1、Pro SIL optionT u V Certified for use in SIL 2 & 3 applicationssrotorsControlsIQ Pro range including“ SIL ” SafetyFunction Con trol Module opti on is T u V certified for use in SIL 2 safety applicatio ns using a 1 out of 1 actuated valve configuration (1oo1). Safety functions are“ Stayput ” and

2、“ ESD'The SIL opti on can be in cluded with any new IQ or IQT range actuator or be retrofitted to existing actuators supplied since 2000.Where SIL 3 is required, IQ Pro -SIL may be used in a 1oo2 actuated valve con figurati on.T u V Approval Certificate:Z10 07 09 64590 001For 50 years Rotork hav

3、e held reliability as the dominant factor in both the desig n and man ufactur ing of electric actuators and accord in gly have gained in dustry recognition for reliable actuation.With the adve nt of sta ndards for determ ining process fun cti onal safety requirements, the reliability of equipment wi

4、thin Safety In strume nted System (SIS) to carry out the required safety fun cti on and meet the target Safety In tegrity Level (SIL) must be defined by design with auditable reliability data.Rotork have brought in here nt desig n rigor of the IQ Pro range together with the desig n requireme nts of

5、Stan dardsIEC61508 and IEC 61511 to provide the first “ SIL ” certified electric valve actuatorin depe nden tly certified by TuV.Pro"Publication E1121EIssue 10/07Established Leaders in Valve Actuatio n Tech no logySafety FunctionsThe two safety functions applicable to valve actuators are:Safety

6、 function 1 - Stayput (High Demand)The actuator shall not move without a valid remote open or close command signal. If an internal failure is detected the actuator will give an alarm signal.Dual hardwired control input signals are required for remote control. Signals must be maintained,“ push to run

7、 “ type onlySafety function 1 is available with IQ and IQT Pro ranges.Safety function 2 - ESD (Low Demand)If an ESD signal is active the actuator will perform the commissioned ESD action (open, close or stayput).If an internal failure is detected the actuator will give an alarm signal.ESD signal mus

8、t be derived from a contact breaking and must be maintained during ESD. Safety function 2 is available with IQ Pro range only.Combined Safety Functions 1 & 2- Stayput with ESDTo stayput as per safety function 1, else perform the commissioned ESD action as per safety function 2.ESD has priority.

9、Combined Safety function 1 & 2 is available with IQ Pro range only.Operati onThe SIL option monitors the standard IQ Pro control board and provides diagnostic coverage and redundant control in order to carry out its safety function if required. In addition, electro-mechanical and mechanical comp

10、onent reliability has been assessed & quantified, meeting reliability requirements of SIL2/3 applications.A safety function status relay provides indication of the actuator availability, redundant safety function operation and control signal status. Status is also duplicated locally on the actua

11、tor display.In order to meet the requirements of SIL2/SIL3 as certified by T, UQ Pro-SIL actuators must be installed,commissioned, operated and maintained/ proof tested in accordance with the safety manual publication E173E3.Available IQ Pro - SIL Actuator typesFor the types shown below there is no

12、restriction on actuator size or speed. Refer to Publication E110E for actuator sizes, speeds and torque performance details.Due to the strict design and implementation requirements necessary, IQ Pro - SIL option is limited to the actuator types and options ONLY displayed in the table below:TypeDutyP

13、ower supplyDuty rat ingStarts/HrBasic CircuitDiagramPlus 4-20mAIn dicati on*IQMulti-turn Isolating &? Turn isolating*3 phase onlyS2 - 25%603000S0003060S0001 n nIQT? turn Isolating1, 3 phase or 24V DCS2 - 20%606000S0006060S000nFIQTM? turn Modulating1, 3 phase or 24V DCS4 - 50%12007000S0007060S000

14、IQTFPart-turn Isolating1, 3 phase or 24V DCS2 - 20%606000S0006060S000Q/MJ. CM CQ-OCZLL ddOSZ)IQMulti-turn Isolating & ? Turn isolating*3 phase supply onlyS2 - 25%603000S0003060S000* requires addition of second stage gearbox* Where a 4-20mA position feedback signal is required, option Current Pos

15、ition Transmitter (CPT) is available. CPT Output signal is not part of the safety function. CPT is 24V DC (nominal) loop powered and will output 4mA on loss of actuator power supply irrespective of position.rotorsControlsIQ - SIL Reliability data for SIL 2 applicationsThe reliability data provided i

16、s applicable to the complete actuator up to and including the actuator output drive assembly. It does not include the valve, valve drive components or second stage gearboxes. The integrity/reliability of the electrical power supply and user derived control signals are not included in the actuator re

17、liability assessment.Safety Function 1: StayputIQIQTSubsystem TypeBBHFT Hardware fault tolerance00/sd Safe detected failure rate2603.7 x 10 -92599.29 x 10 -9治u Safe undetected failure rate9935.8 x 10 -99928.76 x 10-9/d Dangerous detected failure rate0.32 x 10-90.32 x 10-9/u Dangerous undetected fail

18、ure rate33.32 x 10-950.32 x 10-9PFH Probability of failure per hour33.64 x 10-950.64 x 10-9SIL Safety Integrity Level22SFF Safe failure Fraction99.799.6Safety Function 2: ESDIQCombined Subsystem TypesABHFT Hardware fault tolerance0 1SFF Safe failure Fraction (subsystems)85.02%99.8%/d Safe detected f

19、ailure rate1359.8 x 10-9/u Safe undetected failure rate8674.4 x 10-9?dd Dangerous detected failure rate609.13 x 10-9?du Dangerous undetected failure rate933.32 x 10-9PFDProbability of failure on demand (per annum)4.1 x 10 -3SIL Safety Integrity Level2MTTR Mean time to repair*12 HoursTI Proof Test in

20、terval*12 months* Approval for SIL 2 applications based on the stated periods. Users must ensure these intervals are not exceeded in service.Actuator select ion and siz ingThe selection of actuator type and size is dependent on the valve type (multi-turn or part-turn) and the required operating forc

21、es (torque and/or thrust). Actuator performance data is provided in publication E110E. An on-line actuator sizing guide is available at . Contact Rotork for further help or advice.The following conditions will be applied:? Rotork will size the actuator based on the supplied valve data. No additional

22、 safety factors will be added unless expressly requested.? The valve or valve drive components must be capable of safely withstanding the supplied actuator stall torque and/ or developed thrust at stall torque. For design purposes, stall torque must be considered to be at least 3 times supplied actu

23、ator/actuator-gearbox combination rated torque.? If the SIL option takes over the control in order to carry out an ESD to a predetermined end of travel (safety function 2), the actuator may stall against the valve or gearbox stops for a time up to the stroke time +3 seconds.Actuator PowerThe actuato

24、r electrical power supply integrity does not fall within the scope of the actuator reliability data. Users must ensure the integrity of the actuator power supply meets the requirements of the target SIL for the SIS.Actuator Con trolRefer to control connection drawing RWS320 below and Example IQ Circ

25、uit Diagram 3000S000.In order to meet the requirements of SIL 2 for safety function 1 the actuator must be controlled for opening and closing using 2 input signals.Application of only one signal is invalid and will raise an error status feed back on the display and status relay.For safety function 2

26、, a single, maintained ESD signal derived from a normally closed contact (break to ESD) is required. ESD operation will override any existing open or close (local or remote) signal while applied.Actuator In dicati onFault Status RelayThe SIL option includes a status relay contact providing remote in

27、dication that the system has detected an invalid or fault condition and has performed the safety function, or, the safety function cannot be applied or could be overridden. The actuator LCD display also provides fault status indication.Indication ContactsThe actuator has 4 configurable contacts, S1

28、to S4 available for indication including open and closed position limit indication and intermediate position indication (configurable).A full list of available functions is provided in publication E170E3.Monitor RelayThe monitor relay will indicate one or more of the following conditions:? Loss of o

29、ne or more of the power supply phases? Loss of control circuitry supply? Actuator selected for local control? Thermostat tripped? Local / Remote control pushbutton set to Local stop.The monitor relay is not configurable. Refer to actuator circuit diagram for connections.Analogue 4-20mA position indi

30、cationWhere the CPT option is fitted - refer to actuator circuit diagram, a 4-20mA loop powered signal is available for analogue position indication. The CPT must be powered from an external source with a nominal supply of 24V DC. On loss of main actuator power supply, the CPT output will default to

31、 4mA regardless of actuator position.Note:Indication outputs S1 to S4, Monitor Relay and the CPT an alogue positi on sig nal do not fall with in the scope of the actuator reliability assessme nt and therefore should not form part of the SIS.User must en sure the in tegrity of in dicati on meets the

32、requireme nts of the SIL target for the SIS. If n ecessary, limit position indication should be derived from devices exter nal to the actuator and drive n directly from the valve obdurator.ControlsProTypical Remote Con trol circuit diagram3I51SK-1OLINK FITTED BV ROTORSBREAK AT FULLY OPENSIL MODULEHA

33、tE AT FULLY SHUTHATE AT FULLY OPENHRfAK AT FULLY SHUTihDtCATICM CONTACTS S1-S4 *ft£ SHORN IN IHETR WFMJLT CCW(6lRArW, .COITACTS * BE CWFIGUREO Fg *Nr OF IX FUhCKOHS OESCFtieED IN EJ70EJCIRCUIT DRAWN WITH POWER SUPPLY OFFFDR rYPICAL RtrOTt DONTfeut DETAILS St DOCUMENT RWS32O利灯T蟲 WW.YM*Ji LO*O ON

34、 1EMINALS 4 t S 刖 REMOTE COKTROL SIGNAL THF£3K)LE V仇TAGE5饼 WJWUN1EED OPERATION*ON -/ OFF - 5MJNIHL SJGKAL- OOCnNOMINAL CJ1REMT Ofl刖M FROM EACH tONTftOL SlGtHL 1$ 5fl4LOCALrotorsFUSE FSli * 150mA AHT|«SUR% ALL 1RANSFQRICR TYPES * PSI SELF RESETTING FU5E.!*B M- M-' W M- » ViNOTEREFE

35、R TO PUELICATEOtJ Et?d£3 F«l AFPFlOTtO 1-UbEb FS1 AND FS2.TRMIg.TW SUITOHlMQ FQIt2<W)C CWTJ£Tt»S CIA3O-S. fWiJ吕 CH.V FITTED 1*0 II WK GMTAGIDR IS FITTEDFOW |04&r?&.!».91 t 36”込一 rfflAPPL忙恥|。殆ACTiJUTOR 15 IjjV CERTIFIED FEW L2/3 PLICATIMS OHL/ WHEN K5TALLED, COW555

36、1 »EC, OFtRATED I FUhTA:证口 Ih STRICT *CCOD«KE W:TM THE tQ Pft? WFET/ MAMMAL - Pl«LC*TION E173E3-S!5TnnniiJmW mjuyuiHoPATE01REVISJOW 咋”仇$TAPMOH 砂 601 丁5DHZ60WZ220/23017& 242196-25S380/00304-1©343-446Y415/20332-157374-«7Z440/803S2Y84398-SI7TAPN0M1 50/6CmESOHZSOHZW346/3BC.2

37、85-360321-419X申ot-油丄-I3Z-564¥5*0/340192-Sl£16-2021SS0/S7S45-BOS5054FUSE F$1 - 25K AHT-SURGTYPE 3TAPKOMI 50/60HZ50HZ60KZX66O/66O»S34-726COO-726Y680/一55C-759CLOSEJUOPEN厶COMMW -ME 24VDC1._ :叽口F*jCJ1QPfN C001T10N4L片rCLOSEXOHDITIOWLJ_COKHCIM -VE 24VDCi>Vr1www. rotOflt comROTCRK DQNTO0L5

38、 L W 飙TH. BAI 3J0OWLW©T*lfOia25-7lS2«RD TOK CDNiTRCL INCROCKSTNV 1462札 USAEstablished Leaders in Valve Actuati on Tech no logyEstablished Leaders in Valve Actuati on Tech no logyIQ/IQT Remote Con trol Circuitry forSIL2 applications - 24V DCTo meet the requirements of Tu V certificate for S

39、IL2/3applications the following 24V DC remote control connections must be made. The safety integrity assessment for the remote control circuits is the responsibility of others and does not form part of the actuator assessment.Before putting the actuator into service, it must be installed and commiss

40、ioned in accordance with IQ Pro SIL safety manual publication E173E3. Unless specified with order, the actuator is despatched with default settings as listed in publication E173E3.The infra red setting tool enables the configurable actuator settings to be made.Established Leaders in Valve Actuati on

41、 Tech no logyEstablished Leaders in Valve Actuati on Tech no logyCUSTOMFF CGf-.NFCTinN FOR REMOTE CONTROLEstablished Leaders in Valve Actuati on Tech no logySAFETY FUNCTION 1:STA¥PUTOPEN/CLOSE PUSH TO RUN CONTROL (LOCAL CONTROL REMAINS SELF MAINTAINED)Established Leaders in Valve Actuati on Tec

42、h no logyEstablished Leaders in Valve Actuati on Tech no logySAFE" FUNCTION®(t)®EMERGENCE SHUT-DOhl CIRCUITTHE E&D CIRCUIT CAN SE ADDED TOTWE CONTROL CIRCUIT SHOWN ABOVE.AN ESD SIGNAL APPLIED TO THE ACTUATOR WILL OVERRIDEANY EXISTING OPEN OH CLOSE CONTROL 3IGNALTHE OFAULT 6 5D CON

43、FIG RATI ON 眉 *STAY PUT", DERtVEPA hl/C COMTAjCT (StQKlALFOR OTHER CONFIGURABLE ESDSETTING OPTIONS REFER TO PUBL1CATIONE173E1E3D fivntdioerrwl Eu;pply cr gmrwl $【Normal 站 Ctosed j| Break Id ESD)Established Leaders in Valve Actuati on Tech no logyEstablished Leaders in Valve Actuati on Tech no l

44、ogyNote:Actuator remote control signals may be internally or externally supplied at 24V DC (nominal). A valid open or close remote control command consists of a control input signal and conditional input signals being applied simultaneously for the required direction of operation. Invalid signals wi

45、ll not cause operation and will invoke an“ ERR' alarm on thstatus relay (make contact). For full status alarm conditions refer to E173E3.Conditional control input signals are not required for local control. ESD can be user configured for Stayput, Close or Open. ESD signal must be derived from a

46、Stayput, normally closed contact breaking.In ter nally supplied:Fit link “ # ” as shown and connect remote control contacts to internal supply on terminal 5.Exter nally supplied:Connect control contacts to external supply 24V DC +VE.Connect supply 24V DC -VE to terminal 36 & 31.NoteIQT Range actuators - Wiring Diagrams 6000S000/6060S000 and 7000S000/7060S000 are not certified for use in SIL2/3 applications requiring safety function 2:ESD.Established Leaders in Valve Actuati on Tech

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

最新文档

评论

0/150

提交评论