1、变电站负荷分析计算及主变的选择V P=SX COSQ=S x Si n S二P/ COSQ= Js? P2由题意有:35 kV市镇变1:V P=6000 kW COS =0.9 S=P/ COS =6000 / 0.9=6666.67 kVAQ=s2 - p2 =、6666.672 -60002 =2905.94 kvar市镇变 2:v P=7000 kW COS =0.92 S=P/ COS =7000 / 0.92=7608.70 kVAQ=S2 - P2 =. 7608.702 - 70002 =2981.99 kvar煤矿变:v P=4500x 2=9000 kW COS =0.85

2、S=P/ COS =9000 / 0.85=10588.24 kVAQ=S2 - P2 = 10588.242 - 90002 =5577.70 kvar化肥厂:v P=4300x 2=8600 kW COS =0.88 S=P/ COS =8600 / 0.88=9772.72 kVAQ=S2 - P2 二、9772.722 - 86002 =4641.79 kvar砖厂:v P=5000 kW COS =0.85 S=P/ COS =5000 / 0.85=5882.35 kVAQ=S2 - P2 = . 5882.35 50002 =3098.27 kvar10 kV镇区变: T P=1

3、000X 3=3000 kW COS =0.9 S=P/ COS =3000 / 0.9=3333.33 kVAQ=S2 - P2 =、3333.332 - 30002 =1452.97 kvar机械厂: T P=800X 2=1600 kW COS =0.89 S=P/ COS =1600 / 0.89=1797.75 kVAQ=S2 -P2 = .1797.752 -16002 =819.70 kvar纺织厂 1:t P=700 kW COS =0.89 S=P/ COS =700 /0.89=786.52 kVAQ=S2 - P2 = 786.522 - 7002 =358.63 kva

4、r纺织厂 2:t P=:800 x 2=1600 kW COS =0.88 S=P/ COS =1600 / 0.88=1818.18 kVAQ=S2 -P2 = 1818.182 -16002 =863.59 kvar农药厂: t P=600 kW COS =0.88 S=P/ COS =600 /0.88=681.82 kVAQ=S2 - P2 =. 681.822 - 6002 =323.85 kvar面粉厂: t P=700 kW COS =0.9 S=P/ COS =700 /0.9=777.78 kVAQ=S2 - P2 =、777.782 - 7002 =339.03 kvar耐

5、火材料厂:t P=800 x 2=1600 kW COS =0.9 S=P/ COS =1600 / 0.9=1777.78 kVAQ=.S2 - P2 = 1777.782 -16002 =774.92 kvar主变压器冷却方式选择油浸风冷此110 kV降压变电站总的有功功和总的无功功率为:P=6000+7000+9000+8600+5000+3000+1600+700+1600+600+700+1600二45400 kWQ=2905.94+2981.99+5577.70+4641.79+3098.72+1452.97+819.70+358.63+ 863.59+323.85+339.03+

6、774.92=24138.83 kvar查询得同时系数 有功功率取0.85 ;无功功率取0.8则 总的有功功率为 P=45400X 0.85=38590 kW总的无功功率为 Q=24138.83 X 0.8=19311.06 kvar所以 总的视载功率为 S= P2 Q2 = 385902 19311.062 =43152.12 kVA由电力工程电气设计手册 电气一次部分(以下简称设计70%-手册)变电所主变压器容量的确定(P214)可知,对一般性变电所, 当一台主变压器停运时,其余变压器容量应保证全部负荷的80%则110 kV降压变电站主变压器的容量应不小于43152.12 X 0.8=34

7、521.69 kVA由变压器容量型号可知主变压器容量的选择40000 kVA主变压器台数的选择2台(设计手册P214)主变压器相数的选择三相变压器(设计手册P216)主变压器绕组数量的选择三绕组变压器 (设计手册P216)主变压器调压方式的选择有载调压(设计手册P226)主变压器绕组连接方式YN,yn0,d11(设计手册 P216)综上, 110 kV 三绕组有载调压电力变压器型号选择( 电力工程 电气设备手册电气一次部分 P350)型号SFSZL7-40000/ 110额定容量( kVA) 40000额定电压(kV)高压110;中压38.5 ;低压10.5空载电流( %)1.3空载损耗( k

8、W) 60.2负载损耗( kW) 高-中/; 高-低210;中-低/阻抗电压( %)高-中 10.5; 高-低17.5;中-低6.5连接组标号 YN,yn0,d11质量( t ) 器身 52;上节油箱 5.25;油 26.796 ;运输 88,总质 量 96轨距 横向/纵向 2000X 2/1435外形尺寸(长X宽X高,mr) 8900X 4800X 63500参阅图号 2-1-222生产厂电气主接线设计参考了发电厂电气设备 、电力工程电气设计手册电气一次部分,对110 kV、35 kV、10 kV各电压等级选择合适的接线方式, 做出了两种变电站主接线方案。方案一:110 kV选择双母线带旁路

9、母线接线;35 kV、10 kV均 选择单母线分段接线方案二: 110 kV、 35 kV、 10 kV 均选择单母线分段接线 经分析,上述两种方案供电可靠性、灵敏性均满足要求,方案二 更经济、简单、运行简单、投资相对较少。故变电站电气主接线选择 方案二。负荷大小和重要性:一级负荷、二级负荷、三级负荷,按负荷要 求合理接线分布:(1)对于一级负荷必须有两个独立电源供电,且当任何一个 电源失去后,能保证对全部一级负荷不间断供电。(2)对于二级负荷一般要有两个独立电源供电,且当任何一 个电源失去后,能保证全部或大部分二级负荷的供电。(3)对于三级负荷一般只需一个电源供电。 一级负荷:煤矿变、化肥厂

10、、砖厂、耐火材料、机械厂 二级负荷:市镇变 1、市镇变 2、纺织厂 2、农药厂、镇区变三级负荷:纺织厂 1、面粉厂互感器的配置:参考发电厂电气设备 P40-P42电流互感器的配置:往往电流互感器与断路器紧邻布置;变压器中心点接地处配置电流互感器以监视零 序电流;与避雷器配套使用: 间隙处配电流互感器保护。电压互感器的配置:母线处:6-220kv电压等级的每组母线的三相上应装设电压互感器;线路:监视和检测线路断路器外侧有无电压, 装设一台单相电压互感器(出线为 110kv 及以上电压等级)。避雷器的配置:变压器中性点引出线上;母线保护;总进线空开前端(一般) ; 保护间隙多用于 3-10kv 配

11、电系统。地刀的配置:工作接地 : 变压器中性点接地处;保护接地:母线、设备外壳;防雷接地:防雷保护装置不可或缺的部分;防静电接地无功补偿装置及容量的确定由电力工程电气设计手册一电气一次部分P469-P472分析:选择并联电容补偿装置确定并联电容补偿装置安装的“最大容性无功量”的原则 (P476) 粗略计算如下:安装的最大容性无功量应约等于装置所在母线上的负荷按提高 功率因数所需补偿的最大容性无功量。负荷所需补偿的最大容性无功量计算式为:Qcf,m = Pfm( tantan 2Pfm(1 cos2 11- cosP fm Qcfo又 COSj=0.8COS 2取 0.96 (设计手册-P476

12、 表 9-7 ) -1- :1-1=0.458Hcos1 Vco 2查表9-8中,Q取0.46cfo二 Qcf,m = Pfm x 0.46=3859* 0.46=17751.4 kvar综上:负荷所需补偿的最大容性无功量为17751.4 kvar。由电力工程电气设备手册 P1002,选择出并联补偿成套装置技术,相关数据如下:(2组装置)型号:TBB310-10200/100额定电压(kv): 10总标称容量(kvar): 10200单台标称容量(kvar): 100接线方式:双Y外形尺寸宽X深乂高(LX BX H,mm: 9121X 1686X 3236分析:补偿后s/ = p/+Q/= p

13、 +Q=38590+j19311.06-2 X j10200 =38590-j1088.94=38605 kVA/cos =;/=38595=.9996 95符合要求短路计算要考虑短路点及短路类型,用标幺值进行计算。求每个短路点的短路电流周期分量的有效值、冲击电流、短路全 电流最大有效值。分析短路类型:单相短路接地、两相短路接地、三相短路接地 短路点选取:某电压等级下最大电流处,故分别选取110kv、35kv、10kv 母线上为短路点同时,查询选出合适的设备:发电机、变压器的型号,并记录相 关参数。选最大运行方式:4X 200MV发电机并列运行。由电力工程电气设备手册P10,发电机选择如下:型

14、号: QFQS-200-2视在功率( MVA): 235有功功率( MVA): 200额定电压( kV): 15750额定电流( A): 8625转速( r/min ): 3000功率因数: 0.85效率 (%): 98.63超瞬变电抗 X d/ (%):1 4.44220kV双绕组无励磁调压:4X 240MV/变压器,见电力工程电气设备手册 P204:型号: SFP7-240000/220额定容量( kVA): 240000额定电压(kV):高压 220 (242) 2X2.5%低压 15.75空载电流( %): 0.5空载损耗(kW: 185负载损耗(kW : 620阻抗电压(%: 142

15、X120MV变压器,由电力工程电气设备手册P270:型号:SFPSZ7-120000/220额定容量(kVA):高压/中压/低压:120000/120000/60000额定电压(kV):高压220 8X 1.5% 中压121 低压10.5空载电流(%: 0.7空载损耗(kW : 140负载损耗(kW:高-中440高-低143 中-低117阻抗电压(%:高-中13.5 高-低22.4 中-低7.4连接组标号:YN yn0, d11由题中给出的接线图画出等值电路图如下:351. I简化后的等值电路图如下Irr.22011035由查询记录的参数及接线图,计算各元件的电抗标幺值由已知条件:基准容量 S

16、B = Sj=1 MVA则 X:=Ssc2又 V Xc=L =Sc2(105Un)Sc2二 Sc=(1.05u n) Xc2二 Sc=(1.05 220) o.4=1322.5 MVA*二 Xc = 113005=0756对4 X 200MV发电机并联后总的电抗标幺值为:* 1Xg=;Xd(%)1000235=丄 0.1444 X41000 =0.1535235对4 X 240MVA发电机并联后:XtW喘 gW嚅 X 鬻=0.146对 80km 70km 2X30km线路:X* = x L1=0-4 80 10002 = 0.605L1Uav230X* =X I 2 乜=0.4 75 1000

17、2 =0.567XL2L Uav230* 1Xl3汕沽2曲3叫;。严537对2X 120MVA勺变压器并列运行时,由选择的型号及参数可知: UK1 - 13.5UK1 ; = 22.4UK2 ; = 7.41 1 3 冷(U UK1UK21(13.5 22.4 一7.4) =14.2511UK2 = 2(UK1N UK2; -Uk12)= ? (13.5 7.4 _ 22.4) - _0.7511UK-(UK1. UK2 厂 UK 匕(22.4 7.4 一13.5) =8.15X T23 1 2X 120MVA勺变压器并列运行时的电抗标幺值为:X T23 _21 U K2 Sb2而SN1-0.

18、75 1000二-0.03125114.25100021001201 Uk1 Sb2而SN= 0.593752 100 120X T23 J3U心 Sb而sN1 8.151000= 0.6792x x2 100 120对110kV变电站的的两台主变:已知参数:UK1/=10.5Uk1 = 17.5UK2_36.5. 1 1UK1 =2(Uk2 UK1; _Uk2;)= 2 (10.5 17.5 -6.5) =10.7511UK2 二 2(UK 律UK2, UK= 2(10.56.5 一 17.5) = -0.2511()(6.5 17.5 -10.5) =6.75UK32VU K1 -3UK2

19、-3UK1_2?两台主变并列运行的电抗标幺值为:X T45 41 .血 Sb2 100 Sn110.751000210040= 1.34375* 1Xt45 厂?Uk2 Sb100 Sn1-0.251000-210040-0.03125X T45 J3U K3 Sb而sN1 6.7510002 10040= 0.84375Y”t “”转换,并联支路合并后:如下图35-xumi:I丁 X* =x;+X】=0.756 + 0.605=1.361X厂 x; X; X;2 =0.1535 0.146 0.567 = 0.8665X 3 = X T23+ X ;23 / + X ;3 = 0.59375

20、- 0.03125 + 0.4537 0162 当f点短路时:1X1f1 X1+X3+XvX3X21.3611.01621.361 1.0162 =3.9730.8665同理:* * * *X2f1=X2 X3X1-0.86651.01620.8665 1.0162 =2.5301.361由“ Y”“”转换可知:当f点短路时,短路点对电源的电抗为:1* X 1f 1 X 2 flfl*7+ 7X1f1 X2f13.973 2.5301.54573.973 2.530二短路电流周期分量的有效值为:I pi-0.646956Xf1 1.5457有名值为:IB耐眾|P110000000.646956

21、 二 3.248 kA.3 115此时,冲击系数Kim =1.80,查电力系统P120;im短路冲击电流为:|m Kim I miI m1为短路电流周期分量幅值,| m12 | *P1 i*m1 = Kim %。I 匚=1.80 507.646956 =1.6466有名值为:iimIBirn1000000 1.6466 =8.267kA 3 115短路全电流最大有效值为:* * 2I im = I P12 (Km 1)L2= 0.6469561+2x(1.801) =0.9769有名值为:|im=|Bim10000000.9769 =4.905 kA.3 1151 当f 2点短路时:X 1f

22、X 1 (X 3 X T45 J*) X1 (X3 Xt45 二Xt45/)X 丁45_2丿X2十61 (1.0162 十4375 0.03125) 1.361 (1.01620囂75 -0.03125) 347* * * * * ( ) X 23_XT45J_Xt45 少入2彳2一入23 XT45J X T45 _2Xi巾8665 (1.0162 1.34375 -0.03125)8665 0162 “34375 一 0.03125)1.361当f 2点短路时,短路点对电源的电抗为:* X 1f 2 X 2f 2X1f2 X2f27.347 佝8 詔.8587.3474.678二短路电流周期

23、分量的有效值为:I P21=0.3499X巾2858有名值为:十 |*P2 二 Sb p 1000000 0.3499 =5.460 kA1 IB 1甌V 1 屁 37此时,冲击系数Kim.8O,查电力系统P120;短路冲击电流为:i*m2二Kim | m2为短路电流周期分量幅值,| m22 | ;2-说二心 2 G/.802 O.34 = .89565有名值为:1000000.3 370.890565= 13.897 kA短路全电流最大有效值为:* * 2|im=|P2 1 2 (Kim1)= 0.3499汇彳 + 2x(1 .801)2 =0.528349有名值为:Z|b “ 罟詈 252

24、8349 = 8.245 kA 当f3点短路时:3如右图:* * * *X13*(X 3X T45 -1X T45 -3)X, 1 ( X, 3 X.T45J乂45/)*X2= 1.361(1.0162 1.343750.84375)1.361 (1.01621.34375 0.84375)0.8665二 9.5967X?f3=X 2 (X 3 X T45 JT45X2(X3 XT45XT45;)Xi= 0.8665 (1.0162 1.343750.84375)0.8665 (1.01621.343750.84375)1.3616.1099当f点短路时,短路点对电源的电抗为:3XZ3X1f3

25、 X2f3X1f3 X2f39.5967 汉 6.10993 7339.59676.1099 -二短路电流周期分量的有效值为:Xf310.26793.733有名值为:|P33U avP310000000.2679 =14.7313 10.5kA此时,冲击系数KimT.80,查电力系统imP120;短路冲击电流为:i二Kim,|m3I m3为短路电流周期分量幅值, *I m3 - - 2 I P3心3 二 Kim、2 IJ1*802 匕2679 .68186有名值为:iim3B iim310000000.68186 =37.494 kA3 10.5短路全电流最大有效值为:* * 2I m - I

26、 P3 1 2(Kim)= 0.2679x+2*1 .801恭=0.404529有名值为:I m = I B I im =10000000.404529 = 22.244 kA3 10.5各级电压配电装置设计参考发电厂电气设备 P139 及 P153 页:110kV电压等级配电装置选择:SF6全封闭组合电器35kV及10kV电压等级配电装置选择屋内式:具体:35kV: (P139-P143)选择单层式屋内配电装置10Kv:( P139 P143 P144、P151)选择单层式屋内成套配电装置主要电气设备的选择及校验断路器的选择 : 形式:110kV选用SF6断路器;35kV选用户内高压真空断路

27、器; 10kV选用户内高压少油断路器。 按额定电压选择: 断路器的额定电压不小于装设断路器所在电 网的额定电压,一般在10kV及其以上装置中均选择两者相同。 按额定电流选择: 断路器的额定电流不小于装设断路器回路的 最大持续工作电流。 按额定开断电流选择: 额定电压下能保证开断的最大短路电流的有效值。 按使用环境(机械负荷)选择:断路器允许的负荷不大于断路器引线在正常运行和短路时所承受的最大电动力。 见发电厂 电气设备P123,表9.4。110kV电压等级断路器选择:查看电力工程电气设备手册P666,型号: LW6-110Isf6气体压力(MPa: 0.4额定电压( kV): 110最高工作电

28、压( kV): 126 额定电流( A): 3150额定开断电流( kA): 40*(* :为端子短路开断电流,只适用于无近区故障要 求处)近区故障开断电流( kA): 28.4 动稳定电流(峰值) (kA): 100 热稳定电流( 3s 有效值) ( kA): 40 额定关合电流(峰值) (kA): 100失步开断电流( kA): 10 空载线开断电流(实验室) (A): 500固有分闸时间(m : 30分闸时间(m9 : 90全开断时间(ms): i(m)。由上诉断路器型号及参数可知,jP=100kA而断路 器的最大短路冲击电流i(m)=8.267kA。所以,满足iP i(m)。选择的设备

29、符合要求。热稳定校验:断路器允许的最大短路热效应不小于短路热效应,即: I2 t -Qk。2 2 */ It t 二 403 二 48002Q3.248 31-6485 12“ zQk选择的设备符合要求。35kV电压等级断路器的选择,P656型号:ZN-35/ 63081250 16额定电压(kV): 35最高工作电压(kV): 40.5额定电流(A) : 6301250额定短路开断电流(kA): 16动稳定电流(峰值)20(旳:40额定关合电流(峰值)(kA):2040额定短路开断电流开断次数(次):122s热稳定电流(kA): 816一次自动重合闸无电流间隔时间(s): 0.5合作时间(不

30、大于)(s): 0.2固有分闸时间(不大于)(s ):0.06(0.08)操刀机构额定电压(V: 110/220操刀机构额定电流:合闸A):240/120(250/125)分闸(A) : 5/2.5机械寿命(次):5000校验动稳定校验:同理 v iP=20kA j(m)=13.897kA iP i(m)。选择的设备符合要求。热稳定校验:V |:=8役2=128 Qk 乞5.4602 2 = 59.6232 |7txQ 选择的设备符合要求ik10kV电压等级断路器的选择,P617型号:SN10-10IH SN10-10/3000-43.3额定电压(kV): 10额定电流(A) : 3000额定

31、开断电流(kA): 43.3额定断流容量(MVA: 750极限通过电流峰值(kA) :130热稳定电流有效值(kA): 43.3(4s)合闸时间(s): 0.2固有分闸时间(s): 0.6操作循环:分一180s合分一180s合分校验动稳定校验:同理 TjP=130kAi(m)=37.494kA iP im)。选择的设备符合要求。热稳定校验:J |t =43.32汉4 = 7499.56Qk 鬥4.7312 4 =868.009二|2aqk选择的设备符合要求高压隔离开关选择原则: 根据配电装置的特点,选择隔离开关的类型; 根据安装地点选择户内式或户外式; 隔离开关的额定电压应大于装设电路所在电网

32、的额定电压; 隔离开关的额定电流应大于装设电路的最大持续工作电流。110kV电压等级隔离开关的选择,P778型号:GW4-110DW额定电压(kV): 110额定电流(A): 2000动稳定电流峰值(kA): 100热稳定电流(kA) (4s) 31540主刀闸:CS17G、CJ2-G、CS4G、CJ5操刀机构型号:丄、门、接地刀闸:CS17G、CS14G校验动稳定校验:应满足条件:iCwic8.267kA idw00kA二ich乞idw,满足动稳定校验。热稳定校验:应满足条件:| 2汉t色Qk 2 2 It t 二 404 - 64002Q 3.248 42-198 |2 t _Qk选择的设

33、备符合要求35kV电压等级隔离开关的选择:型号:GW4-35DW额定电压(kV): 35额定电流(A) : 2000动稳定电流峰值(kA): 100热稳定电流(kA): (4S)315校验动稳定校验:应满足条件:jch打dwich 3.897kA idw OOkA二ich乞idw,满足动稳定校验。热稳定校验:应满足条件:| t a qk2 2 *.* It t 二 404 64002Qk 七461192464 I2 t _q选择的设备符合要求10kV电压等级隔离开关的选择:型号:GN10-10T/3000额定电压(kV): 10额定电流(A): 3000动稳定电流峰值(kA): 160热稳定电

34、流(kA):(5s) 75校验动稳定校验:应满足条件:ic/jdwich =37.4942 idw -160kA山打dw,满足动稳定校验热稳定校验:应满足条件:|2 t_QK2 2.t t = 755 = 28125Qk 鬥4.7312 5 -1085-0122-It tQK选择的设备符合要求互感器的选择电流互感器的选择 形式的选择:根据安装场所、使用条件,一般 6 20kV户内配电装置中的电流互感器多采用户内式瓷绝缘或树脂浇注绝缘 结构;6 20kV户内配电装置中额定电流大于 2000A的电流互 感器多采用母线式;35kV及其以上的电流互感器多采用油浸 式或油浸瓷箱式瓷绝缘结构。 按额定电压

35、选择:电流互感器的额定电压应不小于装设电流互 感器回路所在电网的额定电压; 按额定电流选择:电流互感器的一次额定电流不小于装设回路的最大持续工作电流。电流互感器的二次额定电流,可根据二 次负荷的要求分别选择 5A 1A或0.5A。 按准确度级选择:电流互感器的准确度级应符合其二次测量仪表的要求。110kV电压等级电流互感器的选择,P488型号:LB6-110额定电流比(A) : (2 X 500)(2 X 750)/5级次组合:凹BB/ B准确级次:0.510%&数:二次负荷(-)2 倍数(倍):151s热稳定倍数(倍):45动稳定倍数(倍):115 校验动稳定校验:电流互感器的内部动稳定能力

36、用动稳定倍数Rm表示,互感器内部动稳定条件为:(Km 2 12-)*。/汉 I 1N =115汇“疋 209.9 =34136.994(3)i im=8.267kA(3)(Km 2|1N)Tim热稳定校验:电流互感器的热稳定能力用热稳定倍数Kh表示,2热稳疋条件为:(KhlN1)Qk2 2v(Kh|N1)t=(45 209.9)仁 8921747.25J2Qk =3.248 仁10.5495 KJ2二(Kh I N1)Qk选择的设备满足要求35kV电压等级电流互感器的选择,P488型号:LB6-35额定电流比(A) : 52000/5准确级次:0.210%倍数:二次负荷() 1.2额定一次电流

37、(A : 400-20001s热稳定倍数(倍):40动稳定倍数(倍):102.0校验动稳定校验:T K/2江 I 1N =102.0乂 J2乂 659.8 = 95176.007i(m13.897kA二(Km 2 |倍)-需热稳定校验:T (k h J N1)St =(40 汇 659.8)2 =696537664 J2Qk=5.46 仁29.8116 KJ2- (Kh lN1)JQk选择的设备满足要求。10kV电压等级电流互感器的选择,P537型号:LDZ1-10额定电流比(A):400 1000/5600 1000/5级次组合:;0.5准确级次:130.5级0.41级二级负荷():0.60

38、.40.610%t 数:151s热稳定倍数(倍):50动稳定倍数(倍):90 校验动稳定校验:T Km江、汇 I 倍=90 汇722309.4 = 293938.6321(3)i im二 37.494kA( 2 )K mI 1N i im22热稳定校验:T (Kh|N1) (50 2309.4) 1.33 1010J2Qk =14.731 仁 217.002 KJ2.(Kh |N1)t-Q选择的设备满足要求电压互感器的选择发电厂电气设备 P132 型式的选择:场所、接线及用途; 按额定电压:为保证测量的准确性,电压互感器一次额定电压应在所安装电网额定电压的90%-110%间;S2 按容量和准确

39、度级选择:电压互感器二次最大一相的负荷不超过设计要求准确度级的额定二次负荷SN2110kV电压等级出线选择电容式电压互感器,P584额定电压(kV):初级绕组1次级绕组剩余电压绕组1/ ,30.1/. 30.1二级负荷(VA:1.0 级3.0级300600最大容量(VA:1200阻尼电阻功率(W: 400型号:TYD110/ 3 0.008旧型号:Y DR-110分压电容量c2(uF):0.08母线保护选择电磁型电压互感器:110kV母线上电压互感器的选择,P592型号:JDFB1-110A最大容量(VA): 2000初级绕组次级绕组剩余电压绕组1 八30.1/ .30.10.5级1级3级25

40、04001000额定电压(kV):二级负荷(VA :剩余电压绕组:输出(VA: 300准确级:3B避雷器的选择110kV电压等级(带有均压环)型号: FZ-1 1 0额定电压有效值( kV):110灭弧电压有效值( kV) : 1 26不小于 不大于工频放电电压有效值( kV) : 452 *312*25 *314*冲击放电电压峰值( 1.5/20us 及 1.5/40us )*不大于( kV):3758/20us 雷电冲击波残压峰值不大于( kV)5kA:375410*10kA : 41535kV电压等级型号: FZ-35额定电压有效值( kV):35灭弧电压有效值( kV):41不小于不大

41、于工频放电电压有效值( kV): 80985kA :13410kA :148冲击放电电压峰值( 1.5/20us 及 1.5/40us )*不大于( kV):1348/20us 雷电冲击波残压峰值 不大于( kV)10kV电压等级型号: FZ-1 0额定电压有效值(kV): 10灭弧电压有效值(kV): 12.7不小于不大于工频放电电压有效值(kV) :2631冲击放电电压峰值(1.5/20us及1.5/40us ) *不大于(kV): 458/20us雷电冲击波残压峰值不大于(kV)5kA:4510kA: 502母线的选择按经济电流密度选择母线截面按经济电流密度选择截面时应满足以下条件:Lw

42、(S2 j (mm )式中S2经济截面,2mm最大回路工作电流,A;J经济电流密度,A/mm2.参考电力工程电气设计手册 P336火力发电厂的最大负荷利用小时数T平均可取5000h,水力发电厂平均可取3200h,变电所应根据负荷性质确定。查T-J经济电流密度可知:因为 T取5000h,则J查得0.8 A/mm2。110kV侧:S2 =匕=2099 =262.375S2J 0.8mm235kV侧:7824.75 mm210kV侧:S_ _Lw2一 j2309.4 =2886.750.8mm110kV母线选择:P340导体尺寸hx b (mm mm:63 x 6.3导体截面S ( mm ):397

43、机械强度要求最大跨距机械共振允许最大跨距截面系数竖放: y(cm)0.417竖放平放cm):406 . a / j ch厂1285. a/j竖放平放cm):45143惯性半径chiy(cm)0.182截面系数平放:y(cm)4.17惯性半径riy(cm)1.82135kV母线选择:P340导体尺寸hx b (mnX mm: 125x 8导体截面S (mm):1000机械强度要求最大跨距/、 竖放cm) : 727需/jch平放2873 a/ich机械共振允许最大跨距(cm):竖放51平放201截面系数竖放: y(cm)1.333惯性半径riy(cm)0.231截面系数惯性半径平放:y(cm)iy(cm)20.833.61310kV

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论