下载本文档
版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
1、SummaryDescription/描绘TheproducttemperaturesensorinGlattfluidbeddriercannotbecalibratedbeforeremovingfromthesystem,discrepancywasinitiatedaccordingtoSOP-0102619section6.1.7Adiscrepancymustbeinitiatedwhenacalibrationfailsornoasfoundreadingscanbetakenbeforethesensorremovedfromthecalibrationschedule.Gla
2、tt制粒机里的产品温度传感器在从系统删除前没法做校验,依据SOP-0102619步骤“校准失败或当仪表从校准计划中删除没法获取前校数据时,一定启动差别办理程序”启动误差。1.Deviation/Actions/误差行动Productionstaffobservedtheproducttemperaturesensorwasbrokenon2015.11.24,maintenanceteamreplacedthebrokenproducttemperaturesensorwithanewimprovedoneon2015.11.26.WorkorderreferstoattachmentTW11
3、18464-01.生产部职工日产品温度传感器破坏,维修团队于日改换了新的经过改良的产品温度传感器。工单见附件TW1118464-01。2.CausalAnalysis/因果剖析5Whystoolwasusedtodothecauseanalysis.5WhysdiagramreferstoattachmentTW1118464-02.用了5Whys工具进行原由剖析。5Whys表示图拜见附件TW1118464-02。1stWhythetemperaturesensorcouldnotbecalibrated?/为何温度探头没法进行校验?(endat22:50on),alarm101-7”Prod
4、uctTemperatureFBD(T202010)-BrokenWire”occurred,operatorcheckedthealarmandfoundthatthepartofFBDproducttemperaturesensorholderinstalledoutofthechamberwasbroken.Electricalengineerwasinformedandconfirmedthatthesensorwasbroken.夜晚23:32左右在结束希罗达SH2105批次后(2015.11.24,22:50结束),Glatt系统发生报警101-7“物料温度(T202010)-断线
5、”,职工检查发现安装在FBD产品温度探头的腔体外面分连杆处断裂。通知了电工,电工确认该温度探头破坏。Calibrationteamcheckedthesensorandevaluatedthesensorcouldnotbecalibratedasthethermocouplemeltingpointofthesensorfelloffandnooutputsignaldetectedfromsensor.校验小组对探头进行了检查,评估该探头没法进行校准,因为探头热电偶熔点掉落且没有检测到信号输出。ThebrokenpartwasinstalledoutsideoftheFBDchamber,
6、pictureofbrokenproducttemperaturesensorreferstoattachmentTW1118464-03.Thebrokenpointwasmarkedwitharrow伤害的部分在FBD墙体外面,破坏的产品温度探头图见附件TW1118464-03。箭头标明了断裂点。Aboveall,damageofFBDproducttemperaturesensorcausedthatthesensorcannotbecalibrated.综上,FBD的产品温度探头破坏致使该探头没法进行校准。2nd-WhytheFBDproducttemperaturesensorwas
7、broken?/为何FBD温度探头被破坏?Bycheckingthebrokenproducttemperaturesensor,thethicknessoftemperaturesensorholderbrokenpointwasabout1mm,madeof316Lstainless.Theendoftheholderwasajunctionboxusedtoinstalltemperaturetransmitter,anditisabitheavy.经过查察破坏的产品温度探头,Glatt产品温度传感器连杆的断裂处壁厚约为1毫米,为316L不锈钢材质,后来部为接线盒,此接线盒用于安装温度变
8、送器,较重。Itispossiblethethinnerstainlessoftemperaturesensorholdercombiningtheheavierjunctionboxintheendledtomechanicalfatigueovertimeandcausedtheholderbrokeintwo.Aftertheholderbroke,thejunctionboxfelldownunderthegravity,pulledthetemperaturesensorandcausedthatthethermocouplemeltingpointofthesensorfellof
9、f.可能因为温度传感器连杆的不锈钢厚度较薄,而且后来端的接线盒较重,所以使用中简单造成材质的机械疲惫,发生断裂。连杆断裂后,接线盒因为重力作用下坠,拉扯温度探头,致使温度探头热电偶熔点掉落。ThebrokentemperaturesensorpassedthecalibrationbeforeinstalledontheFBD,thecalibrationcertificatereferstoTW1118464-05(TT-00142-PRO).Afterthediscrepancyoccurred,calibrationteaminitiatedthecalibrationdecommiss
10、ionforit.SeeattachmentTW1118464-05(TT-00142-PROCCAF-decommission).已破坏的温度探头在安装到制粒机前校准合格,校准证书见附件TW1118464-05(TT-00142-PRO)。此误差发生后,校验小组对该探头进行了报废,详见附件TW1118464-05(TT-00142-PROCCAF-decommission)。SimilarcaseoccurredinJuly2015,thedeviationreportnumberwasTW1062179,therootcausewassameasTW1118464.Followingrem
11、ediationactionwasdefinedinTW1062179followedaspostclosureactionTW1069248:contactSupplier,strengththetemperaturesensorholder,addthicknessupto2mm,andreplacethewiringinthejunctionboxintheendby2meterofflexiblecorddirectly.Thesupplierrespondeditwouldtaketimetochangethedesignofthesensor,thetargetcompletion
12、dateforthisactionis20015.07月发生过近似事件,详见误差TW1062179。误差TW1062179拟订了后续行动以封闭后行动TW1069248追踪:联系供给商,加厚温度传感器连杆壁厚至2毫米,同时后端接线盒接线方式改为直接2米软线引出。供给商答复因为改这个感觉器的设计需要花必定的时间,所以该行动的估计达成日期为。Whenthediscrepancy(TW1118464)occurredon2015.11.24,maintenanceteamjustreceivedthenewsensorandthecalibrationwasnotcompletedyet.本误差(TW
13、1118464)在日发生时,保护小组刚收到新的感觉器,还没有做校验。Causeconclusion/原由总结Thethicknessoftemperaturesensorholderwasabout1mm,madeof316Lstainless.Theendoftheholderwasajunctionboxusedtoinstalltemperaturetransmitter,anditisabitheavy.Itispossiblethethinnerstainlessoftemperaturesensorholdercombiningtheheavierjunctionboxinthee
14、ndledtomechanicalfatigueovertimeandcausedtheholderbrokeintwo.Aftertheholderbroke,thejunctionboxfelldownduetogravity,pulledthetemperaturesensorandcausedthatthethermocouplemeltingpointofthesensorfelloff,andthecalibrationcannotbeconducted.Glatt产品温度传感器连杆的断裂处壁厚约为1毫米,316L不锈钢材质,后来部为接线盒,此接线盒用于安装温度变送器,较重。推断因
15、为温度传感器连杆的不锈钢厚度较薄,而且后来端的接线盒较重,所以使用中跟着时间的推移简单造成材质的机械疲惫,发生断裂。连杆断裂后,接线盒因为重力作用下坠,拉扯温度探头,致使温度探头热电偶熔点掉落,没法进行校准。Recurringdiscrepancyassessment/重复发生的差别的评估(DateClosed)时间框架:查问的时间段从2013.11.19(Trackwise中gDMS在上海上线的日期)到(封闭时间)Assignedsite/工厂:ShanghaiResponsibleOperationalArea/操作地区:productionEquipmentID/设施编号:SH_SHiP
16、-GranulationsystemSearchingperfieldonRectextwith(allthesewords)/在每个可输入文字的地区搜寻重点词(全部这些字):ProductTemperatureSensorResult:tworecordswerefound,TW864400&TW1062179.TW864400wasrelatedtoLODofCellceptCapoutofacceptancelimit.TW1062179wassameasthenewdiscrepancy.Sothetrendstatusisrecurring.结果:搜寻到2个记录,TW864400&T
17、W1062179。TW864400是对于骁悉胶囊干燥失重超限。此中TW1062179和此差别一致,所以趋向状态为“重复”。.RemediationactionhasbeendefinedinTW1062179,therecordNo.wasTW1069248,tocontactsupplier,strengththetemperaturesensorholder,addthicknessupto2mm,andreplacethewiringinthejunctionboxintheendby2meterofflexiblecorddirectly.在TW1062179中已定义挽救举措:联系供给
18、商,加厚温度传感器连杆壁厚至2毫米,同时后端接线盒方式接线改为直接2米软线引出.新的产品温度感觉器已于安装上。3.RemediationActions/挽救行动TW1118464-05(TT-00145-PRO)forCalibrationCertificate.Afterthecalibrationresultpassed,electricalengineerchangedthenewtemperaturesensorfortheFBD,seeattachmentTW1118464-01forreplacementworkorder.(Done,2015.11.26),校验小组对新的温度传感
19、器进行了校验。校准证书见附件TW1118464-05(TT-00145-PRO)。校验合格后,电工改换了新的温度探头,工单见附件TW1118464-01。(已达成,)Thethicknessofthenewoptimizedtemperaturesensorholderhasbeenaddedupto2mm,andthewiringinthejunctionboxwasreplacedby2metersflexiblecorddirectly.改良的温度传感器连杆壁加厚至至2毫米,同时后端接线盒接线方式改为直接2米软线引出。4.ImpactAnalysis/影响剖析Withtimelychec
20、kafterdetectionofbrokenFBDproducttemperaturesensorholder,itwasconfirmedthatthebrokenpartwasoutoftheFBDchamberandtherewasnometalfragments.Theimpactonproduct/processwasexcludedimmediately.在发现FBD产品温度传感器连杆处断裂后实时检查,确认断裂处位于FBD锅体外面且没有金属碎屑产生。立刻清除了对产品/工艺的影响。XelodaTabSH2105wasthe4thbatchofthiscampaign,thegran
21、ulationprocessofbatchSH2105wasendat22:50on2015.11.24,andthealarmoccurredatabout23:32on2015.11.24.ReviewtheXelodaTabSH2102-SH2105GranulationReportdata,therewasnoalarminformation,andnoabnormalshownontemperaturecurve,seedetailsinAttachmentTW1118464-04.希罗达片剂SH2105为这个连续批次的第4个批号,SH2105批次制粒在夜晚22:50分结束,该报警发生在夜晚23:32分左右。回首XelodaTabSH2102-SH2105制粒报告数据,没有该温度传感器的报警信息,产品温度曲线数据没有异样,详见附件TW1118464-04。TheFBDwasusedforXelodatabletandCellceptcapsule,theproducttemperatureisamonitoringvalue,thegranulesqualityisevaluatedbytheLOD,therewasnoabnormalLODreportedduringtheu
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 2026年杭州西湖区青少年宫诚聘教师(非事业)考试参考题库及答案解析
- 智能机器:数字时代的工业变革核心力量
- 2026四川省第三人民医院高层次人才、成熟人才招聘12人考试参考试题及答案解析
- 2026年1月西安唐城医院招聘(48人)考试参考试题及答案解析
- 2026湖南邵阳邵东市市直事业单位人才引进62人笔试备考题库及答案解析
- 2026福建三明市清流县应急管理局招聘县森林消防大队劳务派遣人员1人考试备考题库及答案解析
- 2026年河南医药大学诚聘研究生辅导员10名考试备考试题及答案解析
- 食品饮料:白酒破而后立大众品顺势而为-
- 2026山东枣庄市台儿庄区面向2017年前招募仍在镇(街)工作“三支一扶”人员招聘镇(街)事业单位人员考试备考题库及答案解析
- 2026重庆九洲智造科技有限公司招聘研发工程师10人考试备考试题及答案解析
- 2026年辽宁金融职业学院单招职业适应性测试题库及参考答案详解
- 中小企业人才流失问题及对策分析
- 2026年教师资格之中学综合素质考试题库500道及完整答案【名师系列】
- 中海大海洋地质学课件第4章河口与海岸-3第十二讲
- 招标人主体责任履行指引
- 财务审计工作程序及风险防范措施
- (人力资源管理专科)毕业论文
- 刮板链式运输机三级圆锥齿轮减速器设计
- 解读(2025年版)输卵管积水造影诊断中国专家共识
- (正式版)DB50∕T 1879-2025 《刨猪宴菜品烹饪技术规范》
- 高职院校技能大赛指导手册
评论
0/150
提交评论