第一章变压器··························································································································7
第一节变压器的正常运行维护·······························································································7其次节无载分接开关调压本卷须知····················································································11第三节站用电系统的运行与维护························································································11第四节变压器的异常运行和事故处理················································································11
其次章断路器·························································································································16
第一节本站断路器的配置····································································································16其次节断路器的正常运行维护····························································································16第三节断路器的异常运行与事故处理················································································18
第三章隔离开关·····················································································································21
第一节隔离开关的正常运行维护························································································21其次节隔离开关的异常运行与事故处理············································································21
第四章母线的正常运行维护·······························································································22
第一节母线的正常运行维护································································································22其次节母线的异常运行及事故处理····················································································22
第五章互感器·························································································································25
第一节互感器的正常运行维护····························································································25其次节互感器异常运行及事故处理····················································································26
第六章电力电缆·····················································································································28第七章电力电容器·················································································································30
第一节电力电容器的正常运行维护····················································································30其次节电容器的异常运行与事故处理················································································31
第八章耦合电容器及阻波器的正常运行维护·································································32
第一节耦合电容器及阻波器的正常运行维护····································································32其次节耦合电容器及阻波器的异常运行与事故处理························································32
第九章过电压保护与接地装置···························································································33
第一节接地装置的正常运行维护························································································33其次节避雷器的异常运行与事故处理················································································33
第十章直流系统的运行和维护···························································································35
其次节直流系统异常处理····································································································36第三节碱性镉镍蓄电池组的运行维护················································································37
第十一章继电保护及二次部分···························································································40
第一节通则··························································································································40其次节异常运行及处理········································································································44
附录一本站开关型号及CT变比·····················································································46附录二微机保护动作信息表·····························································································47附录三本站主设备铭牌参数·····························································································49附录四本站典型操作票······································································································51附录五本站设备巡查图56
2
总则
本规程规定了漫水湾变电站的运行方式、操作规定、维护、事故及异常状况处理等方面的内容,本规程是指导漫水湾变电站变电运行的总则,本规程履行审批手续后执行。
第一节倒闸操作的有关规定
1倒闸操作的一般规定
1.1电气设备的倒闸操作必需严格遵守《电业安全工作规程》、《调度规程》和其它的有关规定。1.2倒闸操作必需先根据有关调度员的命令填写操作票(单一操作除外),并经审核合格后,由调度员下达操作命令后方能执行。
1.3值班员接到调度的命令后必需认真执行,受命人应对调度的命令有明白的了解,并即时大声复诵。如对调度命令有疑问或认为不正确时,应予指出,并向其作简要解释,如发令人确认自己的命令正确,并重复其命令时,受令人应马上执行;如执行该命令将要挟人身或设备安全时,受令人必需拒绝执行,并将拒绝的理由报告当值调度员和上级领导。
1.4执行倒闸操作时(包括单项操作),均应先进行模拟操作预演,核对检查操作无误后,再进行实际操作,操作中必需严格执行监护复诵制。
1.5检修设备送电前,运行人员必需对设备进行验收检查,同时要求检修工作负责人对设备的修、试、校工作做好完整的记录,并对设备能否运行下明确的结论,由运行值班人员(工作许可人)办理有关工作票的终结手续,拆除一切与该项检修工作有关的安全措施(调度下令的有关安全措施应按调度命令执行)。恢复固定遮栏及常设标示牌,对设备各连接回路进行检查,确认设备已具备受电条件后才能操作。
1.6以下各项工作可以不用操作票:1)事故应急处理。
2)单一操作(仅拉、合一台断路器、仅拉、合一组隔离开关、仅投退一块压板等)。3)拉开全站仅有的一组接地刀闸或拆除全站仅有的一组接地线上述操作在完成后应做好记录,事故应急处理应保存原始记录。2倒闸操作的基本原则2.1主变压器的操作
2.1.1变压器投入运行时,由高压侧进行充电,后送低压侧,停电与此相反。2.1.2新建或大修改造后的变压器,应核相无误后才能与其他变压器并列运行。2.1.3倒换变压器时,应检查投入变压器确已带上负荷后,才允许退出需停运变压器。2.2线路停、送电的操作
线路停电操作应先断开断路器,然后拉开线路侧隔离开关,再拉开母线侧隔离开关(无母线侧隔离开关可不进行该项操作);线路送电操作与此相反,严防带负荷拉合刀闸。2.3母线操作
2.3.1用断路器向母线充电前,应将母线电压互感器、避雷器、等先投入。2.3.2母线停电操作中,必需避免电压互感器二次侧向母线反充电。2.4断路器的操作
2.4.1一般状况下,凡远方合闸的断路器,不允许带工作电压手动合闸,以免合入故障回路使断路器损坏或引起爆炸伤人。
2.4.2断路器合闸前继电保护必需已按规定投入,同时检查控制回路,辅助回路均应正常,储能
1
机构已储能,即具备投运条件。
2.4.3遥控操作断路器时,应同时监视有关电压、电流、功率等表计的指示及红绿灯的变化;2.4.4电动合闸时扳动控制开关不要用力过猛,以防损坏控制开关,也不要返回太快(约有1秒的停顿),以防时间过短断路器来不及分、合闸。2.5隔离开关的操作
2.5.1合隔离开关时,该回路的断路器必需在断开位置,并经核对编号无误后,方可操作。2.5.2手动操作隔离开关合闸时,应迅速果断,但在合闸终了不得有冲击,即使合入接地或短路回路也不得再拉开。拉闸时,应慢而提防,特别是动、静触头刚分开时,如发现弧光,应迅速合上,中止操作,查明原因。但在切断空载变压器、空载线路、空载母线等时,应快而果断,促使电弧迅速熄灭。
2.5.3分相操作的隔离开关(高压跌落式熔断器),拉闸时先拉中相,后拉边相;有风时,先拉中相,后拉下风相,最终拉上风相,合闸操作相反。
2.5.4当回路中未装断路器时,允许使用隔离开关进行以下操作:
A、拉、合无故障的电压互感器和避雷器(天气正常、系统无接地故障时);拉、合空载母线和直接连接在母线上设备的电容电流;
B、拉、合变压器中性点的接地线,但当中性点接有消弧线圈时,只有在系统没有接地故障
时才可进行;
C、拉、合与开关并联,且开关在合闸位置下的旁路电流(此时必需断开该开关的控制电源);D、拉、合励磁电流不超过2A的空载变压器和电容电流不超过5A的无负荷线路;但当电
压不小于20kV时,应使用屋外垂直分合式的三联隔离开关。E、用室外三联刀闸可拉、合10KV以下,电流不超过15A的负荷电流;F、拉、合10KV以下,电流不超过70A的环路均衡电流。2.5.5以下状况阻止用刀闸进行操作:
1.切断有故障的电压互感器;
2.切断超过规定值的环路电流和励磁电流;3.切断各级电压的单相接地故障;4.系统有接地故障时,拉、合电压互感器。2.6验电、挂接地线的操作2.6.1验电操作的本卷须知
a、高压验电,必需戴绝缘手套,雨雪天气时不得进行室外直接验电;
b、验电时,必需用电压等级适合而且合格的验电器,在检修设备进出线两侧各相分别验电。
验电前,应先在有电设备上进行试验,确证验电器良好。试验验电器时,不必直接接触带电导体,寻常验电器明了发声光报警电压不大于额定电压的25%,因此完好的验电器只要靠近带电体(10、35KV系统分别约为250、500mm),就会发声光报警;
c、验电操作,要态度认真,战胜可有可无的思想,避免因走过场而流于形式,要把握正确
的判断方法和要领。验电时,验电器要渐渐地接近验电设备,正常有电时,验电器靠近带电体,就会发声光报警。(对于静电和感应电,验电器靠近验电设备时,不会发声光报警,直到与设备接触后,有时才发声光报警。)
2
2.6.2挂、拆接地线操作的本卷须知
挂接地线操作除严格遵守《电业安全工作规程》的有关规定外,还应注意以下几点:a、
挂、拆接地线,操作人员必需戴绝缘手套,穿绝缘靴,身体的任何部位都不得接触接地线,以免受感应电压的伤害;
b、装设接地线必需先接接地端,后接导体端,地线的接地端必需接在接地网的接头上,不
得接在设备构架上或断路器、隔离开关的传动杆上;
c、所挂接地线必需与带电设备保持足够的安全距离,又不要与检修设备及工作人员靠得太
近,地线已拆除的设备应视为带电设备,不得再用手去触摸。
2.7投退电压互感器操作
2.7.1操作将电压互感器退出运行时,应先取下二次保险,再拉一次刀闸,投入时顺序相反。2.7.2正常运行时,一段母线上的电压互感器需退出时,而二次负荷由另一段母线的电压互感器供电的操作如下:
2.7.2.1操作前如两段母线上的电压互感器都投运各带一段负荷时(母联开关可能在合上或分闸位置),由切换开关切换二次回路前,应先将电压互感器一次并列(即该电压等级的分段开关及两侧刀闸在合上位置),再投入切换开关(切换开关扳到通位置),检查两段母线的三相电压表一致,切换中间继电器励磁正常,然后再按停用电压互感器的要求,退出待停的电压互感器。恢复时应按顺序投入电压感器检查电压正常后,方可断开切换开关(切换开关扳到断位置),两段电压互感器分别各带一段负荷运行。
2.7.2.2操作前如另一段母线电压互感器在停运状态时,这时该电压等级的分段开关及两侧刀闸一定在合上位置,切换开关已在通位置,这时操作只需投入另一段母线的电压互感器(合上刀闸和投入二次保险),检查无误后,退出需停运的电压互感器即可。
2.7.3一段母线上的电压互感器因故障需退出运行时,应先将故障电压互感器退出运行后,才由切换开关切换二次回路,二次负荷由另一段母线的电压互感器供电。此时需注意:严禁就地用隔离开关拉开有故障(油位异常升高、喷油、冒烟、内部放电等)的电压互感器。
2.7.4两段母线的电压互感器同时投入运行时,电压切换开关应在断开位置。2.7.3、2.7.4条作为参考。
2.8继电保护及安全自动装置的投入、停用的一般原则
a、设备正常运行时,应按有关规定投入其继电保护及安全自动装置,在倒闸操作时,一次
设备运行方式的改变对继电保护动作特性、保护范围有影响,应考虑将其继电保护运行方式、定值作相应调整(需报告当值调度同意后方可执行)。继电保护、二次回路因故障影响保护装置正确动作时,应将相应的继电保护退出运行。
b、投入继电保护时,应先投入保护装置的电源并检查该装置运行正常,再投入保护出口压
板,退出保护时相反。其目的是防止投、退保护时引起保护误动作。
其次节设备异常运行和事故处理
1设备异常运行和事故处理的基本原则1.1事故处理的主要任务是:
a、尽速限制事故发展,消除事故的根源并解除对人身和设备安全的要挟;
3
g、瓦斯继电器内无充气、卡涩现象;
h、有载调压分接开关位置指示正确,手动、电动调压无卡涩现象;i、压力释放器试验应符合安规要求。j、继电保护定值及压板位置应符合要求。4.2变压器并联运行应满足以下条件:
a、绕组接线组别一致;
b、二次侧电压分别对应相等,允许差值不应超过±0.5%;c、阻抗电压值相等,允许相差不应超过10%;d、容量比不超过3︰1。
本站两台变压器完全满足以上条件,可长期并列运行,并列运行时注意两台变压器的分接开关的档位应一致。5变压器的运行及维护
5.1变压器经过空载试运行后,未发现有异常现象,变压器便可以正式投入运行。5.2变压器的维护
5.2.1变压器运行的第一个月,应取油样进行耐压击穿试验,若油的耐压值比出厂试验值下降15-20%时,此时,油应进行过滤;在滤油过程中,若滤纸表面滞留有黑色的碳化物,必需进行器身检查,检查的要求与程序和验收器身检查一样,查出故障点,及时排除。
5.2.2对运行中的变压器,取油样进行色谱分析。分析油中气体的成分及含量,由此来判断变压器有无故障及故障性质。若从油中气体含量来判断暂不会危险变压器的安全运行时,变压器可继续运行,但必需随时加强监视。若故障严重时必需采取措施,作出处理决定。5.2.3事故放油
变压器下节油箱上装有事故放油阀,若发生事故必需紧急放油时,马上开启事故放油阀将变压器油放出。6变压器的巡查
6.1变压器的正常巡查检查项目:
a、变压器的油温柔温度计应正常,储油柜的油位应与温度相对应,各部位无渗油、漏油;b、套管油位应正常,套管外部无破损裂纹、无严重油污、无放电痕迹及其它异常现象;c、变压器音响正常;
d、各冷却器手感温度应相近,风扇运转正常;e、吸湿器完好,吸附剂枯燥;
f、引线接头、电缆、母线应无发热迹象;
g、压力释放器、应完好无损;主变端子箱是否密封严密,是否枯燥、清白。h、有载分接开关的分接位置及电源指示应正常;i、气体继电器内应无气体;
j、各控制箱和二次端子箱应关严,无受潮;6.2变压器的特别巡查:
出现以下状况之一,值班人员应对变压器进行特别巡查,增加巡查次数。a、新设备或经过检修、改造的变压器在投运72h内;
9
b、有严重缺陷时;
c、气象突变(如大风、大雾、大雪、冰雹、寒潮等)时;d、雷雨季节特别是雷雨后;e、高温季节、高峰负载期间;f、变压器急救负载运行时。7变压器的允许运行方式7.1正常周期性负载的运行:
7.1.1变压器在额定使用条件下,全年可按额定容量运行。
7.1.2油浸自冷、风冷式变压器顶层油温最高不超过95?C,一般不宜经常超过85?C;当冷却介质温度较低时,顶层油温也相应降低,温升不超过55?C,当上层油温未超过55?C及负荷未超过无风吹容量规定时(额定负荷的70%左右),可不开风扇运行,主变温度达55?C时自动启动风扇运行,若自动不能启动时应手动启动风扇运行。
7.1.3变压器的运行电压一般不应高于该运行分接额定电压的105%。对于特别的使用状况(例如变压器的有功功率可以在任何方向流通),允许在不超过110%的额定电压下运行,对电流与电压的相互关系如无特别要求,当负载电流为额定电流的K(K≤1)倍时,按以下公式对电压U加以限制
U(%)?110?5K2
7.2长期急救周期性负载的运行:
7.2.1长期急救周期性负载下运行时,将在不同程度上缩短变压器的寿命,应尽量减少出现这种运行方式的机遇;必需采用时,应尽量缩短超额定电流运行的时间,降低超额定电流的倍数,有条件时按制造厂规定投入备用冷却器。
7.2.2当变压器有较严重的缺陷(如冷却系统不正常,严重漏油,有局部过热现象,油中溶解气体分析结果异常等)或绝缘有弱点时,不宜超额定电流运行。7.3短期急救负载的运行:
7.3.1短期急救负载下运行,相对老化率远大于1,绕组热点温度可能达到危险程度。在出现这种状况时,应投入包括备用在内的全部冷却器(制造厂另有规定的除外),并尽量压缩负载、减少时间,一般不超过0.5h。当变压器有严重缺陷或绝缘有弱点时,不宜超额定电流运行。7.3.20.5h短期急救负载允许的负载系数K2见表1-1
表1-10.5h短期急救负载的负载系数K2表急救负载变压器类型前的负载系数K10.7配电变压器(冷却方式ONAN)0.80.91.01
环境温度℃401.951.901.841.751.65302.002.001.951.861.80202.002.002.002.001.9010
102.002.002.002.002.0002.002.002.002.002.00-102.002.002.002.002.00-202.002.002.002.002.00-252.002.002.002.002.00
1.20.7中型变压器(冷却方式ONAN或ONAF)
0.80.91.01.11.21.551.801.761.721.641.541.421.681.801.801.801.751.661.561.841.801.801.801.801.781.701.951.801.801.801.801.801.802.001.801.801.801.801.801.802.001.801.801.801.801.801.802.001.801.801.801.801.801.802.001.801.801.801.801.801.807.3.3在短期急救负载运行期间,应有详细的负载电流记录。
其次节无载分接开关调压本卷须知
1无载开关分接调整必需先停电,并作好安全措施后才能进行。
2在调整时,为了消除触头上的氧化膜和油污,须来回多切换几次,再调整到需要的位置。3在确认变换分接正确并锁紧后,测量绕组的直流电阻,三相应平衡。
第三节站用电系统的运行与维护
1站用变压器的巡查检查
站用变除参照主变压器巡查检查项目进行外,还应进行以下检查:a、检查高压侧跌落式保险接触是否良好,有无放电,打火或发热现象;b、检查交流屏各种仪表指示是否正确,低压总开关接触是否良好。
2本站的站用电取自10KV站变,其低压电源通过低压总刀闸,起动按钮控制交流接触器通断电源,其操作顺序如下:
a、合一台站变低压总刀闸(另一的低压总刀闸必需断开);b、检查电压表指示是否正常;c、起动对应站变起动按钮;d、合上各路负荷空气开关。
停运时其操作顺序与上述相反,严禁将两台站变并列运行。
3运行人员每月应对站用变压器定期切换一次,确保其在良好的工作状态。4站用电的异常及事故处理
4.1控制室、高压室、设备场地,均应有足够的正常照明,控制室和高压室应有事故照明,当正常运行的站用电全部失压时,应手动切换至备用电源上,以保证在正常操作和事故处理时有足够的照明。值班员应定期进行切换试验。
4.2站用电全站失压时,应马上判明失压原因,若因电网故障失压,待电网电压恢复后,马上恢复站用电;若是本站设备故障而造成站用电全站失压时,应首先尽快排除故障点,恢复站用电,站用电的恢复不待调度命令。
第四节变压器的异常运行和事故处理
1防止主变损坏的紧急措施
11
1.1当运行中的主变压器发生以下状况之一时应马上停运,若有运用中的备用变压器,应尽可能先将其投入运行:
a.变压器声响明显增大,很不正常,内部有爆裂声;b.严重漏油或喷油,使油面下降到低于油位计的指示限度;c.套管有严重的破损和放电现象;d.变压器冒烟着火。
1.2当发生危及变压器安全的故障,而变压器的有关保护装置拒动时,值班人员应马上将变压器停运。
1.3当变压器附近的设备着火、爆炸或发生其他状况,对变压器构成严重要挟时,值班人员应马上将变压器停运。2主变的不正常运行现象
2.1值班员发现变压器在运行中以下不正常现象,应马上汇报当值调度,听候处理,同时汇报有关部门,未采取有效措施之前应加强对主变压器的运行监视。
a、变压器温度不正常并不断上升;b、变压器过负荷超过标准;c、变压器套管有放电现象;d、引线接头有明显发红现象;
e、变压器内部有很不均匀的响声,温度不正常并不断上升;f、套管有裂纹及放电现象;
g、渗漏油严重致使油枕油位低于油位计上的最低限度;h、外壳和套管有严重渗油现象;i、引线接头有发热现象;
j、油色显著变化,油内出现炭质变色;k、轻瓦斯发出动作信号。2.2运行中的不正常现象
2.2.1值班人员在变压器运行中发现有不正常现象(如漏油、油位变化过高或过低、温度异常、音响不正常及冷却系统不正常等),应设法尽快消除,并汇报调度和有关领导,同时将经过状况记入运行记录簿和设备缺陷记录簿内。
2.2.3发现变压器有以下状况之一者,应加强监视,马上汇报值班调度,申请停电处理。状况紧急时先停电后汇报。
a、变压器内部声响很大,很不正常,有爆炸声;
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 2026年广东省深圳市高职单招职业适应性测试考试题库有答案详细解析
- 2026浙江事业单位统考台州市临海市招聘67人笔试模拟试题及答案解析
- 2026年应急管理部所属单位第二批次招聘笔试模拟试题及答案解析
- 2026陕西太白黄金矿业有限公司招聘(46人)笔试参考题库及答案解析
- 2026甘肃定西岷县十里镇卫生院招聘乡村医生2人笔试备考试题及答案解析
- 2026广东揭阳市榕城区登岗镇卫生院临时人员招聘1人笔试备考题库及答案解析
- 2026四川凉山州绿色家园安康医院招聘中医医师1人笔试模拟试题及答案解析
- 2026北京大学艺术学院招聘劳动合同制人员1人笔试备考题库及答案解析
- 2026浙江宁波市会展博览集团有限公司招聘1人笔试参考题库及答案解析
- 2026年四川省乐山市第七中学重点名校初三下学期第四次模拟考试卷英语试题理试卷含解析
- GB/T 8554-2026电子和通信设备用变压器和电感器测试方法和试验程序
- 考古发掘配合专项施工方案
- 2026年全国低压电工证(复审)考试笔试试题及答案
- 2026年六安职业技术学院单招职业适应性考试题库附答案详解(基础题)
- 船舶与海上设施起重设备规范-2007 含2016年第1次变更通告
- 第一章《三角形的证明》单元测试卷-2025-2026学年北师大版八年级数学下册
- (2026年春季新版本)人教版二年级数学下册全册教案
- 2026年3月时事政治及参考答案1套
- 2026年高考数学二轮复习策略讲座
- 2026年上交所期权从业考试基础巩固练习题及详细解析
- (新教材)2026年春期人教版一年级下册数学 第三单元 100以内数的认识 核心素养教案
评论
0/150
提交评论