版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
河北工程大学函授毕业设计(论文)河北工程大学函授毕业设计(论文)题 目:110kV变电站电气一次初步设计学 院:专 业:班 级:姓 名:学 号:指导教师:2014年4月7日I河北工程大学函授毕业设计(论文)目录前言······················································································(1)第一部分110kv变电站电气一次部分设计说明书第1章建站依据及必要性·······················································(2)第2章负荷情况分析(2)····························································第3章电气主接线设计···························································(3)第4章短路电流计算······························································(8)第5章电气设备的选择(9)第6···························································章防雷保护与接地系统设计(12)···········································第7章主变压器容量、台数及形式的选择······························(13)第8章变电所总体布置····························································第二部分110kv变电站电气一次部分设计计算书第1章负荷计算··································································(15)第2章短路计算··································································(16)结束语致 谢
································································································································································(22)参考文献···············································································(23)附 录附录一 电气主接线图附录二 变电站平面布置图附录三 进线剖面图附录四 出线剖面图附录四 防雷保护及接地系统图II河北工程大学函授毕业设计(论文)III河北工程大学函授毕业设计(论文)前 言变电站是电力系统的重要组成部分,由电器设备及配电网络按一定的接线方式所构成,他从电力系统取得电能,通过其变换、分配、输送与保护等功能,它直接影响整个电力系统的安全与经济运行然后将电能安全、可靠、经济的输送到每一个用电设备的场所。110KV变电站属于高压网络,电气主接线是发电厂变电所的主要环节,电气主接线直关系着全厂电气设备的选择、是变电站电气部分投资大小的决定性因素。首先,根据主接线的经济可靠、运行灵活的要求选择各个电压等级的接线方式来选择。根据主变容量选择适合的变压器,主变压器的台数、容量及形式的选择是很重要,它对发电厂和变电站的技术经济影响大。本变电所的初步设计包括了:(1)建站依据、必要性分析( 2)负荷分析(3)短路电流的计算(4)电气主接图设计(5)主要设备选择与校验(6)防雷保护与接地保护等内容(7)站变的选择(数量、容量、型式、接线)的分析。[ 关键词]变电站、变压器、接线、高压网络、配电系统1河北工程大学函授毕业设计(论文)第一部分110kv变电站电气一次部分设计说明书第1章 建站依据、必要性1、1原始资料(1)建站规模变电站类型:110kV降压变电站电压等级:110kV/35kV/10kV系统情况:(1)110kV侧:2回,系统侧双回,容量无穷大,COSΦ=0.85,至变电站阻抗标么值0.3(SB=100MVA),电厂侧双回,容量941MVA,至变电站阻抗标么值0.2(SB=100MVA),母线穿越容量211.7MVA;(2)系统110kV母线电压满足常调压要求。(2)环境条件:地质概况:碳酸盐褐土(砂质粘土),土壤电阻率ρ=102Ω·m(2)气象、水文资料:海拔高度:100m,超过该地区百年一遇洪水位:全年最高月平均温度 26.2℃,全年最低月平均温度 1.4℃,年平均温13.7℃,相对湿度60%;地震级:7级,全年平均降水量:200∽300mm;雷电活动情况:少雷区,但该站位置相对较高。第2章负荷情况分析2.1负荷类型分析各类负荷对供电的要求:一类负荷为重要负荷,必须由两个或两个以上的独立电源供电,当任何一个电源失去后,能保证全部一级负荷不间断供电。二类负荷为比较重要负荷,一般要由两个独立电源供电,且当任何一个电源失去后,能保证二级负荷的供电。三类负荷一般指需要一个电源供电的负荷。本设计负荷情况:35kV侧:5回(架空线),Ⅰ、Ⅱ回用于企业用电,总容量63×2MVA,其中一类负荷容量50.82MVA,TMAX=6000h,COSΦ=0.85;Ⅲ回用于一般工业用电,容量40MVA,2河北工程大学函授毕业设计(论文)TMAX=5000h,COSΦ=0.85;Ⅳ回用于农业用电,容量 21.18MVA,TMAX=4000h,COSΦ=0.85;10kV侧:12回(电缆);380V侧站用电总容量 0.73MVA(按输送容量的 0.5%计算)第3章电气主接线的设计3.1电气主接线的设计原则电气主接线设计的基本原则为:严格按照技术规定和标准,结合工程实际的具体特点,准确地掌握原始资料,保证设计方案的可靠性、灵活性和经济性。3.2对主接线设计的基本要求主接线应满足经济性、可靠性、灵活性和发展性等四方面的要求。1.经济性。方案的经济性体现在以下几个方面。(1)投资省。主接线要力求简单,以节省一次设备的使用数量 .占地面积小。直接影响到整个配电装置的占地面积。电能损耗小。经济合理地选择变压器的类型发展性。在不影响连续供电的情况下,完成过度期的扩建,且对一次和二次部分的改动工作量最少。可靠性。主接线的可靠性不仅包括开关、母线等,继电保护、自动装置等。灵活性。电气主接线的设计,应适合在运行、热备用、冷备用和检修等各种方式下的运行要求。3.3本设计变电站的主接线方式拟定可行的主接线方案 2种,内容包括主变的形式,台数以及各级电压配电装置的接线方式等,并依据对主接线的基本要求,保留一种较好的方案。110kv侧的接线方案(一)单母线分段接线段 段图3.13河北工程大学函授毕业设计(论文)分段的单母线的评价为:优点具有单母线接线简单、经济、安全等优点。运行比较灵活。缺点a.任一分段母线或母线隔离开关检修或故障时,连接在该分段母线上的所有进出回路都要停止工作。检修任一电源或出线断路器时,该回路必须停电。方案(二)不分段的双母线段段双母线接线图3.2双母线接线的特点:可轮流检修母线而不影响正常供电。检修任一母线侧隔离开关时,只影响该回路供电。以上二种方案比较:方案(一)主接线供电可靠性与灵活性高,用于110KV,出线回路适合本站设计,因此此方案可行。方案(二)多用于电源较多、输送和穿越功率较4河北工程大学函授毕业设计(论文)大的场合。因此此方案不可行。故110kv侧应采用方案(一)的接线。35kv侧的接线方案(一) 单母线分段接线段段图3.3对用断路器分段的单母线的评价为 :优点具有单母线接线简单、安全等优点。较之不分段的单母线供电可靠性高。缺点任一分段母线或母线隔离开关检修或故障时,连接在该分段母线上的所有进出回路都要停止工作检修任一电源或出线断路器时,该回路必须停电。方案(二) 内桥接线图3.45河北工程大学函授毕业设计(论文)内桥接线的特点为:线路操作方便。如线路发生故障,仅故障线路的断路器跳闸,其余三回路可继续工作,并保持相互的联系。正常运行时变压器操作复杂。以上二种方案比较:方案(一)虽此主接线供电可靠性与灵活性高,此方案适合出线回路比较多的,因此此方案可行。 方案(二)两回进线,两回出线,但此方案适合 出线较多,因此方案不可行。故35kv侧应采用方案(一)的接线。10kv侧的接线采用单母线分段接线段 段图3.5优点具有单母线接线简单、安全等优点。供电可靠性高。母线或母线隔离开关短路时,非故障母线段可以实现完全不停电。缺点a.任一分段母线或母线隔离开关检修或故障时,连接在该分段母线上的所有进出回路都要停止工作。分析可知本方案符合本站设计所须的可靠性与经济性的要求,所以 10kv侧采用单6河北工程大学函授毕业设计(论文)母线分段接线方式。由以上分析比较,可得变电站的主接线方案为: 110KV采用单母分段接线,35KV采用单母分段接线,10KV采用单母分段接线变电站主接线图见附录。第4章短路电流的计算4.1 短路的基本知识短路从根本意义上讲就是供配电系统中一相或多相载流导体接地及相线与相线接触并产生大电流其值远超出规定值。短路电流的大小是比较主接线方案,分析运行方式时必须考虑的主要因素。系统发生短路故障时产生电压降低,靠近短路点处更为严重,这直接影响危害用户供电的可靠性及其安全性。本设计110KV变电站中的各种电气装置设备应能承受短路电流的冲击, 勿使设备过热及电动力的作用造成装置破坏。因此,在设计中充分考虑了各种细节,例如:电流互感器的过电流倍数留有足够的冗余;必须依据短路电流实验结果来选择接地装置的选择。综上所述,短路电流的计算是变电所一次电气部分设计的前提。4.2 短路电流计算的目的选择电气设备。电气设备必须具有充分的电动力稳定性和热稳定性,而电气设备的电动力稳定性和热稳定性的效验是以短路电流计算结果为依据的。(1)继电保护的配置和整定。(2)电气主接线方案的比较和选择。由经验表明,在各种类型的短路中,单相短路占绝大多数,两相短路其次,三相短路的机会最为罕见。但三相短路虽然很少发生,其情况较严重。故本设计都采用三相短路来计算短路电流,并检验电气设备的安全性与稳定性。4.3短路电流计算的内容(1)短路点的选取:各级电压母线、各级线路末端。(2)短路时间的确定:根据电气设备选择和继电保护整定的需要,确定计算短路电流的时间。(3)短路电流的计算:最大运行方式下最大短路电流;最小运行方式下最小短路电流;各级电压中性点不接地系统的单相短路电流。7河北工程大学函授毕业设计(论文)4.4短路电流计算的步骤1)计算各元件电抗标幺值,并折算为同一基准容量下;2)给系统制订等值网络图;3)选择短路点;4)对网络进行化简,把供电系统看为无限大系统5)计算短路容量,短路电流冲击值短路容量:S= 3UjI短路电流冲击值:ish=2.55I6)列出短路电流计算结果7)具体短路电流计算见计算说明书第5章设备的选择与校验.1电气设备选择的一般条件正确地选择设备是使电气主接线和配电装置达到安全、经济运行的重要条件。在进行设备选择时,应根据工程实际情况,应保证安全、可靠。电气设备要能可靠的工作,必须按正常工作条件进行选择,并按短路状态来校验其热稳定和动稳定。5.2按短路情况校验㈠短路热稳定校验短路电流通过时,导体和电器各部件温度(或发热效应)应不超过允许值,既满足热稳定的条件为:Qd Qr 或I2tjz Ir2t式中 Qd——短路电流产生的热效应;Qr——短路时导体和电器设备允许的热效应;Ir——时间t内允许通过的短时热稳定电流(或短时耐受电流) 。㈡电动力稳定校验电动力稳定是导体和电器承受短路电流机械效应的能力。满足动稳定的条件是:ich idw 或 IchIdw式中 ich、Ich——短路冲击电流幅值及其有效值;idw、Idw——允许通过稳定电流的幅值和有效值。5.3 断路器的选择一般6~35kV选用真空断路器,10kV侧的断路器都采用真空的断路器, 35~500kV宜8河北工程大学函授毕业设计(论文)选用SF6断路器,本变电站设计中110kV和35kV断路器均采用SF6断路器。5.3.1110kV侧断路器的选择(1)预选SFM110-110/2000的断路器(2)额定电压的选择为:Ue110KVUew110KV(3)额定电流的选择为:Imax=PnSn=250=0.527KA,故:Ie2000A527A=1.053Uaccos3Uac3115(4)额定开断电流的检验条件为: It=I″=4.39KA Iek 31.5KA动稳定的校验条件:ich9.87idw80KA110KV则短路电流热稳定电流为:QdtI2tima4.3920.6312.14KA2sQrIt2t31.5232976.75KA2s故:QKA2s2Q12.14KAsrdtSFM110-110/2000的断路器,可满足技术条件要求 侧断路器的选择(1)预选LW8-40.5的断路器(2)额定电压的选择为:Ue35KVUew35KV(3)额定电流的选择为:Imax=Pn=Sn=38.281.05=0.628KA,故:Ie1600A628A3Uaccos3Uac337(4)额定开断电流的检验条件为:It=I″=7.29KAIek25KA动稳定的校验条件:ich16.40idw63KA110KV则短路电流热稳定电流为:QdtI2tima7.2920.6333.48KA2sQrIt2t25242500KA2s故:QKA2sQ33.48KA2srdtLW8-40.5的断路器,可满足技术条件要求 侧断路器的选择(1)预选ZN12-10的断路器(2)额定电压的选择为:Ue10KVUew10KV(3)额定电流的选择为:PnSn=11.21.05=0.648KA,故:Ie1250A648AImax==3Uaccos3Uac310.5(4)额定开断电流的检验条件为:It=I″=19.37KAIek31.5KA9河北工程大学函授毕业设计(论文)动稳定的校验条件:ich43.58idw80KA110KV则短路电流热稳定电流为:QdtI2tima19.3720.63236.37KA2sQrIt2t31.5243969KA2s故:QKA2sQ236.37KA2srdtZN12-10的断路器,可满足技术条件要求5.4 隔离开关的选择隔离开关的用途:(1)倒闸操作,投入备用母线或旁路母线以及改变运行方式时,常用隔离开关配合断路器,协同操作来完成。(2)隔离电压,在检修电气设备时,用隔离开关将被检修的设备与电源电压隔离,以确保检修的安全。(3)分、合小电流。隔离开关的型式应根据配电装置的布置特点和使用要求等因素,进行综合的技术、经济比较,再根据其校验计算结果后确定。 侧隔离开关的选择(1)预选GW4-110\2000的隔离开关(2)额定电压的选择为:Ue110KVUew110KV(3)额定电流的选择为:Imax=Pn=Sn=2501.05=0.527KA,故:Ie1250A527A3Uaccos3Uac3115动稳定的校验条件:ich9.87idw50KA110KV则短路电流热稳定电流为:QdtI2tima4.3920.6312.14KA2sQrIt2t20241600KA2s故:Qr1600KA2sQdt12.14KA2s根据上述计算110kV可选用:GW4-110\2000的隔离开关,可满足技术条件要求。 侧隔离开关的选择(1)预选GW4-35\1250的隔离开关(2)额定电压的选择为:Ue35KVUew35KV(3)额定电流的选择为:Imax=Pn=Sn=38.281.05=0.628KA,故:Ie1250A628A3Uaccos3Uac337动稳定的校验条件:ich16.4oidw50KA110KV则短路电流热稳定电流为:10河北工程大学函授毕业设计(论文)QdtI2tima7.2920.6333.48KA2sQrIt2t20241600KA2sQr1600KA2sQdt33.48KA2s根据上述计算35kV可选用:GW4-35\1250的隔离开关,可满足技术条件要求。 侧隔离开关的选择1)预选GN2-10\2000的隔离开关2)额定电压的选择为:Ue10KVUew10KV3)额定电流的选择为:Pn=Sn=11.21.05=0.648KA,故:Ie2000A648AImax=3Uac310.53Uaccos动稳定的校验条件:ich43.58idw85KA110KV则短路电流热稳定电流为:QdtI2tima19.3720.63236.37KA2sQrIt2t36245184KA2s故:QKA2sQdt236.37KA2sr根据上述计算10kV可选用:GN2-10的隔离开关,可满足技术条件要求。第6章 防雷与接地方案的设计6.1 防雷保护直击雷保护直击雷过电压:雷电直接击中电气线路、设备或建筑物而引起的过电压,又称直击雷。在雷电的主放电过程中,其传播速度极快(约为光速的 50%-10%),雷电压幅值达10-100MV,雷电流幅值达数百千安,伴以强烈的光、热、机械效应和危险的电磁效应以及强烈的闪络放电,具有强烈的破坏性和对人员的杀伤性。110KV配电装置、主变压器为户外布置、采用在构架上设置 2支避雷针,及其余设备均为户内布置,采用配电楼屋顶设避雷带,和避雷针联合作为防直击雷保护,确保户外主变压器、110KV配电装置在其联合保护范围内。避雷带采用Ф16的热镀锌圆钢,避雷针与建筑物钢筋隔离,并采用3根引下线与主接地网相连接,连接点与其他设备接地点的电气距离应满足规范要求。 侵入波保护雷电波入侵(高电位侵入):架空线路遭受雷击或感应累的影响,在线路上形成沿线路传播的高电压行波.此种电压波入侵到建筑物内或进入电气设备造成过电压。据统计城市中雷击事故的 50%-70%是由于这种雷电波侵入造成的。 因此,在工厂中应予以重视,11河北工程大学函授毕业设计(论文)对其危害给予足够的防护。为防止线路侵入雷电波的过电压,在110KV进线,10KV母线桥及10KV每段母线上分别安装氧化锌避雷器。为保护主变压器中性点绝缘,在主变110KV侧中性点装设氧化锌避雷器。10KV并联电容器根据规定装设氧化锌避雷器保护。 变电所进线段保护虽然变电所 110kV出线采用全线保护,但为了减少临近变电所 1-2KM内雷电的绕击和反击,应考虑变电所的进线段保护,在进线段装设管型GXS避雷器。管型GXS避雷器作用:DL在开断状态,又有雷电波入侵时,由于反击电压上升到 2U50%,使断路器或隔离开关绝缘对地放电而引起短路。对10kV电缆出线采取电缆外壳接地,架空线路在进线上装设一组FS-10型避雷器。第7章主变压器容量、台数及形式的选择7.1 概述发电厂中用来向电力系统或用户输送电能的变压器成为主变压器(简称主变) ,其中用于沟通两个升高电压等级并可相互交换功率的变压器称为联络变压器, 而只供发电厂本身用电的变压器则称为厂用变压器。主变的容量、台数直接影响主接线的形式和配电装置的结构。它的选择除依据基础材料外,主要取决与输送功率的大小、与系统联系的紧密程度、运行方式等因素,并至少要考虑5~10年规划负荷的发展需要。要合理选择变压器的容量、台数和形式。7.2 主变压器台数的选择为了保证供电可靠性,避免一台主变压器故障或检修时影响供电,发电厂中一般装设两台主变压器。考虑到两台主变同时发生故障机率较小。适用远期负荷的增长以及扩建,而当一台主变压器故障或者检修时,另一台主变压器可承担 70%的负荷保证全变电站的正常供电。故选择两台主变压器互为备用,提高供电的可靠性。7.3 主变压器容量的选择主变容量一般按发电厂建成近期负荷, 5~10年规划负荷选择,对于重要负荷的变电站,应考虑当一台变压器停运时,其余变压器容量在过负荷能力后允许时间内,应保证用户的一级和二级负荷,对一般性能的变电站,当一台主变压器停运时,其余变压器容量应保证全部负荷的 70%~80%。该变电站是按70%全部负荷来选择。因此,装设两台变压器变电站的总装容量为:∑ se=2(0.7PM)=1.4PM。7.4 主变压器型式的选择(1)绕组数的确定最大机组容量为125MW及以下的发电厂,当有两种升高电压向用户供电或与系统连接时,宜采用三绕组变压器,但每个绕组的通过容量应达到该变压器额定容量的 15%及以上。否则绕组未能充分利用,反而不如选择两台双绕组变压器合理。调压方式12河北工程大学函授毕业设计(论文)通过主变的分接开关切换,改变变压器高压侧绕组匝数。从而改变其变比,实现电压调整。通常发电厂主变压器可以通过调节发电机励磁来实现调节电压, 一般均采用无激磁调压。3)冷却方式主变压器一般采用的冷却方式有:自然风冷却,强迫油循环风冷却,强迫油循环水冷却。自然风冷却:一般只适用于小容量变压器。强迫油循环水冷却,虽然散热效率高,节约材料减少变压器本体尺寸等优点。但它冷却器的密封性能要求高,维护工作量较大。所以,选择强迫油循环风冷却。综上所述并且根据工厂的负荷性质和电源情况,工厂变电所的主变压器考虑有下列两种可供选择的方案: 1)装设一台变压器:主变压器的容量 ST满足:SN.T≥S’30,一般取S30=(0.85~0.9) S’30(2)=874.1~925.5 kVA。因此选用1000 kVA的变压器一台,型号选 SC9-1250/10 Dyn11。 2)装设两台变压器:型号选 SL7,而每台变压器容量根据下面两式选择 SN.T ≈(0.6~0.7)*925.5=(555.3~647.85) kVASN.TS30(X)=(134.29+165+44.4)=343.7kVA因此单台变压器的容量为630kVA。因此变压器型号为SC9-630/10,并采用Dyn11接法,且两台变压器并列运行13河北工程大学函授毕业设计(论文)第二部分110kv变电站电气一次部分计算书第一章 主变压器负荷计算电力系统负荷的确定,电力负荷应在调查和计算的基础上进行。负荷计算的方法有需要系数法、二项式等几种,本设计采用需要系数法确定。 主要计算公式有:有功功率:PC=Kd?PN无功功率:QC=PC?tanφ视在功率:SC=PC/cosφ计算电流:IC=SC/UN站负荷情况电源:系统侧:双回路,容量:无穷大,供电电压: 110KV, =0.85,至变电站阻抗标幺值:0.3(SB=100MVA)电厂侧:双回路,容量:941MVA,供电电压:110KV, =0.85,至变电站阻抗标幺值:0.2(SB=100MVA)母线穿越容量:211.7MVA:10-2、出线:110KV侧,4回路Ⅰ、Ⅱ回路(企业用电)总容量 84.7MVA,其中一类负荷容量 50.82MVA;Tmax=6000小时, =0.85;Ⅲ回(一般工业用电)容量 40MVA,Tmax=5000小时, =0.85;Ⅳ回(农业用电)容量21.18MVA,Tmax=4000小时, =0.85;380V侧:(站内用电)总容0.73MVA(按输送总量的 0.5%计算),采用动力和照明共的三相四线制系统14河北工程大学函授毕业设计(论文)第二章 短路电流的计算查资料可知,架空线电抗X一般取为0.4Ω/km.选基准:SB=100MVAUB=Uav110kv侧:SBUB)=0.502KA/(310kv侧:SBUB)=5.499KA/(3取基准容量为SMVA基准电压为UBUav,又依公式:B100,SB;XBUB2。计算出基准值如下表1-1所示:IB3UBSBSB100MVA表1-1基准值UB(KV)1153710.5IB(KA)0.5521.7166.048XB()120.2312.451.002.1 计算变压器电抗Uk1%1Uk(12)%Uk(31)%Uk(23)%211710.56.52=10.51Uk2% Uk(12)% Uk(23)% Uk(31)%21176.510.52=6.5Uk3%1Uk(31)%Uk(23)%Uk(12)%215河北工程大学函授毕业设计(论文)1176.510.52=0XXX
*Uk1%SB10.51000.21T1100SN10050*Uk2%SB6.51000.13T2100SN10050*Uk3%SB01000T3100SN100502.2 系统等值网络图系统等值网络图如下图 1-1所示:图1-1 系统等值网络图2.3 短路计算点的选择选择上图中的d1、d2、d3、d4、d5各点。2.4 短路电流计算[2][6][7](1)d1点短路时(如图1-2所示):Uav 37KA次暂态短路电流标幺值的计算:16河北工程大学函授毕业设计(论文)''11.0I*I*1.13X1*0.888次暂态(0s)和4s时的短路电流相等,三相短路电流有名值为:I''I*''SB3Uav1.13100337)1.76KA(两相短路电流为:0.8661.761.52KA冲击电流为:ishI''2.551.76KA2.554.49短路容量为:SUI''3MVA3B371.76112.79Ish1.51I''1.511.762.66KA图1-2 d1点短路时的系统网络等值简化(2) d2点短路时(如图 1-3所示):Uav 10.5KA17河北工程大学函授毕业设计(论文)图1-3 d2点短路时的系统网络等值简化次暂态短路电流标幺值的计算:''11.00.8231.22I*I*X2*次暂态(0s)和4s时的短路电流相等,三相短路电流有名值为:I''I*''SB1.221006.71KA3Uav(310.5)两相短路电流为: 0.866 6.71 5.81KA冲击电流为:ishI''2.556.71KA2.5517.11短路容量为:SUBI''MVA3310.56.71122.03Ish1.51I''1.516.7110.13KA(3)d3点短路时(如图1-4所示):Uav115KA18河北工程大学函授毕业设计(论文)图1-4 d3点短路时的系统网络等值简化次暂态短路电流标幺值的计算:''11.00.7861.27I*I*X3*次暂态(0s)和4s时的短路电流相等,三相短路电流有名值为:I''I*''SB1.271000.64KA3Uav(3115)两相短路电流为: 0.866 0.64 0.55KA冲击电流为:ishI''2.550.643.98KA2.55短路容量为:SUI''31150.64127.48MVA3BIsh1.51I''1.510.640.97KA(4)d4点短路时(如图1-5所示):Uav37KA19河北工程大学函授毕业设计(论文)图1-5 d4点短路时的系统网络等值简化次暂态短路电流标幺值的计算:''11.00.9531.05I*I*X4*次暂态(0s)和4s时的短路电流相等,三相短路电流有名值为:I''I*''SB3Uav1.05100337)1.64KA(两相短路电流为:0.8661.641.42KA冲击电流为:ishI''2.551.64KA2.554.18短路容量为:SUI''3MVA3B371.64105.1Ish1.51I''1.511.642.48KA20河北工程大学函授毕业设计(论文)第8章 变电所总体布置1、总体规划变电所总体规划可协调所区与各级电压进出线的关系,所区的方向、朝向与进出线相配合,同时合理地安排所区、生活区、水源地、排出口等位置,合理选择所道路,解决变电所与城镇发展的矛盾。变电所的总体规划一般采用一次性规划,结合外部条件合理确定各级电压的出线方向,并有足够的出线走廓,尽量减少交叉跨越,当必须跨越时,电压等级高的出线在上侧。就近解决水源,为运输创造良好条件。2、总平面布置①、总平面布置的主要内容解决和协调全所建筑物、道路在平面布置上的相互关系和相对位置,主要有方向布置,管沟布置、道路、绿化及美化。②、总平面布置的基本原则(1)重视外部条件,发挥优势。(2)满足功能要求,布局合理。(3)布置紧凑合理,节约用地。(4)结合地形地势,因地制宜。(5)符合防为规定,确保安全。(6)注意风向朝向,有利环境。(7)便于巡视运输,路径短捷。(8)树立整体观念,协调美观。(9)适当留有余地,考虑发展。(10)方便检修和生活,安全运行。根据以上原则及要求,确定总平面布置图,具体布置见总平面布置图。21河北工程大学函授毕业设计(论文)结 束 语这次毕业设计,时间长、内容多,几乎覆盖了大学中所学的知识。我经过了从收集资料、设计、绘图、审核的整个过程。三个月的时间既充实又紧张。设计过程中,我获得了综合运用过去所学过的大部分课程进行设计的基本能力。变电站设计是一个思维创造与运用的过程,在这个过程中,我做到了学以致用,使设计思维在设计中得到锻炼和发展。在相关资料的帮助下,能结合自己的思路去设计。有许多地方是不懂的,但在老师的指导与帮助下得以解决。在设计期间,自己动手查看了大量的资料,一方面,充分地检查自己的设计能力,丰富了自己在电气设计特别是变电站设计方面的知识,为自己将来从事该专业打下了坚实的基础;另一方面,使我体会到搞设计或科研需要具备严谨求实、一丝不苟和勇于献身的精神。这次的设计,我最大的收获就是学到了变电站的设计步骤和方法,还
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 产品开发周期与成本KPI绩效衡量表
- 电视台节目制作团队制作绩效衡量表
- 第21课《陀螺》教学设计 试讲稿 说课稿(统编版语文四年级上册新教材)
- T/SDUWA 2002-2023城镇供水绿色水厂评价标准
- T/SDEC 001-2021山东省企业文化成果认定规范
- T/SCJA 17-2026机动车交通事故主动识别代码
- 电力工程师电力设备运行维护与安全性能评估绩效评定表
- 运动器材制造企业销售部经理绩效衡量表
- 飞机制造公司试飞员绩效考评表
- 墨水制造工岗前实操知识水平考核试卷含答案
- T/CAPA 16-2025医疗美容从业人员执业规范
- 大体积混凝土浇筑施工应急预案
- 四上《习作:我的心儿怦怦跳》课件
- 2026年中考生物一轮复习:人教版(2024)七八年级4册必背知识点提纲
- 2026年科研伦理与学术规范期末考试题库含完整答案详解(网校专用)
- 人教版七年级英语上册 Starter Unit 1 语音专项教学设计:字母与基础音素感知
- 外研版(三起)英语三年级上册教学课件unit 3 Part 1
- 交通设施拆除施工方案
- 配电网线路故障查找方法
- 哈里伯顿EZSV机械坐封工具操作规程
- 2025年消防中级面试题及答案
评论
0/150
提交评论