/采暖通风和空气调节方案设计说明HVACConceptDesign1、设计依据:DesignBasis1.1相关设计规范RelatedDesignCode(1)《采暖通风与空气调节设计规范》(GB50019-2003)“DesignCodeforHVACDesign”(GB50019-2003)(2)《洁净厂房设计规范》(GB50073-2001)“CodeforDesignofCleanroomplant”(GB50073-2001)(3)《建筑设计防火规范》(GB50016-2006)“CodeforDesignofBuildingFireProtection”(GB50016-2006)(4)《建筑防排烟技术规程》(DGJ-88-2006-J10035-2006)上海市规范“TechnicalSpecificationforBuildingSmokeControl”(DGJ-88-2006-J10035-2006)Localcode1.2甲方提供的工艺资料(FPGspaceFacilityMatrix_Mar30'09);ProcessdataprovidedbyPartyA1.3建筑专业提供的平、立和剖面图。Layout,elevation,sectiondrawingsprovidedbyarchitecture.2、设计范围:DesignScope一层厂房内洁净通风及空调系统;二层厂房内的办公区和实验空调通风和IT机房的恒温恒湿空调系统;以及一、二层的消防排烟系统。Cleanventilationandairconditioningsystemingroundfloor;Airconditioningandventilationinfirstfloorofofficeareaandlab,constanttemperatureandhumidityairconditioningsysteminITroom.Fire-fightingsmokeexhaustsystemingroundfloorandfirstfloor.3、采暖、空气调节的设计参数:DesignParameterforHVACDesign3.1室外空气计算参数OutdoorAirCalculationParameter夏季:Summer空调计算干球温度:34Dry-bulbtemperatureforairconditioncalculation34空调计算湿球温度:28.2Wet-bulbtemperatureforairconditioncalculation28.2通风计算干球温度:32Dry-bulbtemperatureforventilationcalculation32℃平均风速:3.2m/s;Averagewindspeed3.2m/s;大气压力:1005.30PaAtmosphericpressure1005.30Pa冬季:Winter空调计算干球温度:-4Dry-bulbtemperatureforairconditioncalculation-4空调计算相对湿度:75%Relativehumidityforairconditioncalculation75%通风计算干球温度:3Dry-bulbtemperatureforventilationcalculation3平均风速:3.1m/s;Averagewindspeed3.1m/s;大气压力:1025.1PaAtmosphericpressure1025.1Pa3.2室内设计参数IndoorDesignParameter序号房间名称温度℃湿度(%)新风量标准
m3/h.人洁净度房间正压值Pa噪声
dB(A)夏季冬季夏季冬季1办公区(含会议、餐厅等)262265≥4020--2≤452SV+Integrgrationlab25±325±340~5040~5030--5≤553IT/DATA24±124±150±550±530--5≤554Testfloor25±325±340~5040~5030--10≤555Mechincallab25±325±340~5040~5030--5≤556FAlab25±325±340~5040~5030--5≤557Stresslab/reserved25±325±340~5040~5030--5≤558Chemicallab25±325±340~5040~5030--5≤559前室/库房25±325±340~5040~5030--5≤55NoNameTemperature℃Humidity(%)Makeupairstandard
m3/h.personCleardegreePositivepressurevalueofroomPaNoise
dB(A)SummerWinterSummerWinter1Officearea(includingmeetingroom,canteenetc)262265≥4020--2≤452SV+Integrationlab25±325±345~6045~6030--5≤553IT/DATA24±124±150±550±530--5≤554Testfloor25±325±340~5040~5030100k(8ISO)10≤555Mechanicallab25±325±340~5040~5030--5≤556FAlab25±325±340~5040~5030--5≤557Stresslab/reserved25±325±340~5040~5030--5≤558Chemicallab25±325±340~5040~5030--5≤559Frontroom/Storage25±325±340~5040~5030--5≤554、空调系统可靠性设计:Thereliabilityofairconditioningsystermdesign.4.1.以业主所提出的空调系统可靠性设计要求为依据,对于各个系统做出如下设置;Tosetupsomethingasbelowasproprietor′sdemandaboutthereliabilityofairconditioningsysterm.4.2.办公区各个系统交叉设置,但设备容量仍按设计负荷设置;Althoughthesystermintersectedbetweendifferentoffice,thecapacityoftheequipentisalwaysasthecalculation.4.3.SV+Integrationlab的设备容量按设计负荷的150%设置;Thecapacityoftheequipent(SV+Integrationlab)istobesetupasthe150%asthecalculation.4.4.1F空调系统的设计容量按设计负荷的125%设置。Thecapacityofthefirstfloorequipentistobesetupasthe125%asthecalculation.3、空调系统设计说明:Airconditioningsystemdesign3.1.办公区设计采用直接蒸发式多联机加板翅式全热交换式换气机,确保新风换气;Usemulti-splitairconditionerofdirectevaporationtypeplusairtoairexchangersofplate-fintoensurethemakeupairexchangeinofficearea.3.2.IT/DATA设计采用独立的风冷型恒温恒湿机组,该机组为双冷源设置;备用冷源由一台水冷型螺杆式冷水机组提供。加湿器供水管接市供上水管。UseindependentwindcoolingconstanttemperatureandhumidityunitsforIT/DATAdesign,whichisbelongtodoublecoldsource.Thereservationcoldsourceisprovidedbyonesetofwaterchillingunitofwatercoolingscrewbolttype.Thepipeofhumidifiershouldconnectwiththecitysentpipe.3.3.IT/DATA业主将提供另一套高热密度的设计方案,如采用该方案将由我方配合相关供应商完成施工图设计。Proprietorshouldprovideanotherplanofhighheatdensity,ifitwastaken,wewouldcooperatewiththesupplier,tofinishthedrawing.3.4.Integrationlab设计采用直接蒸发吊顶式空调机组多台,接风管上送上回风;加湿器供水管接市供上水管。Useseveralsetsofdirectevaporationceilingairconditioningunits,connectthewindpipetosendupperreturnair.Thepipeofhumidifiershouldconnectwiththecitysentpipe.3.5.Testfloor及一层各间设计采用直接蒸发式洁净空调机组,机组内设有初、中效过滤;并在整个空调区域进行气压控制,即气流由testfloor区流向其他各房间。空调箱中的初、中效过滤器设计分别采用MERV8和MERV13(ASHRAE);送风机采用变频控制。Usedirectevaporationcleanairconditioningunitsfirtestfloorandroomsofgroundfloor,insideofwhichinstallpreliminary,middlefilter.Controltheairpressureinwholeairconditioningarea,whichisthatairflowtootherroomsfromtestfloor.TheprimaryandmiddlerankairfilterofmodularairhandingunitaretouseMERV8andMERV13(ASHRAE);Supplyfanistousefrequencyconversioncontrol.3.5.空调系统风量负荷表:Airconditioningvolumeloadtable:序号房间名称空调冷负荷(KW)空调热负荷(KW)送风量(M3/h)新风量(M3/h)排风量(M3/h)面积(M)21office(meeting、restaurant.et.)(2F)198.9159370804000--12372SV+Integrgrationlab(2F)13633.6290001697--242.483IT/DATA(2F)1181676000850--117.754Testfloor(1F)349947200096201706755Mechincallab(1F)23546192956272033.756FAlab(1F)7923145481166--166.57Stresslab/reserved(1F)163183271331872310125.258Chemicallab(1F)24561206120612033.75NoNameCoolingloadofaircondition(KW)Heatloadofaircondition(KW)Airsupply(M3)/h)Makeup(M3/h)Airexhaust(M3/h)Area(M)21office(meeting、restaurant.et.)(2F)198.9159370804000--12372SV+Integrgrationlab(2F)13633.6290001697--242.483IT/DATA(2F)1181676000850--117.754Testfloor(1F)349947200096201706755Mechincallab(1F)23546192956272033.756FAlab(1F)7923145481166--166.57Stresslab/reserved(1F)163183271331872310125.258Chemicallab(1F)24561206120612033.754.通风及消防排烟的设计:Ventilationandfire-fightingsmokeexhaustdesign4.1.以当地消防规范为依据,一、二层各无窗房间,凡面积大于300(M)2的均需设置机械式火灾排烟系统。本工程二层office和一层testfloor需设置机械排烟系统,排烟风量为,60M3/H.M2Accordingtolocalfire-fightingcodes,roomswithnowindowsandarealargerthan300m2ingroundfloorandfirstfloor,shallinstallsmokeexhaustsystemofmechanicaltype.Installmechanicalsmokeexhaustsysteminofficeareaoffirstfloorandtestfloorofgroundfloorwithsmokeexhaustvolumeof6排烟风量如下:smokeexhaustvolumeasfollow:(1)testfloor:40000m3/h;(2)office:60000m3/h。上述排烟系统的补风风量均为排烟风量的50%。Complementairvolumeofabovesmokeexhaustsystemis50%ofsmokeexhaustvolume.4.2.各房间内工艺设备及实验通风柜均设置独立的排风系统,风机设在屋面;Installindependentairexhaustsystemforprocessequipmentandlabventilationcabinetofrooms,andfanontheroof.4.3.特种气体存放室内设置防爆型机械通风系统,设置平时通风及事故通风二种工况,通风量(平时/事故):8/15次换气/小时。Installexplosion-proofmechanicalventilationsystemforspecialgasroom.Installtwoworkingconditionsofnormalventilationandemergencyventilation.Ventilationvolume(normal/emergency):8/15times/hour5.备用冷源及工艺设备低温冷却水冷源系统:Reservedcoldsourceandprocessequipmentlowtemperaturecoolingwatersystem5.1.IT/DATA室的恒温恒湿空调系统的备用冷负荷为236KW(67tons);工艺设备低温冷却水设计冷荷为316KW(90tons)。设计选用94tons水冷螺杆式冷水机组,1台,作为冷源。上述二者共用此冷源的冷水。ThereservedcoldloadforconstanttemperatureandhumidityairconditioningsysteminIT/Dataroomis236KW(67tons).Thelowtemperaturecoolingwaterdesignedcoldloadforprocessequipmentis316KW(90tons).Useonesetof94tonsscrewboltwatercoolingunit,asthecoldsource.Thetwoequipmentsabovewillsharethecoldsource.5.2.该冷源供回水温为7/12℃,工艺设备低温冷却水系统以此为板式热交换器的一次回路,二次回路详见给排水专业设计。Watersupplyandreturnofthiscoldsourceis7/12℃,lowtemperaturecoolingwatersysteminprocessequipmentistheprimarycircuitofplatetypeheatexchanger,andsecondarycircuitrefertoplumbingdisciplinedesign.Therearetwocoldpumpsandtwocoolpumps,oneisbeused,theotheroneisreadyforuse6.设备表详见图纸equipmenttablerefertodrawings动力方案设计说明UtilityConceptdesign1、设计依据:DesignBasis1.1相关设计规范RelatedDesignCodes:(1)《空压站房设计规范》(GB50019-2003);“Codefordesignofcompressedairstation”(GB50019-2003)(2)《洁净厂房设计规范》(GB50073-2001)“Codefordesignofcleanroomplant”(GB50073-2001)(3)《建筑设计防火规范》(GB50016-2006)“Codefordesignofbuildingfireprotection”(GB50016-2006)(4)《建筑防排烟技术规程》(DGJ-88-2006-J10035-2006)上海市规范“Technicalspecificationforbuildingsmokecontrol”(DGJ-88-2006-J10035-2006)localcodes1.2甲方提供的工艺资料(FPGspaceFacilityMatrix_Mar30'09);ProcessdataprovidedbyPartyA1.3建筑专业提供的平、立和剖面图。Layout,elevation,sectiondrawingsprovidedbyarchitecturediscipline2。设计范围:DesignScope工艺所需的压缩空气、真空管道系统及特种气体站房及管道系统。Processrequiredcompressedair,vacuumpipelinesystemandspecialgasstationandpipelinesystem3.设计说明:Designexplanation3.1.压缩空气需求量约:581.9cfm(16.5m3/min),设计采用INGERSOLLRAND的S110型无油润滑螺杆式空压机,排气压力:1.0MPa,各种工艺设备不同的压力需求采用末端减压装置,同时设置干燥净化装置一套;上述设备均设1用1备。Compressedairvolumeisabout:581.9cfm(16.5m3/min),useS110oil-freelubricationscrewboltcompressedairmachinewithexhaustpressureof1.0MPa.Useendpressurereduceequipmentfordifferentpressurerequirementsofkindsofprocessequipment,andinstallonesetofdrycleaningequipment.3.2.该压缩空气系统还作为消防喷淋系统的备用气源。Thiscompressedairsystemisalsousedasreservedgassourceofhydrantsystem.3.3.真空系统需求量约:46cfm(1.3m3/min)设计采用一台片式真空泵,与管道系统连接;设1用1备。Vacuumsystemvolume:useonesetofplatetypevacuumpumpof46cfm(1.3m3/min),toconnectwithpipelinesystem.3.4.各种特种气体采用瓶装放置在独立站房。Eachspecialgaswillbeinstalledatindependentroomsinbottles.3.5.氮气采用室外管道接入车间内。Nitrogenisfromoutsidepipetohegarage.4.主要设备表:Mainequipmenttable序号设备编号设备名称及型号性能单位数量1AP/1F-01S110型风冷无油螺杆空气压缩机流量:18m3/min(581.9cfm),排气压力:0.85MPa,功率:110KW台22IR/1F-01IR170ED型微热再生式干燥机处理气量:17Nm3/min,耗电量:7.7KW台23T/1F-01不锈钢储气罐有效容积:10(M)3台14VP/1F-01旋片式真空泵抽气量:1.3m3/h(46cfm)台2NoEquipmentnumberNameandtypePerformanceUnitNumber1AP/1F-01S110windcoolingoil-freescrewboltcompressedairmachineFlowvolume:18m3/min(581.9cfm),airexhaustpressure:0.85MPa,power:110KWSet22IR/1F-01IR170EDmildfeverRegenerativedryerGastreatmentvolume:17Nm3/min,powerconsumption:7.7KWSet23T/1F-01StainlesssteelgastankEfficiencyvolume:10(M)3set14VP/1F-01SlidingvanerotaryvacuumpumpBleedairflow:1.3m3/h(46cfm)Set2暖通设计说明题纲:空调系统设计:本工程空调系统设计采用的是分散的直接蒸发式的冷热源系统(没有采用英特尔工厂的集中式冷热源系统)。以下将做详细比较论证。2F办公区/会议/餐厅区/空调系统:1.2.1.室内设计参数;1.2.2.空调系统的形式:直接蒸发多联式空调系统加板翅式全热交换式换气机,确保新风换气;1.2.3.
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 2025年中职(畜牧兽医)饲料营养阶段测试试题及答案
- 2025年高职蒙医学(蒙药应用)试题及答案
- 2025年高职纸制品设计(设计实操)试题及答案
- 2025年高职第二学年(环境艺术设计)AI辅助设计阶段测试试题及答案
- 2025年大学第四学年(生物学)分子生物学综合测试试题及答案
- 2025年高职第一学年(市场营销)营销策划阶段测试试题及答案
- 2025年高职水产养殖管理应用管理(管理技术)试题及答案
- 2025年大学大二(广播电视编导)电视节目编导综合测试卷
- 2025年大学(房地产开发与管理)房地产估价案例分析阶段测试题及解析
- 2026年阿坝职业学院单招综合素质笔试参考题库带答案解析
- 肿瘤化疗导致的中性粒细胞减少诊治中国专家共识解读
- 2025年查对制度考核考试题库(答案+解析)
- 云南省2025年普通高中学业水平合格性考试历史试题
- 四川省2025年高职单招职业技能综合测试(中职类)汽车类试卷(含答案解析)
- 消化系统肿瘤多学科协作(MDT)诊疗方案
- 安泰科技招聘笔试题库2025
- 二级生物安全培训课件
- 2025广东省横琴粤澳开发投资有限公司第二批社会招聘21人笔试历年典型考点题库附带答案详解试卷2套
- 塔吊拆除安全操作培训
- 2025年及未来5年中国抓娃娃机行业市场全景监测及投资前景展望报告
- 电机与拖动基础期末试卷及答案
评论
0/150
提交评论