电站年负荷增长率为5%,变电站总负荷考虑五年发展规划.3、地区气温:?1?年最高气温45C,年最低气温 -5C .

7、?2?年平均气温15C .4、待建110KV延长变电所各电压级负荷数据如下表:电压 等级线路名称最大负荷(MW)COS负荷级别供电距离(KM )T max 及 同时率35KVA200.851105000/0.9B150.8112冶炼厂110.828天然气厂200.827采油厂150.8511010KVA30.8511.53500/0.85B20.8522.5煤矿10.821.0水泥厂1.20.821.5原油集输站0.80.821.0水厂20.811.5、对原始资料的分析计算为满足电力系统对无功的需要,需要在用户侧装设电容器,进行无功补偿, 使用户的功率因数提高,35kV线路用户功率因数提高到0

8、.9为宜,10kV线路用 户功率因数应不低于0.9.根据原始资料中的最大有功及调整后的功率因数,算出最大无功,可得出以下数据:电压 等级线路 名称最大有功(MW)最大无功(MVAr)COS负荷级别T max同时 率35KVA209.190.9150000. 9B157.270.91冶炼厂115.330.92天然气厂209.190.92采油厂157.270.9110KVA31.460.9135000. 85B20.920.92煤矿10.490.92水泥厂1.20.580.92原油集输站0.80.390.92水厂20.920.91第二章110KV延长变电所接入系统设计一、确定电压等级输电线路电压等

9、级的确定应符合国家规定的标准电压等级选择电压等级时,应根据输送容量和输电距离,以及接入电网的额定电压的情况来确定, 输送 容量应该考虑变电所总负荷和五年发展规划因此待建110KV延长变电所的最高 电压等级应为110kV.二、确定回路数110KV延长变电所建成后,所供用户中存在I、U类重要负荷,因此110KV延长变电所应采用双回110KV线路接入系统.三、确定110KV线路导线的规格、型号由于待建110KV延长变电所距离受电110KV清涧变电站65KM ,处于山区 河网地区,因此应采用架空线路,导线选择LGJ型.四、110KV线路导线截面选择导线截面积选择的一般方法是:先按经济电流密度初选导 线

10、标称截面积,然后进行电压损失的校验1、待建110KV延长变电所总负荷的计算S 35 =R5+jQ35 =20+ 15+ 11 + 20+ 15+ j(9.19+7.27+5.33+9.19+7.27+) =81+j38.255S5 (1+5%=( 81+j38.25 )X 1.28 = 103.7+j49S35= 114.8S 10 =Po+jQ1o =3+2+1+1.2+0.8+2+j(1.46+0.92+0.49+0.58+0.39+0.92) =10+j4.765So (1+5%=( 10+j4.76 ) X 1.28 = 12.8+j6.1So =14.25S 110=Kh0K35sB

11、5+K|0S|0 ( 1+5%5 =0.950.9(81+j38.25)+0.85(10+j4.76)*1.05=98.7+j46.65S110=V(98.7 2 + 46.65 2 ) = 109.2COS> = P 110 / S 110 =98.7/109.2 = 0.92、 根据Tmax查图3- 1,软导线经济电流密度表,确定 JecP35*Tmax35+Pi0*Tmax1081*5000+10*3500T max= 4835(小时)P35+P1081+10查图 3 1 得 Jec = 1.15 (A/mrn)3、计算导线的经济截面积 S,查附表1 21找出S选I j0.5S11

12、0/ (V3 Un)32S J=一一一249.2伸口确定回路数35KV A线路所供用户为I类重要负荷,因此应采用双回线路供电. 确定线路导线的规格、型号由于待建110KV延长变电所处于平原河网地区,因此采用架空线路,导线 选择LGJ型. 线路导线截面选择(1) 35KV A线路总负荷的计算5S 35 一R5+jQ35 =(20 + j9.19)*(1+5%)一 25.5+ j11.7S 35一V(25.5 2 + 11.7 2 ) 一 28.1CO 一 P 110 / S 110 =25.5/28.1 一 0.9)J J1.154、 结论:选取导线规格为2回LGJ- 240/405、对所选导线

13、进行校验;按机械强度校验选一LGJ-240/40大于LGJ-35,符合要求.、选一LGJ-240/40大于LGJ-70,符合要求.按电压降校验接电晕校验S(3)、 正常运行时:n=2PR+QX98.7 X 0.12 X 30 + 46.65 X 0.4 X 30 U% 一一X100%2UN22X1102=3.8% < 10%,符合要求.98.7 X 0.12 X 30 + 46.65 X 0.4 X 30X 故障运行时,考虑一条回路因故障切除,另一条回路能保证全部负荷供电PR+QX100%N2110=7.6% < 15% ,符合要求.结论:本变电所经上述计算、校验,决定采用 接入系

14、统.第三章110KV延长变电所地方供电系统设计一、35KV A线路设计 U% 一-2 回 LGJ 240/40 导线U(2) 根据Tmax查图3- 1,软导线经济电流密度表,确定 JecTmax= 5000(小时)查图 3- 1 得 Jec = 1.12 (A/mrn)3=209(mm)(3) 计算导线的经济截面积SJ,查附表1-21找出S选I j0.5S35/ (V3 Un)S j=J J1.12 结论:选取导线规格为2回LGJ- 185/304、对所选导线进行校验;(1) 、按机械强度校验S 选=LGJ- 185/30大于LGJ-35,符合要求.(2) 、接电晕校验S选=LGJ- 185/

15、30大于LGJ-70,符合要求.(3) 、按电压降校验 正常运行时:n=2PR+QX25.5 X 0.17 X 10+ 11.7 X 0.38 X 10 U% =X100%2 22Un2X 35=3.5% < 10%,符合要求. 故障运行时,考虑一条回路因故障切除,另一条回路能保证全部负荷供电PR+QX25.5 X 0.17 X 10+ 11.7 X 0.38 X 10 U% =X 100%2 2UN35=7% < 15%,符合要求.二、35KV B线路设计1、确定回路数35KV B线路所供用户为I类重要负荷,因此应采用双回线路供电.2、确定线路导线的规格、型号由于待建110KV延

16、长变电所处于山区河网地区,因此采用架空线路,导线选择LGJ型.3、线路导线截面选择(1) 35KV B线路总负荷的计算5S 35 =P35+jQ35 =(15 + j7.27)*(1+5%)=19.1 + j9.3S 35=V(19.1 2 + 9.3 2 ) = 21.2CO = P 110 / S 110 =19.1/21.2 = 0.9 根据Tmax查图3- 1,软导线经济电流密度表,确定 JecTmax= 5000(小时)查图 3- 1 得 Jec = 1.12 (A/mrn)32=156.1(mm )(3)计算导线的经济截面积SJ,查附表1-21找出S选I j0.5S35/ (V3

17、Un)S j=J J1.12 结论:选取导线规格为2回LGJ- 150/254、对所选导线进行校验;(1) 、按机械强度校验S 选=LGJ-150/25大于LGJ-35,符合要求.(2) 、接电晕校验S选=LGJ-150/25大于LGJ-70,符合要求.(3) 、按电压降校验正常运行时:n=2PR+QX19.1 X 0.21 X 12+ 9.3 X 0.387 X 12 U% =X 100%2 22Un2X 35=3.7% < 10%,符合要求.故障运行时,考虑一条回路因故障切除,另一条回路能保证全部负荷供电PR+QX19.1 X 0.21 X 12+ 9.3 X 0.387 X 12

18、U% =X 100%2 2UN35=7.4% < 15%,符合要求.三、35KV冶炼厂线路设计1、确定回路数35KV冶炼厂线路所供用户为U类重要负荷,因此采用双回线路供电.2、确定线路导线的规格、型号由于待建110KV延长变电所处于山区河网地区,因此采用架空线路,导线 选择LGJ型.3、线路导线截面选择(1) 35KV冶炼厂线路总负荷的计算5S 35=R5+jQ35 =(11 + j5.33)*(1+5%)=14+ j6.8S 35=V(142 + 6.8 2 ) = 15.56CO = P 110 / S 110 =14/15.56 = 0.9(2) 根据Tmax查图3- 1,软导线经

19、济电流密度表,确定JecTmax= 5000(小时)查图 3- 1 得 Jec = 1.12 (A/mrn)(3)计算导线的经济截面积Sj,查附表1-21找出S选I J0.5S35/ (V3 Un)S j=J J1.1232=114.6(mm )结论:选取导线规格为2回LGJ- 120/254、对所选导线进行校验;(1) 、按机械强度校验S 选=LGJ-120/25大于LGJ-35,符合要求.(2) 、接电晕校验S 选=LGJ-120/25大于LGJ-70,符合要求.(3)、按电压降校验正常运行时:n=2PR+QX14X 0.22 X 8 + 6.8 X 0.39 X 8 U% =2 2UN3

20、5=3.7% < 10%,符合要求.100%故障运行时,考虑一条回路因故障切除,另一条回路能保证全部负荷供电PR+QX14X 0.22 X 8 + 6.8 X 0.39 X 8 U% =X 100%2 2UN35=7.4% < 15%,符合要求.四、35KV天然气厂线路设计1、确定回路数35KV天然气厂线路所供用户为U类重要负荷,因此采用双回线路供电2、确定线路导线的规格、型号由于待建110KV延长变电所处于山区河网地区,因此采用架空线路,导线选择LGJ型.3、线路导线截面选择(1) 35KV天然气厂线路总负荷的计算5 S 35=R5+jQ35 =(20 + j9.19)*(1+5

21、%)22S 35=V(25.5 + 11.7) = 28.1CO = P 110 / S 110 =25.5/28.1 = 0.925.5+ j11.7(2)根据Tmax查图3- 1,软导线经济电流密度表,确定 JecTmax= 5000(小时)查图 3- 1 得 Jec = 1.12 (A/mrm)3=209(mm)(3) 计算导线的经济截面积SJ,查附表1 21找出S选I J0.5S35/ (V3 Un)S j=J J1.12结论:选取导线规格为2回LGJ- 185/304、对所选导线进行校验;(1) 、按机械强度校验S 选=LGJ 185/30大于LGJ-35,符合要求.(2) 、接电晕

22、校验S选=LGJ 185/30大于LGJ-70,符合要求.(3) 、按电压降校验正常运行时:n=2PR+QX25.5 X 0.17 X 7+ 11.7 X 0.38 X 7 U% =X 100%2 22Un2X 35=2.45% < 10% ,符合要求.故障运行时,考虑一条回路因故障切除,另一条回路能保证全部负荷供电PR+QX25.5 X 0.17 X 7+ 11.7 X 0.38 X 7 U% =X 100%2 2UN35=4.9% < 15%,符合要求.五、35KV采油厂线路设计1、确定回路数35KV采油厂线路所供用户为I类重要负荷,因此应采用双回线路供电2、确定线路导线的规格

23、、型号由于待建110KV延长变电所处于山区河网地区,因此采用架空线路,导线选择LGJ型.3、线路导线截面选择(1) 35KV米油厂线路总负荷的计算5S 35 =P35+jQ35 =(15 + j7.27)*(1+5%)=19.1 + j9.322S 35=V(19.1+ 9.3) = 21.2CO = P 110 / S 110 =19.1/21.2 = 0.9(2) 根据Tmax查图3 1,软导线经济电流密度表,确定JecTmax= 5000(小时)查图 3 1 得 Jec = 1.12 (A/mrn)(3) 计算导线的经济截面积SJ,查附表1 21找出S选I j0.5S35/ (V3 Un

24、)2S j=156.1(mm)J J1.12结论:选取导线规格为2回LGJ 150/254、对所选导线进行校验;(1) 、按机械强度校验S 选=LGJ-150/25大于LGJ-35,符合要求.(2) 、接电晕校验S 选=LGJ-150/25大于LGJ-70,符合要求.(3) 、按电压降校验 正常运行时:n=2PR+QX19.1 X 0.21 X 10+ 9.3 X 0.387 X 10 U% =X100%2 22Un2X 35=3.08% < 10% ,符合要求. 故障运行时,考虑一条回路因故障切除,另一条回路能保证全部负荷供电PR+QX19.1 X 0.21 X 12+ 9.3 X 0

25、.387 X 12 U% =X100%2 2UN35=6.16% < 15%,符合要求.六、10KV线路设计1、10KV A 线路(1) 确定回路数,I类负荷,采用双回路供电,即n=2(2) 确定导线规格,采用架空线路,LGJ导线(3) 考虑五年发展需要,线路的容量:S = (3+j1.46)(1+5%)5 =3.83 + j1.86(4) 根据 Tmax= 3500h,,查图 3 1 得J ec = 1.26(A/mm 2)(5) 计算导线经济截面积:n=222VP+Q(V3.83 +1.86 ) X 1032S j = = 97.5 mm2V3 UNJec2X 1.732 X 10X

26、 1.26查附表1 21选取导线规格为2回LGJ- 95/20(6) 对所选导线进行校验 按机械强度校验S选=LGJ-95/20大于LGJ-35,符合要求. 按电压损耗校验,查附表1 25得r i=0.332, R =r il=0.332 X 1.5 = 0.50xi=0.356, X =xil=0.368 X 1.5 = 0.58*正常运行时:n=2(PR+QX)/2(3.83 U%U210X 0.5+1.86 X 0.58)/2 =1.5 % < 10%符合要求.*故障运行时:PR+QX U%Un=13.83X 0.5+1.86 X 0.58 =3% <15%1022、符合要求

27、.由以上可知,所选导线2回LGJ-95/20,符合要求.10KV B线路(1) 确定回路数,II类负荷,采用双回路供电,即n=2.(2) 确定导线规格,采用架空线路,LGJ导线.(3) 考虑五年发展需要,线路的容量:5S = (2+j0.92)(1+5%)=2.55 +1.17 j(4) 根据 Tmax= 3500h,,查图 3- 1 得2J ec = 1.26(A/mm )(5) 计算导线经济截面积:n=2VP+Q(V2.552+1.172) X 1032S j = = 64 mm2V3 UNJec2X 1.732 X 10X 1.26查附表1-21选取导线规格为2回LGJ- 70/10(6

28、) 对所选导线进行校验按机械强度校验S选=LGJ-70/10大于LGJ-35,符合要求.按电压损耗校验,查附表1-25得1=0.45, R = r 11 = 0.45 X 2.5 = 1.13X1=0.368, X = X1I = 0.368 X 2.5 = 0.92*正常运行时:n=2(PR+QX)/2(2.55 U%=2UNX 1.13+1.17 X 0.92)=2.0 % < 10%22X 10符合要求.'故障运行时:n=1PR+QX 2.55 U%=2UN符合要求.X 1.13+1.17 X 0.92=4 % < 15%102由以上可知,所选导线2回LGJ-70/1

29、0,符合要求.3、10K V煤矿专线(1) 确定回路数,II类负荷,采用双回路供电,即n=2.(2) 确定导线规格,采用架空线路,LGJ导线.(3) 考虑五年发展需要,线路的容量:5S = (1+j0.49)(1+5%)=1.28 + j0.63(4) 根据 Tmax= 3500h,,查图 3- 1 得2J ec = 1.26(A/mm )(5) 计算导线经济截面积:n=2VP+Q(V 1.282+0.632) X 1032S j = = 32.7 mm2V3 UNjec2X 1.732 X 10X 1.26查附表1-21选取导线规格为2回LGJ- 35/6(6) 对所选导线进行校验 按机械强

30、度校验S 选=LGJ-35/6等于LGJ-35,符合要求. 按电压损耗校验,查附表1-25得r1=0.9, R = r 1l = 0.9 X 1= 0.9X1=0.389, X = X1l = 0.389 X 1 = 0.39*正常运行时:n=2(PR+QX)/2(1X 0.9+0.49 X 0.39)=0.5 % < 10% U%=2 2UN2X10符合要求.*故障运行时:n=1PR+QX 1X 0.9+0.49 X 0.39 U%= 1 % < 15%2 2U N102符合要求.由以上可知,所选导线2回LGJ-70/10,符合要求.4、10K V水泥厂线 确定回路数,II类负荷

31、,采用双回路供电,即n=2.(2)确定导线规格,采用架空线路,LGJ导线.(3) 考虑五年发展需要,线路的容量:5S = (1.2+j0.58)(1+5%)=1.54 + j0.76(4) 根据 Tmax= 3500h,,查图 3- 1 得2J ec = 1.26(A/mm )(5) 计算导线经济截面积:n=2VP2+Q(V 1.542+0.762) X 1032S j = = 39.3 mm2V3 UNJec2X 1.732 X 10X 1.26查附表1-21选取导线规格为2回LGJ- 35/6(6) 对所选导线进行校验 按机械强度校验S选=LGJ-35/6等于LGJ-35,符合要求. 按电

32、压损耗校验,查附表1-25得r1=0.9, R = r 1l = 0.9 X 1= 0.9x1=0.389, X =x1l = 0.389 X 1 = 0.39*正常运行时:n=2(PR+QX)/2(1.54 U%UX 0.9+0.76 X 0.39)=0.8 % < 10%22X 10符合要求.*故障运行时:n=1PR+QX 1.54 U%-=2UNX 0.9+0.76 X 0.39 =1.6 % < 15%102符合要求.由以上可知,所选导线2回LGJ-70/10,符合要求.5、10kV原油集输站专线因原油集输站负荷较煤矿轻,供电距离与毛纺厂煤矿相同,又属于 II类重要 负荷,

33、故选择双回LGJ-35/6导线完全符合要求.6、10K V水厂线因水厂线属于I类重要用户,与10KV B线路负荷相同,供电距离小于10KV B 线路供电距离,因此选择和10KVB线路相同的双回LGJ-70/10线路完全可以满足要 求.第四章110KV延长变电所主变选择主变压器的型式、容量、台数直接影响主接线的形式和配电装置的结构 .它 的确定除依据传递容量基本原始资料外,还应根据电力系统 510年发展规划、 输送功率大小、馈线回路数、电压等级以及接入系统的紧密程度等因素, 进行综 合分析和合理选择在选择主变压器容量时对重要变电所, 应考虑当一台主变器停运时,其余变 压器容量在计及过负荷能力允许

34、时间内, 应满足I类及U类负荷的供电;对一般 性变电所,当一台主变压器停运时,其余变压器容量应能满足全部负荷的60%70%.本变电所主变容量按远景负荷选择,并考虑到正常运行和事故时过负荷能 力.一、主变方案选择1、 方案一:单台三相三绕组变压器,型号SFSZ9-120000/11Q电压等级 110/35/10.2、 方案二:两台三相双绕组变压器,其中一台型号为SFSZ9-90000/11Q 电压等级110/35;另一台为SFSZ9-20000/11Q电压等级110/10.3、 方案三:四台三相双绕组变压器,其中两台型号为SFSZ9-90000/11Q 电压等级110/38.5;另两台型号为SF

35、SZ9-12000/110,电压等级110/10.4、方案四:两台三相三绕组变压器, 型号为SFSZ9-75000/11Q电压等级 110/35/10.二、主变方案技术比较案较 、>比万案一万案二万案三方案四优点接线简单、占地面积小.接线简单.运行可靠性、 灵活性高,能 满足重要用户 的需要.运行可靠性、 灵活性高,能 满足重要用 户的需要.缺点运行可靠性、 灵活性差,不 能满足重要 用户的需要.运行可靠性、灵 活性差,不能满 足重要用户的需要-选用变压器 多,运行维护 工作量大.110KV盐北变电所有重要的I、 U类负荷,为满足运行的可靠性和灵活性, 应选择两台以上变压器,因此选择方案

36、三、方案四进行经济比较分析三、主变容量、参数选择1、方案三,如图35KV负荷由两台电压为110KV/35KV变压器供电,其中一台主变事故停运 后,另一台主变压器的容量应保证 35K V用户的一级和二级全部负荷的供电.35KV用户的一级和二级全部总容量:S35 = 89.57 (MVA),因此可选择两台SFPSZ9-90000/110型三相三绕组有载调压变压器,接线组别:YN, d11.10KV负荷由两台电压为110KV/10KV变压器供电,其中一台主变事故停运 后,另一台主变压器的容量应保证 10K V用户的一级和二级全部负荷的供电.10K V用户的一级和二级全部总容量:S10 = 11.08

37、 (MVA),因此可选择两台SFSZ9-12500/110型三相三绕组有载调压变压器,接线组别:YN, d11.2、方案四,如图所有负荷均由两台电压为110KV/35KV/10KV变压器供电,其中一台主变事 故停运后,另一台主变压器的容量应保证所有用户的70%全部负荷的供电.用户的70%全部总容量:SnQ = 76.3 (MVA),因此可选择SFPSZ9-75000/110 型三相三绕组有载调压变压器,接线组别:YN,y n0, d11.由于 15%Sii0 = 15 %X 109.2 (MVA) = 16.38(MVA) > S 10 = 11.08 (MVA),15%S110 = 1

38、5 %X 109.2 (MVA) = 16.38(MVA) < S 35 = 89.57 (MVA),因此主变110KV 35KV 10KV三侧容量分别为100% / 100 % / 50 %.3、主变主要技术参数选择(1)方案三:主变额定电压空载电流空载损耗负载损耗阻抗电压参考价(万元)SFPSZ9-90000/110110/350.35%74KW330KW'10.5440SFSZ9-12500/110110/100.3%18.1KW70KW10.5110(2)方案四:主变额定空载空载损负载阻抗参考价电压电流耗损耗电压(万元)SFPSZ9-75000/110110/35/100

39、.36%98.6KW356KW18587333KW10.5304KW6.5四、主变方案经济比较3、主变及其附属设备综合投资比较 方案三:SFPSZ9-90000/110主变两台,2X440= 880万元 SFSZ9-12500/110主变两台,2X 110= 220 万元110KV SF6断路器户外间隔四个,4 X 58.1=232.4万元 35KV SF6断路器户外间隔两个,2X 18.8=37.6万元 10KV真空断路器户内间隔两个,2X 9.1=18.2万元 综合投资:1388.2万元. 方案四:SFPSZ9-75000/110主变两台,2X400= 800万元 110KV SF6断路器

40、户外间隔两个,2X 58.1=116.2万元 35KV SF6断路器户外间隔两个,2X 18.8=37.6万元 10KV真空断路器户内间隔两个,2X 9.1=18.2万元 综合投资:972万元.2、主变年运行费用比较年运行费1 = ( a 1 + a 2 )X Z / 100+ pXA A 式中1 年运行费,元/年;a 1 基本折旧费,取4.8 %;a 2大修费,取1.4 %;z 投资费,元;A A 年电能损耗,KW.H年;B 电价,元 /KW.H,取 0.52 元/KW.H.(1) 方案三A A= 330X 8760X 2+ 70X 8760X 2 = 7008000KW.H1 = (4.8

41、% + 1.4%)X 1388.2 / 100+0.52 X 700.8=365.3(万 兀)方案四A A=( 356+ 333+ 304)X 8760/2 = 4349340KW.H 卩=(4.8% + 1.4%)X 972 / 100+0.52 X 434.9=226(万 元)3、结论、方案三方案四综合投资1388.2万元972万元年运行费用365.3万元226万元从上表比较可知,方案四比较方案三不管在综合投资方面,还是在年运行 费用都要经济,因此决定选用方案四两台SFPSZ9-75000/110三相三线圈变压器五、主变110KV侧分接头选择按电力系统电压和无功电力导则(试行)的规定,各级

42、变压器的额定 变比、调压方式、调压范围及每档调压值,应满足发电厂、变电所母线和用户受 电端电压质量的要求.各电压等级变压器分接开关的运行位置,应保证系统内各 母线上的电压满足要求,并在充分发挥无功补偿的技术经济效益和降低线损的原 则下予以确定.确定分接头范围分以下几个步骤:首先在最大运行方式下:(1)从系统母线电压推算到盐北变主变压器高压侧电压.(2)将35KV 10KV侧最大负荷距线路末端允许最低电压反推到变压器 高压侧电压.(3)参考电气工程专业毕业设计指南一电力系统分册中的电压调 整:35KV用户的电压允许偏差值应在系统额定电压的 90%110%; 10KV用户 的电压允许偏差值为系统额

43、定电压的+ _7% .其次在最小运行方式下(考虑70%的容量):(1 )从系统母线电压推算到盐北变主变压器高压侧电压 .(1)将35KV 10KV侧最大负荷距线路末端允许最低电压反推到变压器 高压侧电压.(2)参考电气工程专业毕业设计指南一电力系统分册 中的电压调整: 35KV用户的电压允许偏差值应在系统额定电压的 90%110%; 10KV用户的电 压允许偏差值为系统额定电压的+ _ 7%.最后比较6组数据,取最大、最小的数据确定分接头范围1系统大方式(1)从系统潮流推算到延长变110KV母线电压如图所示,U1 = 113KV为系统大方式下盐城电厂110KV母线电压.盐城电厂至110KV东郊

44、变线路长5KM、2X LGJ-300导线R12=0.105 X 5/2= 0.26X12=0.395 X 5/2= 0.99110KV东郊变至110KV延长变线路长30KM、2X LGJ-240导线R23=0.131 X 30/2= 1.965X23=0.401 X 30/2 = 6.02盐城电厂至 110KV 东郊变潮流 S= (51+51+98.7)+j(31.6+31.6+46.65)=200.7+ j109.85则盐城电厂至110KV东郊变线路压降:PR12+QX2200.7 X 0.26 + 109.85 X 0.99尿=1.42U 1112PX2 QR2200.7 X 0.99 1

45、09.85 X 0.26S Ui2= 1.51U 11122 2U2 = "( U1 U2)+( S Uh)/ 22=V( 112 1.42 )+( 1.51 )=110.6(KV)110KV东郊变至110KV盐北变潮流S= 98.7+j46.65则110KV东郊变至110KV盐北变线路压降:PR23+QX398.7 X 1.965 + 46.65 X 6.02 U23= 4.25U 2110.6PXs QR398.7 X 6.02 46.65 X 1.965S U23= 4.50U 2110.622Ug = ( Ch)+( S U23)/ 2 2=V( 110.6- 4.25)+(

46、 4.50)=106.4(KV)从35KV、10KV最大负荷距推算到盐北变110KV母线电压从35KV最大负荷距推算到盐北变110KV母线电压根据已知条件,35KV最大负荷距为35KV A线路,S = 25.5+j11.7,供电距 离10KM. 般应保证用户端电压不小于 35KV.线路长10KM、2X LGJ-185导线R23=0.17x 10/2= 0.85X23=0.38 X 10/2= 1.9PR23+QX325.5 X 0.85 + 11.7 X 1.9 U23= 1.25U 335PXs QR325.5 X 1.9 11.7 X 0.85S U23= 1.1U 335/ 22_U2

47、= "( U3+ U23) +( S' U23), 2 2=V( 35+1.25)+(1.1 )=36.3(KV)U1 = K X U2 = (110/35)X 36.3= 114.1(KV)从10KV最大负荷距推算到盐北变110KV母线电压根据已知条件,10KV最大负荷距为10KV B线路,S= 2.55+j1.17,供电距 离2.5KM. 一般应保证用户端电压不小于 10KV.线路长2.5KM、2X LGJ-70导线R23=0.45X 2.5/2= 0.56X23=0.368 X 2.5/2= 0.46PR23+QX32.55 X 0.56 + 1.17 X 0.46 U

48、23= 0.2U 310PX3 QR32.55 X 0.46 1.17 X 0.56S U23= 0.05U 310U2 = V( U3+ U23)+( S U23)/ 2 2=v( 10+0.2) +( 0.05)=10.2(KV)5= K X U2= (110/10)X 10.2= 112.2(KV)2、系统小方式(70%的总容量)(1) 从系统潮流推算到盐北变110KV母线电压如图所示,U1 = 113KV为系统小方式下盐城电厂110KV母线电压.盐城电厂至110KV东郊变线路长5KM、2X LGJ-300导线R12=0.105 X 5/2= 0.26X12=0.395 X 5/2= 0

49、.99110KV东郊变至110KV盐北变线路长30KM、2X LGJ-240导线R23=0.131 X 30/2= 1.965X23=0.401 X 30/2 = 6.02盐城电厂至110KV东郊变潮流70% S = (51+51+98.7)+j(31.6+31.6+46.65) X 70%=140.5+ j76.9则盐城电厂至110KV东郊变线路压降:PR12+QX2140.5 X 0.26 + 76.9 X 0.99 Ul2= 1U 1113PX2 QR2140.5 X 0.99 76.9 X 0.26S Ui2= 1.06U 1113, 2U2 = "( U1 U12) +(

50、S U12)/ 2 2=V( 113 1)+(1.06)=112(KV) 110KV 东郊变至 110KV 盐北变潮流 70%S= (98.7+j46.65)X 70%=69+j32.7则110KV东郊变至110KV盐北变线路压降:PR23+QX369 X 1.965 + 32.7 X 6.02 U23= 3U 2111.6PX3 QR369X 6.02 32.7 X 1.965S U23= 3.15U 2111.6U3 = V( U2A 123)+( S U23)/ 2=v( 112- 3)+( 3.15)=109(KV)从35KV、10KV最大负荷距70%容量推算到盐北变110KV母线电压

51、从35KV 70%的最大负荷距推算到盐北变110KV母线电压根据已知条件,35KV最大负荷距为35KV A线路,70%S= 17.85+j8.19, 供电距离10KM.线路长10KM、2X LGJ-185导线R23=0.17X 10/2= 0.85X23=0.38 X 10/2= 1.9PR23+QX317.85 X 0.85 + 8.19 X 1.9 U23= 0.88U 335P为3 QR317.85 X 1.9 8.19 X 0.85S' Ul23= 0.77U 335U2 = "( U3+ U23)+( S U232 2=V( 35+0.88)+(0.77 )=35.9(KV)U1 = K X U2 = (110/35)X 35.9= 113(KV)从10KV 70%最大负荷距推算到盐北变110KV母线电压根据已知条件,10KV最大负荷距为10KV B线路,S= 1.79+j0.82,供电距离 2.5KM.线路长2.5KM、2X LGJ-70导线R23=0.45X 2.5/2= 0.56X23=0.368 X 2.5/2= 0.46PR23+QX31.79 X 0.56 + 0.82 X 0.46 Ul23= 0.14U 310PX23- QR31.79 X 0.46 0.82 X 0.56S U23= 0.035U 310/ 22U2

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。