1、LIGHTING SYSTEM 照明系统 1 LIGHTING SYSTEM 1.Lighting system prepare; 2.Lux calculation; 3.Lighting system arrangement drawing; 4.Lighting system single line diagram. LIGHTING SYSTEM 1. Lighting System Prepare Reference for design: - Construction specification; - General arrangement(GA)drawing; - Hazard

2、ous area division drawing; - Fire zone division drawing; - Escape route arrangement drawing; LIGHTING SYSTEM 2.Lux calculation; Present two of solutions - Calculation with formula ; - Calculation with vendor software。 LIGHTING SYSTEM - Calculation with formula NUfF=EAD N : Lighting fixture Qty U : U

3、tilization factor 利用系数 F : Lumen 流明 E : Lux(average intensity of illumination required) 勒克斯(平均照度) A : Room area 房间面积 D : Depreciation factor = 1/M(Maintenance factor) 折旧率=1/M(维护系数) LIGHTING SYSTEM U : Utilization factor 利用系数 Room Index = AxB / (A+B) x h),或 = S / (P/2) x h) A:Width; B:Depth; S:Area;

4、P:Perimeter; h: Room height - 0.85M(from floor) - Distance from lights to ceiling. Room Index Uf 0 - 1.490.35 1.5 - 1.990.40 2 - 2.490.45 2.5 and above0.50 LIGHTING SYSTEM F : Lumen 流明 Fluorescent 40w 3000 lm Incandescent 200w 2500 lm LIGHTING SYSTEM D : Depreciation factor (1/M) 折旧率 Fluorescent Acc

5、omm. the emergency lighting level shall as a minimum be 30% of the general lighting requirement. - The emergency lighting system shall be switched on automatically in the event of failure of the main source of electrical power. Distribution boards for emergency lighting shall be equipped for remote

6、alarming of tripped circuit to a manned area. - Escape lighting system supplied from the battery backup source of electrical power system. Distribution boards for escape lighting shall be equipped for remote alarming of tripped circuit in a manned location. - Hazardous areas as per IEC-61892-7 and t

7、he philosophy for isolation sources in case of emergencies shall be complied with. LIGHTING SYSTEM NORSOK - Normal lighting: Covering approximately 70% of the lighting requirements. The normal lighting shall be fed from the main distribution system. - For the general level of illuminance at 1 m of e

8、levation, the area requirements according to Annex table apply. - The illuminance levels shall comply with NORSOK standard S-002 (as below). - Emergency lighting: Covering approximately 30% of the platform lighting requirements. In normal operation the emergency stand by lighting shall form part of

9、the normal lighting system. The illuminance levels comply with the relevant parts of EN 1838. - Distribution boards for emergency lighting shall be equipped for common remote alarming of tripped circuit. - Emergency escape lighting: A part of the emergency luminaries, shall be supplied from a batter

10、y source, and sited according to EN 1838. Other emergency luminaries e.g. floodlights, shall be supplied from a UPS system. - Portable emergency lighting: The battery charger for battery operated hand lamps shall be fed from the emergency distribution system. - Local distribution boards shall be pro

11、vided for power distribution to the lighting system within each functional area. The distribution boards shall to the extent possible be located in non-hazardous dry areas. LIGHTING SYSTEM DescriptionIECDescriptionNORSOK Average llumi- nance E (lux) E min E (lux) E max E (lux) Average llumi- nance E

12、(lux) E min E (lux) E max E (lux) General Outdoor Area5020100External walkways and access ways100- General Indoor Areas, Corridor s, accommodation ect. 10040200 Corridor in LQs100- Corridor in work areas100- Lay down area200- Muster area200- Coffee bar in LQ, television room etc.150- Gymnasiummin: 3

13、00- Cabins150- Toilet / Changing roommin: 200- Coffee bar outside LQ150- Stairways15060300 Stairs, walkways and access ways in enclosed work area150- Process areas - Occasionally manned 15060300 Unmanned machinery room200- Battery room200- Stores - Large parts200- Stores - small parts300- Descriptio

14、nIECDescriptionNORSOK Average llumi- nance E (lux) E min E (lux) E max E (lux) Average llumi- nance E (lux) E min E (lux) E max E (lux) Process areas - frequently manned300150450 General process and utility area200- HVAC room200- Local instrument room400- Mud room, mixing area200- Mud room, test sta

15、tion300- Mud lab300- Monkey board200- Pipe rack area200- Mud / well logging500- Shale shaker300- Blowout preventer and well hea d150- Crane cabin400- Drillers cabinAdj: 400- Operator cabin in drilling unit400- Drill floor300150450Drill floor350- Control rooms - Laboratories500250750 Central control

16、roomAdj: 500- Local control room400- Laboratory500- Engine rooms - Pump rooms20080400 Main generator room200- Fire pump room200- Auxiliary engine rooms20080400Emergency generator room200- LIGHTING SYSTEM DescriptionIECDescriptionNORSOK Average llumi- nance E (lux) E min E (lux) E max E (lux) Average

17、 llum inance E (lux ) E min E (lux) E max E (lux) Workshops300120600 Inst/El. Workshop500- Mechanical workshop/ welding500- Workshop office500- Paint shop500- Sandblasting room300- Switchboard rooms300150450Switchboard and transformer room200- Offices500250750Office / Meeting roomAdj: 500- Laundry,

18、galley and mess area300120600 Laundry - machinery area300- Laundry - work area300- Galley500- Serving area400- Dining room300- Dish washingmin: 300- Hospital300120360 Hospital / wardmin: 500-Emergency hospital (if required)300120360 Hospital spotlight10005001500 Radio rooms500250750Radio room500- LI

19、GHTING SYSTEM LIGHTING SYSTEM Areas index Calculation (IEC) IEC-61892-2 The number of measuring points required for measuring in a given area is based on the area index and must be based on an even grid layout for the whole area. Area indexNumber of points Below 14 1 and up to 29 2 and up to 316 3 a

20、nd above25 The area index is given by the formula : K= (a*b)/h (a+b) Where K is the area index, a and b are the sides of the room/area and h is the height of the luminaries above the work plane. Any light measurement must be considered in addition to any background light at the place of measurement.

21、 Note: The initial illumination levels should allow for lamp deterioration and accumulation. LIGHTING SYSTEM NORSOK Illumination - For the general level of illuminance at 1 m of elevation, the area requirements according to Annex table apply. - The uniformity of the illminance shall be equal to, or

22、better than, Emin/Emean = 0.5 in process, utility and dril-ling areas. - The uniformity of the illuminance for individual work areas shall be equal to or better than Emin/Emean=0.7. - For lighting calculations, a maintenance factor reflecting the environment and time between maintenance intervals sh

23、all be established and applied. Maintenance factor 0.7 is recomme- nded. - Lighting shall be specified for each workplace that requires at least daily access or is critical from a safety point of view. The guidelines in EN 12464-1 shall be applied in the specification of task lighting. LIGHTING SYST

24、EM - The lighting shall, as a minimum, be included for workplaces that require daily access or detailed reading of information, critical from a safety point of view. This includes gauges, indicators, areas that need to be checked for leakage and areas that frequently need maintenance. - To avoid sha

25、dows, illumination planning shall take the location of fixtures, racks and m echanical equipment into consideration. - The difference in illumination level between adjacent areas should not exceed 5:1. - In enclosed work areas, the difference shall never be more than 40:1 within the total field of v

26、ision. - Provision shall make to avoid direct glare from sunshine, from artificial light sources and from reflecting surfaces. - Glare in visual display units from reflecting surfaces, lamps and windows shall be avoided. - In the design of the lighting, the level of illumination and location of lamp

27、s shall make it easy to see obstructions, steps in corridors, walkways etc. - Different levels of illuminance require different light colors if the lighting is to be comfortable. Warm color should be used in cabin and recreation areas where the lighting levels are below 500lux. High color temperatur

28、e, whiter light, should be used in areas with high light levels. - In areas monitored by closed circuit television, the illuminance shall be sufficient to produce quality video pictures. - The need for adjustable workstation lighting shall be provides as needed for fixed work places. LIGHTING SYSTEM

29、 Emergency Lighting System IEC-61892-2 Emergency lighting shall not be below the escape lighting level requirement as per table Below. The location of the lighting fixture shall be based on the need for light in the emergency operation situation. The emergency lighting system shall be switched on au

30、tomatically in the event of failure of the main source of electrical power. The emergency lighting system shall: ensure illumination for safe operation of emergency systems including manual operation area; illuminate all accommodation spaces, control center, work locations, escape routes; helicopter

31、 deck and other possible evacuation locations such as lifeboat stations; illuminate the sea where lifeboat and life rafts are to be launched; illuminate the identification system of the unit; illuminate all spaces where loss of lighting presents a danger to personal; illumination system for control

32、stations that shall be operative under emergency conditions. Hospitals and emergency hospitals, if any, shall be fully operational at all times. LIGHTING SYSTEM Escape lighting system IEC-61892-2 The escape lighting system shall, as a minimum, provide a lighting level to meet illumination level give

33、n in table below. The escape lighting system shall be switched on automatically in the event of failure of the main and emergency power supply. The location of escape light fixture shall be based on the need for light in the escape situation. The escape lighting systems shall: have a power supply wi

34、th minimum 30 minutes backup time supplied by batteries either integrated or centralized and have a supply from a emergency generator; NOTE the backup should take account of the way in which personal will muster and evacuate a unit, and how much an evacuation is to be taking out; for helicopter and

35、their mobilization time. illuminate all accommodation spaces, control center, work locations, escape routes; helicopter deck and other possible evacuation locations such as lifeboat station; illuminate the sea where lifeboat and life rafts are to be launched; illuminate all spaces where loss of ligh

36、ting presents a danger to personal; illuminate all locations where operation of safety equipment can be necessary to bring the in stallation of a safe stage. LIGHTING SYSTEM LIGHTING SYSTEM AREAAverage illuminance E (lux)E min General Outdoor Area routes51 General Indoor escape routes, Corridors, ac

37、commodation ect.51 Stairways escape routes51 Process areas - Occasionally manned51 Process areas - frequently manned101 Drill floor203 Control rooms250125 Engine rooms - Pump rooms101 Workshops101 Switchboard rooms102 Offices101 Laundry, galley and mess area51 Hospital300120 Hospital spotlight100050

38、0 Emergency hospital (if required)300120 Radio rooms250125 Loading stations - muster station203 Overside (sea level)152 Lifeboat - Liferaft station203 Sea level launching areas152 1 WAY 2 POLE 22 50/15 50/15 : 80 % LIGHTING SYSTEM LIGHTING SYSTEM 23 J/B in unit toilet D/B 2 WAY 2 POLE Typical Wiring

39、 Diagram 典型接线典型接线 船舱 灯具 三芯电缆 灯具 三芯电缆 双极开关 接线盒 三芯电缆 三芯电缆 三芯电缆 到其它的接线盒(另一房间接法类似) 到其它的房间(另一房间接法类似) 三芯电缆 典型开关控制接线图(带接线盒) 三芯电缆 交流电由照明分电箱提供 Typical Wiring Diagram 典型接线典型接线 交流电由照明分电箱提供 双联开关 双联开关 接线盒三芯电缆 到其它接线盒 灯1 灯2 灯3 灯4 船舱 三芯电缆 典型双联开关控制接线图(带接线盒) 1号门 2号门 到其它接线盒/灯具 灯具灯具 接线盒 交流电由照明分电箱提供 双联开关双联开关 三芯电缆 三芯电缆 T

40、ypical Wiring Diagram 典型接线典型接线 船 舱 A船 舱 B 卫 生 单 元 的 开 关 和 灯 具 由 卫 生 单 元 厂 家 安 装 卫 生 单 元 的 开 关 和 灯 具 由 卫 生 单 元 厂 家 安 装 卫 生 单 元 接 线 盒 卫 生 单 元 接 线 盒 三芯电缆 三芯电缆 接 线 盒 典 型 卫 生 单 元 详 细 接 线 图 (带 接 线 盒 ) 三 芯 电 缆 到 其 它 房 间 的 卫 生 单 元 接 线 盒 (另 一 房 间 接 法 类 似 ) 三 芯 电 缆 三 芯 电 缆 交 流 电 由 照 明 分 电 箱 提 供 NAVIGATION LIG

41、HT Navigation Lighting Definition: Masthead light - means a white light placed over the fore and aft centerline of the vessel showing an unbroken light over an arc of the horizon of 225 degrees and so fixed as to show the light from right ahead to 22.5 degrees abaft the beam on either side of the ve

42、ssel. Sidelights - means a green light on the starboard side and a red light on the port side each showing an unbroken light over an arc of the horizon of 112.5 degrees and so fixed as to show the light from right ahead to 22.5 degrees abaft the beam on its respective side. In a vessel of less than

43、20 meters in length the sidelights may be combined in one lantern carried on the fore and aft centerline of the vessel. Stern light - means a white light placed as nearly as practicable at the stern showing an unbroken light over an arc of the horizon of 135 degrees and so fixed as to show the light

44、 67.5 degrees from right aft on each side of the vessel. Towing light - means a yellow light having the same characteristics as the “stern light” defined in paragraph (c) of this Rule. All-round light - means a light showing an unbroken light over an arc of the horizon of 360 degrees. Flashing light

45、 - means a light flashing at regular intervals at a frequency of 120 flashes or more per minute. NAVIGATION LIGHT Visibility of Lights The lights prescribed in these Rules shall have an intensity as specified in Section 8 of Annex I to these Regulations so as to be visible at the following minimum r

46、anges: (a) In vessels of 50 meters or more in length: a masthead light, 6 miles; a sidelight, 3 miles; a sternlight, 3 miles; a towing light, 3 miles; a white, red, green or yellow all-round light, 3 miles. (b) In vessels of 12 meters or more in length but less than 50 meters in length: a masthead l

47、ight, 5 miles; except that where the length of the vessel is less than 20 meters, 3 miles; a sidelight, 2 miles; a sternlight, 2 miles; a towing light, 2 miles; a white, red, green or yellow all-round light, 2 miles. (c) In vessels of less than 12 meters in length: a masthead light, 2 miles; a sidel

48、ight, 1 mile; a sternlight, 2 miles; a towing light, 2 miles; a white, red, green or yellow all-round light, 2 miles. (d) In inconspicuous, partly submerged vessels or objects being towed: a white all-round light, 3 miles. NAVIGATION LIGHT 29 112.5 degree 112.5 degree 225 degree135 degree225 degree PORT : RED STBD : GREEN Power-driven vessel underway shall exhibit:Power-driven vessel underway shall exhibit: (i) a masthead light forward; (ii) a second masthead light abaft of and hig

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

最新文档

评论

0/150

提交评论