目录.docx

低压开关柜母排设计与研究含SW三维及4张CAD图

收藏

资源目录
跳过导航链接。
压缩包内文档预览:
预览图 预览图 预览图 预览图 预览图
编号:20808907    类型:共享资源    大小:40.38MB    格式:RAR    上传时间:2019-07-12 上传人:QQ14****9609 IP属地:陕西
50
积分
关 键 词:
设计含SW三维 及4张CAD图纸 含SW三维及4张CAD图 张CAD图纸 含SW三维及 设计及sw三维 含4张CAD图
资源描述:
低压开关柜母排设计与研究含SW三维及4张CAD图,设计含SW三维,及4张CAD图纸,含SW三维及4张CAD图,张CAD图纸,含SW三维及,设计及sw三维,含4张CAD图
内容简介:
低压开关柜母排设计与研究含SW三维及4张CAD图需要咨询购买全套设计请加QQ1459919609-图纸预览详情如下:A1示意图.dwgA1装配图.dwgANSYS EM仿真结果.zipSW示意图.zip低压开关柜母排设计与研究任务书.docx低压开关柜母排设计与研究开题报告.doc低压开关柜母排设计与研究立体审核表.doc低压开关柜母排设计与研究答辩稿PPT.ppt外文翻译文件清单.txt母排SW三维设计.zip母排图.DWG测量数据.zip目录.docx相关图片.zip装配图.DWG设计副本说明书.docx摘 要处于“中国制造2025”大环境下,中华民族正加大力度促使祖国建设的进步,努力把国家建造成生产制造大国。在这个智能化时代,很多方面都需要电力的支持,低压开关柜作为用户和电网进行沟通的智能化设备,重要性不言而喻。这次研究设计能够使低压开关柜更加智能,更加小型化和更加低成本,能够满足及适应现的新型电网发展要求。本文内容如下:(1)对母排的电磁干扰源和传播方式进行分析,通过棱边单元法分析计算母排通入电流不同时磁场强度大小,找到磁场随母线在不同的电流、间距及高度的变化规律。使用Ansys仿真软件进行母排室仿真设计以及分析,确定母排参数。(2)利用GMR传感器确定最佳测试位置为Y=10cm,X=20mm,GMR传感器的线性工作区间为0-1000A,电流测量的相对误差不超过0.50%等较满意的测试结果,证明了该母排设计的稳定和可靠性,满足了智能电网的基本需求。关键词:低压开关柜,母排,电磁仿真DESIGN and RESEARCH on BUSBAR of LOW VOLTAGE SWITCHGEARABSTRACTUnder the environment of made in China 2025, the Chinese nation is stepping up its efforts to promote the progress of the construction of the motherland and to build the country into a big country of production and manufacture. In this intelligent era, many aspects need the power support, low-voltage switchgear as the intelligent equipment for communication between the user and the power grid, the importance is self-evident. This research and design can make the low-voltage switchgear more intelligent, smaller and lower cost, and can meet and adapt to the requirements of the new grid development. The contents of this article are as follows:(1)The electromagnetic interference sources and propagation modes of the bus row are analyzed and calculated by the edge element method. The variation rule of the magnetic field with different current, spacing and height of the bus line is found out. The simulation design and analysis of the master row chamber are carried out by using the Ansys simulation software, and the parameters of the bus row are determined.(b) The GMR sensor is used to determine the optimal test position is Y=10cm, X= 20mm, the linear operating range of the sensor is 0 1000A, the relative error of current measurement is not more than 0.50%, etc. The stability and reliability of the bus design are proved. Meet the basic needs of the smart grid.Key words: low voltage switch cabinet ,Busbar,Electromagnetic simulation目 录摘要1ABSTRACT21 绪论31.1 课题研究背景31.1.1 智能电网下的低压开关柜31.1.2 低压开关柜的种类及结构31.2 低压开关柜国内外现状41.2.1 低压开关柜母排研究国内外现状41.2.2 本研究设计国内外分析现状51.2.3 母排抗电磁干扰研究近况61.3 研究意义及设计目标61.3.1 研究意义61.3.2 设计目标62 低压开关柜母排大电流测量研究72.1电流测量方法72.1.1 经典测量电流方法72.1.2 智能测量电流方法92.2 Giant Magneto Resistance原理基础102.2.1 巨磁阻测量原理102.2.2 静态磁场研究122.3 Giant Magneto Resistance 阵列研究142.3.1 Giant Magneto Resistance测量阵列拓扑142.3.2 矩阵数学模型152.4本章小结173 低压开关柜磁场仿真与研究173.1 电磁场计算分析173.1.1 数值分析方法173.1.2 电磁场有限元法183.2 低压开关柜母排室有限元处理203.2.1 母排电磁场方程203.2.2 电磁场方程棱边元离散213.3 GMR传感器测量位置的确定233.3.1GMR传感器位置实验233.3.2 磁场数据仿真263.3.3 数据线性分析273.4 母排设计数据分析293.4.1 工作电流大小产生的效应293.4.2 母排与母排间距大小的影响303.4.3 母排高度大小的影响323.5 本章小结334 低压开关柜母排室抗电磁干扰研究344.1 电磁干扰的方式344.2 低压开关柜相关电磁干扰354.2.1 柜体内部干扰源354.2.2 柜体弱电系统受干扰分析364.3 低压开关柜电磁抗干扰研究364.3.1 监控系统屏蔽364.3.2 母排室屏蔽384.4 本章小结425 低压开关柜母排三维仿真模型425.1 三维仿真模型425.1.1 建立电磁场中母排仿真模型425.1.2 母排材料确定445.1.3 电流相关条件的确定445.1.4 仿真结果总结455.2 低压开关柜母排室结构465.2.1 确定母排摆放方式475.2.2 确定母排选取规格495.3 本章小结506 全文总结与期望506.1 全文总结506.2研究展望51参考文献52附录54The Effect of Altitude on the Operation Performance Of Low Voltage Switchgear and Controlgear Components ALTITUDE (m) G. Erich Heberlein Jr. Senior Member, IEEE Director of Engineering Packaged Control Products Rockwell Automation 788 North Jefferson St. Milwaukee, WI 53202 USA Phone: 414.382.2004 Fax: 414.382.0273 geheberlein VOLTAGE CURRENT Chester Malkowski, Jr. Member, IEEE Senior Principal Engineer Packaged Control Products Rockwell Automation 788 North Jefferson St. Milwaukee, WI 53202 USA Phone: 414.382.3054 Fax: 414.382.0273 Cmalkowski 2600 Michafel J. Cibulka Member, IEEE Project Engineer High Current Laboratory Rockwell Automation 1201 outh 2“d Street Milwaukee, WI 53204, USA Phone: 414.382.4627 Fax: ,414.382.2255 Micibulka 0.95 0.99 Abstract- Decreased air density due to increased altitude can have an effect on the operation performance of low voltage switchgear and controlgear components. For applications at high altitude little is known about this effect on the operation performance of these components. Characteristics such as dielectric voltage-withstand, thermal ampacity, overload calibration, contact life and interruption capability can be affected by the decreased air density. Tests were conducted in an electrical laboratory capable of producing needed electrical circuit parameters. The testing was conducted using a vacuum chamber to artificially lower the air density to simulate altitudes up to 6000 m A fact finding study was developed defining the operation performance capabilities for low voltage components at higher altitudes. 1500 I. INTRODUCTION 0.95 0.99 There is little technical guidance for high altitude applications, e.g. altitudes from 1000 m to 6000 m, of low voltage switchgear and controlgear components (LVCs) used in low voltage switchgear assemblies, motor control centers and panels. These LVCs include: molded case circuit breakers, disconnect switches, fuses, starters, contactors, soft start solid state starters, variable frequency drives, overload relays, control relays, and transformers. Since the air pressure and density decrease as the altitude increases the operation performance for LVCs is affected, in theory, the dielectric voltage withstand is reduced, thermal ratings are reduced, calibration is affected, contact life is affected, contactor interruption performance is reduced, and short-circuit interrupting capability is reduced. There is some guidance based on IEEE Std. 27 which provides empirical correction factors for the voltage rating (dielectric withstand) and current rating (thermal ampacity) l. See Table I. An example of how these altitude correction factors can be applied is shown in Table 11, However, information is not provided on operation performance criteria such as current interruption, which may also be affected by the reduction I 3000 0.80 TABLE I ALTITUDE CORRECTION FACTORS FROM IEEE STD. 27 0.96 I CORRECIION FACTORS ALL OTHER TYPES OF SWITCHGEAR ASSEMBLIES I CORRECTION FACTORS CURRENT VOLTAGE, ALTITUDE (m) loo0 I 1 .w I 1 .XI ALTITUDE (m) BUS AMPACITY (A) “1 3 m 768 I152 1536 1920 2400 of the dielectric and thermal characteristics at higher altitudes. Thus, engineers applying equipment at high altitudes have little guidance for properly selecting LVCs, and in reality, no guidance at all is provided for applications at altitudes above 3000 m. An example of LVC industry standards where altitude requirements are found is the NEMA Standard ICs 1-1993 2. This NEMA standard defines two altitude classes. Class 1 Km is for equipment installations that do not exceed an altitude of 1000 m. Systems using power semiconductor equipment are usually Class 1 Km. 0-7803-6401-5/00/$10.00 0 2000 IEEE 2688 Class 2 Km is for equipment installations that do not exceed an altitude of 2000 m. Electromagnetic and manual devices are Class 2 Km. However, guidance is not given in this standard for qualifying LVCs above these altitudes. Also, the International Electrotechnical Commission (EC) Standard, IEC 60947-1, includes a restriction that LVCs should not be applied above 2000 m 3. However, included in IEC 60947-1 is a note that permits LVCs to be used at higher altitudes, but the reduction of dielectric strength and cooling effects of the air must be addressed. As in the NEMA standard, guidance is not provided in IEC 60947-1 for qualifying LVCs for use above 2000 m nor is there guidance on how, at higher altitudes, the reduction of dielectric strength and cooling effects can be addressed. Thus, in order to address these LVC performance and application issues at different altitudes, a research program was initiated. This program was designed to investigate, not only, the effects caused by reduction of dielectric strength (dielectric withstand performance) and cooling effects (thermal capacity) of air at higher altitudes, but also investigate other operation performance criteria to determine if there were any significant performance changes, e.g., calibration, overload interruption, contact life, and short- circuit interruption. To investigate the affect on the operation performance for LVCs at increasing altitude, tests were conducted using a vacuum chamber to simulate the air densities normally found at the corresponding altitudes. See Fig. 1. The LVCs tested consisted of components qualified or addressed by IEC Standards, NEMA Standards, and Underwriters Laboratory Standards (Standards, et al) 3141516171 8191 l0lU 11. 11. TEST PROGRAM COMMENTS It must be noted that this investigation was not meant to be a qualifying type test program but a program to establish if there is significant change in the performance data due to changes in air density. Therefore, the test parameters, at times, were more severe than the norm in order to make this determination. Also, the test devices were selected as representative samples of LVCs and with the hope that the testing of these particular samples might demonstrate significant findings. This program is a first step process to determine which operational performances would indicate significant trends. Further testing may be required to more accurately determine the exact impact that altitude has on the operational performances. The altitude stated as 0 m in this investigation, air pressure norm 101.3 kPa, was not actually at sea level, but at the altitude of the test laboratory which is approximately 200 m 12. The air pressure of the laboratory was recorded before each test series and ranged from 99.9 kPa to 103.3 kPa. The air pressure in the test chamber was set at Fig. 1. Test Setup 47.1 kPa for the maximum test altitude of 6000 m. Fig. 2 shows the correlation of air pressure to altitude and was used for establishing the pressure for the testing with the base of 101.3 kPa for the air pressure at sea level 12. Although humidity was not considered in the study, it may have had some effect on certain tests. The humidity was monitored throughout the testing and the humidity did change at the different altitudes, e.g., 0 m to 6000 m altitudes, the humidity decreased from 17% RH to 12% RH respectively. 120 100 20 0 0 1500 3000 4500 6000 Altitude (m) Fig. 2. Air Pressure at Altitude 2689 111. DIELECTRIC WITHSTAND PERFORMANCE The Standards, et al, require through air and over surface requirements as well as a dielectric withstand test. These dielectric performance requirements are conservative and the LVCs have a very high dielectric withstand capability. Therefore, performing dielectric withstand tests on a product may not indicate any significant correlation to field usage at high altitude. Factors of material selection, the porosity of the materials used, and the design configuration may be more significant on LVC dielectric withstand performance than the reduction in dielectric strength due to the effects of lower air density at higher altitudes. However, to address the effects in dielectric withstand performance at higher altitudes, LVC samples were tested in a devised circuit based on Standards, et al. The dielectric withstand test was as follows: The three line terminals were connected together by jumpers. The three load terminals were also connected together by jumpers. A dielectric withstand test voltage of 2200 V was applied between the line and load terminals, with the device contacts open. See Fig. 3a. The air pressure was gradually decreased until the air pressure corresponding to an altitude of 6000 m was attained, i.e. altitude from 0 m to 6000 m. The circuit was changed. The jumpers were removed. The B phase line terminal was connected to earth by a jumper. The A and C phase load terminals were connected together by a jumper. The device contacts are closed and a dielectric withstand test voltage of 2200 V was applied between the B and the C phase line terminals. See Fig 3b. The air pressure was gradually increased until the air pressure corresponding to an altitude of 0 m was attained, i.e., altitude from 6000 m to 0 m. The duration of the test for each LVC was approximately 4 minutes. The current of the high voltage source was monitored throughout the duration of the test and set to trip at 50 mA leakage current. The following LVCs were subjected to dielectric withstand tests: IEC contactor, NEMA contactor, IEC circuit breaker, NEMA circuit breaker. All the devices successfully withstood 2200 V without breakdown at all altitudes. The findings indicated that there is sufficient margin in the design of the devices so that de-rating is not required for dielectric withstand performance at higher altitudes. IV. THERMAL AMPACITY It is known that for bus bar systems in open air the cooling and resultant thermal ampacity is adversely affected due to the lower air density at higher altitudes. Thus, IEEE Std. 27, as indicated in Table I, provides guidance regarding current de-rating based on altitude 11. However, lower air density at higher altitudes, should have less effect on LVCs since the internal components current carrying parts f“f“r-1 Fig. 3a. Dielectric performance (Contacts Open) Fig. 3b. Dielectric performance (Contacts Closed) are in contact with component moldings. Substantial cooling occurs by the conduction of heat through the molding material, which in turn, distributes the heat to the mounting plate. The effect on thermal ampacity for the LVCs was evaluated by placing the devices in the altitude test chamber and conducting a temperature: rise test at the simulated altitude air pressures. However, because the vacuum test chambers thick aluminum walls might act as a heat sink and effect the test results, the test.s samples were not mounted directly to the chamber but were suspended by wires. Thus, the change to the air density should be the only variable which would affect the temperamre test results. The following LVCs were subjected to a temperature test: IEC contactor, NEMA circuit breaker, HRC fuse. All the temperature tests were run at the maximum rated current for the LVC. The findings of the tcmperature rise test are shown in Fig. 4. The tests indicate that thermal capacity is significantly affected by altitude. The tests also indicate that devices with thermal elements., such as circuit breakers and fuses, are affected more significantly than devices without 35 , - 1 , 15 10 0 m 6030 Alutude (m) 1.1 IEC Contactor - - Thermal Magnetic Cllrlut Breaker IEEEStd 27 - HRC Fuses - Fig. 4. Ternperamre Test 2690 thermal elements, such as contactors. Interestingly, fuses were affected to such a great degree that this performance would need to be addressed when applying fuses at high altitudes. Also, plotted in Fig. 4 for comparison, is the thermal correction factor for 0 m to 3000 m based on IEEE Std. 27 with 3000 m to 6000 m extrapolated. ; 1 0 - f 9 n s - c 00 V. COMPONENT CALIBRATION PERFORMANCE T LVCs that provide overload current protection contain bimetallic, eutectic, or electronic elements for monitoring the current. This being the case, the decreased air densities at higher altitudes can have an effect on the calibration because the load current or 12R is actually monitored through heat transfer, e.g., convection and radiation of the heat to a bimetal. Also, the electronic devices often contain heat sensing elements, e.g., thermistors. These elements are used for monitoring the ambient, the circuit board, reset time, etc., and may affect the operation performance at lower air densities. A comparison of the calibration at different altitudes was evaluated by conducting an overload calibration test at 300% of the overloads trip setting and monitoring the trip time. The following LVCs were subjected to the overload calibration test: NEMA eutectic overload relay, IEC bimetal overload relay, IEC electronic overload relay with current transformers, IEC electronic overload relay with hall effect current monitors. The findings of the calibration performance tests are shown in Fig. 5. The tests show that the eutectic and bimetal overload relays are affected by the air density at higher altitudes and that the electronic overload relays are not adversely affected. Therefore, it would be necessary to use altitude correction factors with the eutectic and bimetal overload relays in order to avoid nuisance tripping. The findings support the use of electronic overload relays for applications above 2000 m. I I I n 3 m 6wO Altitude (m) -. Eutectic Alloy Heater - IEC Electronic (CT) 7 - - IEC Electranic (Hall Effect) - IEC Bimetalhc Element Fig. 5, Overload Calibration VI. CONTACT LIFE PERFORMANCE Contact life is a part of the application requirements for motor contactors. The type of operation affects the selection and sizing of the contactor for a given application, e.g., number of normal start and stop operations (AC3), percent of inching and plugging duty (AC4), etc. 3. Manufacturers supply contactor life curves and formulas to assist the application engineer in selecting the appropriate size contactor for the application. However, should there be a significant change to contact life at higher altitudes, the application engineer would have to address this change. A contactor with well known contact life was chosen for this testing. The contactor samples were disassembled and each of the contacts were carefully weighed. The contactors were then reassembled and a contact life performance test at the various altitudes was run. The contacts were re-weighed upon conclusion of the testing. Using this data, the altitude effect on contact life performance was evaluated. NEMA contactors were subjected to the contact life test. An example of the findings of the contact life test are shown in Fig. 6. The findings indicate there is no significant effect on the contact life caused by lower air densities at higher altitudes. To the contrary, the findings indicate that the contact life is slightly improved at higher altitudes. Therefore, it would not be necessary to change the contact life criteria used for selecting and sizing contactors at altitudes up to 6000 m. 0 1000 2000 3000 4000 SO00 6000 Altitude (m) Fig 6. Loss of Contact Material VII. CONTACTOR OVERLOAD INTERRUPTION PERFORMANCE Switching devices with limited interrupting capacity, such as contactors and disconnects, may be required to interrupt currents of ten to twenty times their ratings, e.g., lock rotor currents, inrush currents, etc. This interruption capacity is not a normal duty requirement, but a requirement under an overload condition. Thus, it is essential that the interrupting capacity should not be reduced with the increase in altitude. A contactor with well documented interruption capacity was chosen for this testing. The starting test current for each test 269 1 altitude was 50 A less than the known maximum interruption current of the contactor at sea level. Understandably, there is some variation in the interruption performance level, therefore, five test trials were conducted at each current level. The current level was increased 50 A if the device passed, and the test series repeated until the maximum interruption level was determined. To keep the test conditions as constant as possible, the tests were conducted as opening (0 shots) only. Thus, on these tests an external close-in contactor was used to eliminate any influence on the test sample interruption performance. IEC contactors were subjected to the contactor overload interruption test. The findings of the interruption performance tests are shown in Fig. 7. The findings indicate that the contactor interruption is improved at higher altitudes. The amount of current the contactor could successfully interrupt, increased as the altitude increased. Therefore, the interrupting rating of the contactors would not require de-rating at altitudes up to 6000 m. ,-. 40 E 2 35 E 6 30 .g 25 a $ 20 . . 5 I 5 10 c U 0 0 1 5 W 3oM 45cQ 6wO Altitude (m) - IEC Contactor - - . IEC Conmtor(Trend) Fig. 7. Contactor Overload Interruption closing angle is a difficult case for interruption by current limiting breakers as well. The following LVCs were subjected to a short-circuit interruption test: IEC circuit breaker, NEMA circuit breaker, HRC fuse. The short-circuit interruption tests were run at the rated short-circuit current and1 voltage for the LVC. Examples of the findings for the interruption performance tests are shown in Fig. 8 through Fig. 10. The findings indicate that all the LVCs appear to have sufficient margin in the design of the devices enabling them to interrupt their rated interrupting current at higher altitudes. However, the findings also indicate that while the pea
温馨提示:
1: 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
2: 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
3.本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
提示  人人文库网所有资源均是用户自行上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作他用。
关于本文
本文标题:低压开关柜母排设计与研究含SW三维及4张CAD图
链接地址:https://www.renrendoc.com/p-20808907.html

官方联系方式

2:不支持迅雷下载,请使用浏览器下载   
3:不支持QQ浏览器下载,请用其他浏览器   
4:下载后的文档和图纸-无水印   
5:文档经过压缩,下载后原文更清晰   
关于我们 - 网站声明 - 网站地图 - 资源地图 - 友情链接 - 网站客服 - 联系我们

网站客服QQ:2881952447     

copyright@ 2020-2025  renrendoc.com 人人文库版权所有   联系电话:400-852-1180

备案号:蜀ICP备2022000484号-2       经营许可证: 川B2-20220663       公网安备川公网安备: 51019002004831号

本站为文档C2C交易模式,即用户上传的文档直接被用户下载,本站只是中间服务平台,本站所有文档下载所得的收益归上传人(含作者)所有。人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对上载内容本身不做任何修改或编辑。若文档所含内容侵犯了您的版权或隐私,请立即通知人人文库网,我们立即给予删除!