版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
欢迎大家!内容(Contents)系统总体设计(Overalldesignconcept)6,5%机房工程系统的设计和实施是本着“以人为本、统一规划、分步实施的原则”。该项目机房系统应体现:先进性、安全性、实用性、稳定性、开放性和超前性。机房系统通过系统集成技术把机房各子系统有机的结合起来,实现信息共享和各种联动控制功能
TheServerroomengineeringanddesignfollowingtheprinciplesof"people-oriented,theunifiedplanning,step-by-stepimplementation".Theprojectsystemshouldreflect:advancedsafety,practicality,stability,openandmarketleadship.Computersystemintegrateseachsubsystem,realizingthesharingofinformationandvariouslinkagecontrolfunction.系统总体设计(Overalldesignconcept)6,5%总体设计要求
Generaldesignrequirements节能、环保抗变形设计抗震设计防尘防水抗干扰防火设计保温、隔热、隔音消声与减振措施电磁屏蔽Energysaving,environmentalprotectionAntideformationdesignSeismicdesignDustproofWaterproofAnti-interferenceFireprotectiondesignThermalinsulation,heatinsulation,soundinsulationNoisereductionandvibrationreductionmeasuresElectromagneticshielding系统总体设计(Overalldesignconcept)6,5%工艺设计中的节能环保的要求1、电气照明采用高效三基色荧光灯具,发光效率高,发热量小;房间内灯具分区控制,多回路设计,可减小不必要的能源浪费;用电设备均匀的接在三相电网上,降低三相电压不平衡度,减少能源的损耗。2、装饰装饰材料均为绿色环保材料;空调区地板下做保温处理;机房外窗封堵(无外窗设计)。3、空调空调采用环保型制冷剂;新风系统采用温、湿度预处理的新风机组新风系统安装消声器,减少风管产生的噪音系统总体设计(Overalldesignconcept)6,5%Processdesignofenergysavingandenvironmentalprotectionrequirements1、Electrical
Lightingwithhighfluorescentlamps,highluminousefficiency,smallcalorificcapacity;Theroomlightingsubareacontrol,multiplecircuitdesign,canreducetheunnecessarywasteofenergy;Electricequipmentgroundinginuniformthreephasenetwork,reducethethree-phasevoltageunbalancedegree,reducetheenergyloss.2、Decoration
Decorativematerialsaregreenenvironmentalprotectionmaterial;Airconditioningareaunderthefloorheatinsulationtreatment;withoutwindow(sealingwindowdesign).3、Airconditioner
Airconditionerusingenvironmentallyfriendlyrefrigerants;Airsystemusingtemperature,humiditypretreatmentunitsAirsysteminstallationmuffler,reducethenoisegeneratedbythewindpipe系统总体设计(Overalldesignconcept)6,5%工艺设计中的抗干扰措施防静电地板下设置等电位铜排网络,并与等电位箱的引出接地点相连接。机房等电位网格与结构钢筋连接;机房动力设备地线PE、设备外壳、金属管、槽外壳;墙、顶龙骨,地板支架、金属墙体等均与等电位铜排网络可靠相连,机房内形成法拉第笼接地网;为防止混凝土内预埋的电力配电线产生的电磁干扰,在墙内埋设的各种电气配线穿金属厚壁管,金属管接头采用螺丝接头连接;机房内UPS末端布线采用阻燃电磁屏蔽线缆,并穿金属管;放射式配线,而不作环形配线;系统总体设计(Overalldesignconcept)6,5%ProcessdesignofantiinterferencemeasuressetequipotentialcoppernetworkunderAntistaticfloor,andconnectedtoequipotentialboxoutlet.Roomandotherpotentialgridconnecttostructurereinforcement;ITroompowerequipmentgroundPE,equipmentshell,metalpipe,tankshell;wall,atopkeel,floorstand,metalwallconnectedtoequipotentialcoppernetwork,formaFaradaycagegroundinggrid;Inordertopreventelectromagneticinterferencegeneratedbythepowerdistributionlineinthewalls,electricalwiringtubeusehighthicknesspipe,metalpipejointwithscrewconnection;RoomUPSterminalwiringwithflameretardantandelectromagneticshieldingcable,andametaltube;Radiationtypewiring,notcircularwiring;系统总体设计(Overalldesignconcept)6,5%工艺设计中的抗干扰措施设置联合接地系统:变压器中性点工作接地、UPS输出端中性点工作接地、电气设备保护接地、等电位接地、电梯控制系统的直流接地、弱电系统直流接地及其它电子设备的直流接地共用大楼接地体;灯具选用节能型电感镇流器加补偿电容的方式,不对机房产生电磁干扰,灯具自身的谐波分量小于10%。系统总体设计(Overalldesignconcept)6,5%ProcessdesignofantiinterferencemeasuresSettingcombinedearthingsystemfortransformerneutralpointgrounding,UPSoutputneutralpointgrounding,electricequipmentprotectiongrounding,equipotentialearthing,theelevatorcontrolsystemofDCgrounding,elvDCgroundingandotherelectronicequipmentDCgroundingusebuildinggroundingbody;Lampsenergy-savinginductanceballastsandcompensationcapacitor,noroomelectromagneticinterference,lightingtheharmoniccomponentislessthan10%.系统总体设计(Overalldesignconcept)6,5%工艺设计中的抗变形设计、抗震设计1、抗变形设计一是材料材质:装饰材料(吊顶材料、墙面材料、地面材料等)、其他材料(管槽、吊架、风管等)具有一定的机械强度,地板的机械性能应符合《防静电活动地板通用规范》中的规定;二是整体结构系统的抗变形设计:吊顶结构中的吊件、龙骨设计,墙面结构中的龙骨设计,地板结构中的地板支架,隔墙结构中的龙骨设计,风管结构中的吊架设计,各种管线(强电、弱电、冷媒等)敷设中的固定结构等,在这些结构设计中,要充分考虑结构的抗变形能力。2、抗震设计建筑结构本身的抗震设计;3、其他根据机房设备情况,对楼板荷载进行负荷计算;机房内所有设备均采用支架式安装。系统总体设计(Overalldesignconcept)6,5%Processdesignofantideformationdesign,seismicdesign1、Antideformationdesign
Material:decorativematerials(ceilingmaterials,wallmaterials,surfacematerials,othermaterials(pipe)groove,hanger,windpipe)hasacertainmechanicalstrength,thefloormechanicalperformanceshallbeinaccordancewith"theactivitiesofanti-staticfloorgeneralspecification";Overallstructureofsystemantideformationdesign:ceilingstructureofhangingpieces,keeldesign,wallstructureinthekeeldesign,structureofthefloorbracket,wallstructureinthekeeldesign,windpipeinthestructureofthehangerdesign,allkindsofpipelines(power,Elv,refrigerant)installationfixedstructures,designtofullyconsiderthestructuredeformationresistance.2、SeismicdesignBuildingstructureseismicdesign;3、OtherAccordingtotheequipment,calculationthefloorloadallequipmentareallusingastentmounted.系统总体设计(Overalldesignconcept)6,5%工艺设计中的防尘、防水、防火等设计1、防尘设计机房密封处理:门、窗、结构墙体孔洞等的处理;2、防水设计各专业设计上放置水患的产生(消防、取暖等);注意防水、排水设计;在可能产生水的地方采用漏水报警系统。3、防火设计装饰材料防火等级(吊顶、地板、墙面、隔断、电缆等材料);电力电缆管槽内敷设、不裸露;火灾自动报警系统、自动灭火系统设计;动力电源、通风、安防等系统与消防联动。4、保温、隔热、隔音机房结构保温、隔热、隔音。系统总体设计(Overalldesignconcept)6,5%Processdesignofdustproof,waterproof,fireproof系统总体设计(Overalldesignconcept)6,5%机房整体布局-ITroom1系统总体设计(Overalldesignconcept)6,5%机房整体布局-ITroom2系统总体设计(Overalldesignconcept)6,5%机房整体布局-配线间Distributionroom1-4机房装修系统Decoration机房装修系统Decoration抗静电活动地板Antistaticmovablefloor500mm高地板500mmhighfloor净高大于3.0米Clearheightmorethan3metres乳胶漆墙面Latexpaintwall无天花设计Noceilingdesign机房配电系统Electrictiy机房配电系统Electrictiy配电系统设计机房设置1台配电柜;从大楼配电室引一路市电进入机房配电柜,市电电源主要提供机房内空调、照明和维护电源插座等动力设备的供电。从机房配电柜输出一组电源至UPS,UPS电源为机房内的服务器、交换机、存储设备等计算机设备的用电以及机房内的应急照明。IT机房1和IT机房2均设置UPS扩展位置IT机房1另设置单独UPS供电给配线间设备。Setup1powerdistributioncabinets.Powersourcefromthebuildingpowerdistributionroom,Citypowersupplyair-conditioning,lightingandmaintenancepowersupplysocket.UPSpowersupplyservers,switches,storagedevicesandcomputerequipment,electricityandthemachineryroomemergencylighting机房UPS不间断电源系统UPS机房UPS不间断电源系统UPSUPS系统配置机房1ITRoom1:40KVAUPSAPC-MGEGalaxy350040kVA400V1组(32节)65AH电池后备时间0.5小时40KVAUPSAPC-MGEGalaxy350040kVA400V1groups(32)65AHbatterystandbytime0.5hours预留扩展位100%capacityextension.机房2ITRoom2:40KVAUPSAPC-MGEGalaxy350030kVA400V1组(32节)65AH电池后备时间0.5小时40KVAUPSAPC-MGEGalaxy350030kVA400V1groups(32)65AHbatterystandbytime0.5hours预留扩展位100%capacityextension.配线间1-4DR1-4:5KVAUPSAPCSmart-UPSRT5000VA230V1组(4节)65AH电池后备时间0.5小时5KVAUPSAPCSmart-UPSRT5000VA230V1groups(4)65AHbatterystandbytime0.5hours机房UPS不间断电源系统UPS推荐的UPS产品Galaxy350040kVA400V
APCSmart-UPSRT5000VA230V产品特性请参见说明文档机房防雷接地系统Lightingprotection&grounding机房防雷接地系统Lightingprotection&grounding本设计是根据对机房电源实行三级的电源防雷保护。对直击雷的防护可凭借大厦相关措施。机房电源防雷主要针对感应雷、电力系统各种操作过电压进行保护。一级防雷:采用开关型SPD产品,在机房配电室低压配电柜中进线总开关处安装。二级防雷:采用限压型SPD产品。在机房UPS输入端和机房所在楼层的分配电柜处安装。该防雷器的设计目的:依据VDE-0675标准对1000V以下的低压负荷设备依据标准实行保护。它保护电气设备不受雷电和开关操作所引起的瞬态过压损坏,将电源防雷器置放在配电柜中总开关前端,这样既节省空间,又起到了美观、易维护的作用,防雷器中的地线就近接到防雷地上。三级防雷:对于机房内的重要设备(如小型机、服务器、交换机等)可以加装防雷插排为设备供电。机房防雷接地系统Lightingprotection&groundingThedesignisbasedonthreelayerpowersupplylightningprotection.Directlightningprotectionbybuildingmeasures.Lightningprotectionofpowersystemdesignedforinductionthunder,operatingovervoltageprotection.Level1ofprotection:useofswitchtypeSPDproducts,installinthelow-voltagedistributioncabinetinletwireswitch.Level2ofprotection:thevoltagelimitingtypeSPDproducts.InstallinUPSinputterminalandadistributioncabinet.ThelightningprotectiondevicedesignedaccordingtoVDE-0675standardtolessthan1000V.Itprotectstheelectricalequipmentfromlightningandswitchingoperationtransientovervoltage,powerlightningprotectiondevicearrangedinthepowerdistributioncabinetswitchfront,therebysavingspace,alsobeautiful,easymaintenance,lightningarrestergroundingthenearestearthpoint.Level3ofprotection:theequipment(suchasservers,switches)powersupplysocketcaninstalllightningprotection.机房防雷接地系统Lightingprotection&grounding设置以下几种接地: 计算机系统的直流工作地 安全保护地 交流工作地 防雷接地 机房静电防护系统(静电散流网)TheServerroomshouldsetthefollowingkindsofgrounding: computersystemDCgrounding safetyprotectiongrounding ACgrounding lightningprotectiongrounding electrostaticprotectionsystem(electrostaticpowderdrift)机房空调系统Airconditionner机房空调系统Airconditionner热负荷计算(计算过程请参见技术说明)Heatloadcomputation(caculationprocessseetechnicalnote)Q1Q2Q3Q4Q5热负荷小计Heatload制冷量需求Mincoolingcapacity机房1ITRoom115050104903439.586020398.5Kcal/h23.72KW机房2ITRoom2150501238.403601.586020749.9Kcal/h24.13KW配线间1DR1481.6137.601246.501865.7Kcal/h2.17KW配线间2DR2481.6137.601246.501865.7Kcal/h2.17KW配线间3DR3481.6137.601246.501865.7Kcal/h2.17KW配线间4DR4481.6137.601246.501865.7Kcal/h2.17KW机房空调系统Airconditionner冷源设计采用风冷精密空调设备,采用环保型制冷剂。考虑到将来设备的扩容因素,空调制冷量设计应有余量保证。机房1、机房2设计至少25KW的制冷量的空调系统,每个机房设计选用Stulz公司的2台制冷量29.1KW的CPD291精密空调,单回路系统,1+1冗余模式。每个配线间设计至少2.5KW的制冷量的空调系统,设计每个机房选用大金公司的1台制冷量1P(3KW)普通空调,单回路系统。机房1和2空调的出风形式:风冷下送风配线间1-4空调的出风形式:风冷上送风Consideringthefutureequipmentexpansionfactor,airconditioningrefrigerationquantityshouldbedesignedtoensureroomdesignmargin,design25KWrefrigeratingcapacityforITroom1&2.eachroomuse2ofStulzCPD2911+1RedundancyAircooledlowerblowing.EachDRset2.5kwaircon,useDaikin1HPcommercialaircon.Aircooledupperblowing.Design:precisionairconditioningequipment,usingenvironment-friendlyrefrigerant.。机房环境监控系统Enviromentmonitoring机房环境监控系统系统设计设计综合监监控和管理的区域主要包括:机房各功能区根据用户实际主要,机房集中监控系统主要包括六个子系统:配电监测子系统、UPS监测子系统、空调监控子系统、漏水检测子系统、温湿度监测子系统、消防报警监测子系统等。通过RS485总线将各个子系统连接起来,形成一个智能型机房动力与环境集中监控系统。Accordingtocentralizedmonitoringsystemrequirements,designofintegratedsupervisionandcontrolsystemmonitoringregioninclude:ServerroomAccordingtotheactualrequirements,centralizedmonitoringsystemmainlyincludessixsubsystems:powerdistributionmonitoringsystem,UPSmonitoringsubsystem,airconditioningsystem,waterleakagedetectionsubsystem,temperatureandhumiditymonitoringsystem,firealarmmonitoringsystem.ThroughtheRS485busconnectingthevarioussubsystems,forminganintelligentServerroompowerandenvironmentcentralizedmonitoringsystem.机房环境监控系统系统结构拓扑图:Systemtopologygraph:
机房消防系统Gasextinguisher机房消防系统系统设计机房是重要资料电子信息的保护场所。所以必须设计一个安全、可靠、先进的消防系统确保机房的安全运行。根据消防设计规范以及招标要求,机房采用七氟丙烷管网式气体消防系统。系统控制方式:本系统具有自动、手动、机械应急操作三种启动方式。Serverroomistheimportantelectronicinformationprotectionareas.Mustdesignasafe,reliable,advancedfireprotectionsystemtoensurethesafeoperationoftheServerroom.Accordingtothecodeforfireprotectiondesignandtenderrequirements,firesystemuseFM200pipenetworktypegasfirefightingsystem.Thesystemhasautomatic,manual,mechanicalemergencyoperationthreestartingways.机房消防系统GasautomaticfireextinguishingsystemFM-200洁净气体自动灭火系统的性能特点
Cleangasautomaticfireextinguishingsystemperformancecharacteristics1) 灭火速度快、效率高、主动性强speed,highefficiency,stronginitiative2) 洁净Clean3) 安全Safe4) 环保environmentalprotection5) 经济economy机房综合布线系统IndoorCabling机房综合布线系统IPDS系统设计Design光纤主干布线系统:24芯室内多模万兆光缆。Fiberopticbackbonecablingsystem:24coreindoormultimode10Gcable.铜缆布线系统:六类屏蔽双绞线,统一采用独立弱电桥架走线方式Coppercablingsystem:cat6unshieldedtwistedpair,adoptaunifiedindependentELVcabling右侧:ITROOM1indoorcablingdiagram机房综合布线系统IPDS系统设计Design光纤主干布线系统:24芯室内多模万兆光缆。Fiberopticbackbonecablingsystem:24coreindoormultimode10Gcable.铜缆布线系统:六类屏蔽双绞线,统一采用独立弱电桥架走线方式Coppercablingsystem:cat6unshieldedtwistedpair,adoptaunifiedindependentELVcabling右侧:ITROOM2indoorcablingdiagram系统设计技术标准Designcode&standard系统设计技术标准Designcode&standard系统设计技术标准Designcode&standard系统设计技术标准Designcode&standard系统设计技术标准Designcode&standard系统设计技术标准Designcode&standard系统设计技术标准Designcode&standard系统设计技术标准Designcode&standardATOS简介introductionofAtosoriginATOS简介introductionofAtosorigin源讯公司(ATOS)是一家全球领先的信息技术服务公司。它在法国巴黎证交所上市,注册地址位于法国巴黎,运营总部设在比利时布鲁塞尔。公司年收入50亿欧元;全球4.8万名员工;业务涉及40余个国家和地区。ATOSOrigin和西门子IT集团成立了新的全球IT战略合作伙伴关系,自2011年7月合并成立源讯公司(ATOS)。源讯公司为客户提供完整的业务和信息整合服务,我们的三大服务领域如下:管理咨询;系统集成;运营管理。Atosorigin(ATOS)isaleadingglobalproviderofinformationtechnologyServicesCompany.ItlistedinFranceParisstockexchange;registeredaddressislocatedinFranceParis,operationalheadquartersinBrusselsBelgium.Thecompanyanannualincomeof5trillioneuros;global48000employees;businessinvolvesmorethan40countriesandregions.ATOSOriginandSiemensITgroupestablishedanewglobalITstrategiccooperativepartnership,mergedin2011JulytradeasATOSorigin(ATOS).Atosprovidecustomerscompleteservicesandinformationintegrationservices,ourthreemajorserviceareasareasfollows:managementconsulting;systemintegration;operationmanagement.ATOS简介introductionofAtosorigin源讯公司在全球提供多样综合的IT服务,支持全球信息产业和互联网行业的发展。源讯公司在中国市场活跃超过15年;一千多名员工分布在在北京、上海和广州地区;数据中心位于香港和上海;具备全球采购和服务中心功能。AtosoriginoffersavarietyofintegratedITservicesintheworld,supportfortheglobalinformationindustryandthedevelopmentoftheInternetindustry.AtosorigininChinesemarketisactiveformorethan15years;morethanonethousandemployeeslocatedinBeijing,ShanghaiandGuangzhou;datacenterislocatedinHongkongandShanghai;withglobalsourcingandservicecenter.ATOS简介introductionofAtosorigin源讯公司提供首屈一指的服务,包括:数据中心服务:数据中心是整个企业IT基础中的基础,其稳定性直接影响企业的信息化水平咨询服务包括以下几个阶段,在各个阶段,协助甲方明确需求和技术方案,绿色数据中心咨询,提出合理化建议,帮助甲方选择最优决策,保证投资的合理性;可行性研究;立项;招标书——技术部分的制作;中标方初步设计;深化设计;实施过程监督指导;工程验收;运维移交。Datacenterservices:DatacenteristheentireenterpriseITfoundation,itsstabilitydirectlyaffectthelevelofenterpriseinformationAdvisoryservicesincludingthefollowingseveralstages,ineachstage,toassistcustomerhaveacleardemandandtechnologyscheme,greendatacenter,proposestherationalizationproposal,helpthecustomerchooseoptimaldecision,guaranteedinvestmentrationality;feasibilitystudy;project;tender--technologypartproduction;preliminarydesign;detaileddesign;implementationprocesssupervisionguidance;acceptance;operationtransfer.ATOS简介introductionofAtosoriginATOS简介introductionofAtosorigin源讯在全球的数据中心业务的主要客户Atosoriginmajorcustomersintheglobaldatacenterbusiness:序号No.项目名称projectname完成时间Finishtime1泰国曼谷国际机场信息总包---数据中心ThailandBangkokInternationalAirportInformationPackage-DataCenter20052印度德里国际机场信息总包---数据中心IndiaDelhiInternationalAirportInformationPackage-DataCenter20073印度班加罗尔国际机场信息总包---数据中心IndiaBangaloreInternationalAirportInformationPackage-DataCenter20084印度海德拉邦国际机场信息总包---数据中心
IndiaheadPradeshIn
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 物业公司绿化管理制度
- 汽车行业研发项目经理面试技巧大全
- 37.-XX区实验初级中学2026年春季学期教导处教学仪器设备管理方案
- 专门学校考勤制度
- 安保人员日常考勤制度
- 中国电信考勤制度
- 浙江金华市义乌市2025-2026学年第一学期七年级道德与法治期末考试试卷(无答案)
- 2025-2026学年第二学期北京东直门中学九年级数学开学测试卷(无答案)
- 小规模企业考勤制度
- 居家办公按照考勤制度
- 博物馆讲解培训课件
- 《机械设计》课件-上
- 卧底侦查话术手册
- 2026年-高中语文阅读理解专题训练50篇(含答案)
- 2026年湖南高速铁路职业技术学院单招职业技能考试必刷测试卷及答案1套
- 护理文件管理制度
- 2025福建福港拖轮有限公司招聘7人笔试历年备考题库附带答案详解试卷2套
- 广东省惠州市示范名校2025-2026学年物理高二第一学期期末学业水平测试试题含解析
- 多模态信息环境下虚假新闻智能检测技术研究
- 2025公安机关执法资格考试笔试试卷及答案
- 特教学校安全第一课课件
评论
0/150
提交评论